IPCHS01 Power Chassis by ABB Bailey | MPS II IPCHS01
Manufacturer: ABB
Product No.: IPCHS01
Condition: In stock
Product Type: Power Module Chassis
Product Origin: USA
Payment: T/T, Western Union
Weight: 500g
Shipping port: Xiamen
Warranty: 12 months
Estimate delivery times: 12-26 days (International), 3-6 days (United States).
Return within 30 days of purchase. Duties & taxes are non-refundable.
Guaranteed Safe Checkout
ABB Bailey IPCHS01 Power Module Chassis
The ABB Bailey IPCHS01 is a power module chassis designed for the MPS II power system. It provides the mechanical mounting structure, power input connections, output bus bars, and terminal interfaces required for cabinet power distribution.
The chassis supports up to eight power modules and one central power monitor module. Its nine-slot arrangement places the monitor module in the center, with four power module positions on each side. Each side has isolated power inputs, while all power module outputs connect to a common output bus.
This architecture supports redundant power configurations and distributes regulated power to cabinet loads through the chassis backplane, bus bars, and terminal strips.
01 | Chassis Architecture and Slot Arrangement
| Position | Module Assignment | Function |
|---|---|---|
| Slots 1–4 | Power modules | Four power module positions on one side of the monitor slot |
| Slot 5 | IPMON01 | Dedicated central power monitoring position |
| Slots 6–9 | Power modules | Four power module positions on the opposite side |
Supported power module models:
- IPBLC01
- IPSYS01
- IPFLD01
- IPFLD24
- IPFLD48
- IPFLD125
Compatible power monitor: IPMON01.
02 | Electrical Capacity and Distribution
The IPCHS01 provides separate input paths and shared output distribution. The following ratings define the stated chassis capacity.
| Electrical Parameter | Rating |
|---|---|
| Input power capacity | 20 A maximum per side |
| 5.1 VDC output bus | 85 A maximum |
| ±15.1 VDC output bus | 15 A maximum |
| 25.5 VDC output bus | 85 A maximum |
| 49.1 VDC output bus | 12 A maximum |
| 125.6 VDC output bus | 12 A maximum |
Power distribution arrangement:
- Power module outputs share a common output bus.
- The backplane provides bus bars for cabinet power distribution.
- Terminal strips provide connections for ±15 VDC and 48/125 VDC outputs.
- Cables connect the bus bars and ±15 VDC terminals to the cabinet system power bus.
- The 48/125 VDC terminals serve as user output connections.
These figures are chassis bus capacity ratings. They should not be interpreted as the guaranteed output of every installed power module combination. Verify the actual load capability against the selected module ratings and system configuration.
03 | Power System Design and Availability
| Design Feature | Engineering Benefit |
|---|---|
| 2N redundancy | Supports a fully redundant power architecture when correctly configured. |
| N, N+1 and N+x arrangements | Allow power capacity and redundancy to match system requirements. |
| Active load sharing | Power modules share the system load to reduce uneven loading. |
| Power factor correction | Reduces upstream electrical distribution and UPS sizing pressure. |
| Redundant cooling fans | Provides continued cooling capability and supports online fan replacement. |
The MPS II input specifications list 60% efficiency at full rated load. Active power factor correction provides a minimum power factor of 0.95 when input current exceeds 0.5 A.
04 | Power Monitoring and System Feedback
When installed with the IPMON01 power monitor module, the chassis supports monitoring of key power system conditions.
- AC or DC input power status
- System bus voltage
- I/O bus voltage
- Cabinet temperature
- Power system fan speed
- Auxiliary monitoring channels
- Contact input status
This monitoring architecture helps maintenance personnel assess power system health and identify abnormal operating conditions. The monitoring functions depend on the installed monitor module and the configured system connections.
05 | Associated MPS II Power Components
| Component | Model | Technical Information |
|---|---|---|
| Power monitor module | IPMON01 | Central monitoring module for the chassis |
| Power modules | IPBLC01, IPSYS01, IPFLD01, IPFLD24, IPFLD48, IPFLD125 | Power conversion and supply modules |
| Power entry circuit breaker | IPECB11, IPECB13 | Input protection and power entry |
| Power entry switch | IPEWS11, IPEWS13 | Power input switching |
| System fan | IPFAN14 | Power system cooling |
Related power entry specifications:
- IPECB11 and IPEWS11: 102–264 VAC input.
- IPECB13 and IPEWS13: 102–144 VDC input.
- Maximum input current: 20 A.
- Nominal voltage drop across the breaker or switch: 2 V at 20 A.
IPFAN14 fan input ratings:
- 120 VAC: 0.72 A nominal
- 240 VAC: 0.42 A nominal
- 125 VDC: 0.5 A nominal
- AC frequency: 47–63 Hz
Model distinction: IPCHS01 and IPCHS02 are listed as MPS II power module chassis models. The approximately 7 A Harmony connector rating applies specifically to IPCHS02. Do not assume this connector rating applies to IPCHS01.
06 | Installation and Commissioning Considerations
- Verify the chassis model. Confirm IPCHS01 against the cabinet drawings and installed MPS II power system documentation.
- Check module placement. Reserve the center slot for IPMON01 and use the eight surrounding positions for supported power modules.
- Confirm input compatibility. Check the power entry arrangement and selected module requirements before applying AC or DC power.
- Review load distribution. Calculate the demand on each output bus and compare it with the chassis and module ratings.
- Inspect power connections. Check bus bar connections, terminal strips, cable routing, and connection security.
- Verify monitoring and redundancy. Confirm monitor feedback, fan operation, module status, and load-sharing behavior during commissioning.
Isolate the power source and follow the approved site safety procedure before installing or removing components. Use the applicable ABB Bailey installation documentation for wiring and replacement procedures.
07 | Applications in Industrial Control Cabinets
- DCS power distribution: Supplies multiple DC power rails to distributed control system cabinets.
- Process automation: Supports control electronics that require stable, distributed power.
- Redundant power systems: Provides the chassis structure for N+1, N+x, and 2N power arrangements.
- Industrial utility systems: Supports cabinet-level power distribution and condition monitoring.
- Control system maintenance: Provides a common mounting and distribution platform for replaceable power modules.
08 | Product Supply and Purchasing Information
| Manufacturer | ABB Bailey |
| Model | IPCHS01 |
| Product Type | Power Module Chassis |
| System | MPS II Power System |
| Related Model | IPCHS02 |
| Condition | New & Original in Factory Packing |
| Warranty | Factory Warranty: 12 Months |
| Shipping | FedEx, UPS, DHL |
Contact Global PLC Spare HUB to confirm IPCHS01 availability, configuration compatibility, and delivery options. Please provide your required quantity and cabinet or system details when requesting a quotation.
09 | Engineering FAQs
Q1: How can I determine whether the existing IPCHS01 has enough capacity for additional power modules?
Check the current load on every output bus before adding modules. Compare the measured or calculated demand with the chassis bus ratings and the installed module capacities. Also verify input capacity on each side. Unused slots alone do not confirm sufficient electrical capacity.
Q2: What should I check if the power modules do not share the load evenly?
First, compare module types and output specifications. Then inspect input supply stability, output connections, and module status indications. Confirm that the installed modules support the intended load-sharing arrangement. Unequal current may indicate a configuration, connection, or module issue.
Q3: Can I install IPCHS01 in a cabinet that currently uses IPCHS02?
Do not treat the two chassis models as automatic drop-in replacements. Compare mounting dimensions, connector interfaces, wiring, terminal assignments, and cabinet drawings. The IPCHS02 Harmony connector rating is a model-specific detail that should not be transferred to IPCHS01.
Q4: What information should I provide when sourcing a replacement chassis?
Provide the complete part number, existing chassis label, installed power module models, power monitor model, and cabinet system details. Photos of the nameplate and connection area can help identify hardware differences before ordering.
Q5: What is a practical way to investigate repeated power system alarms?
Review input voltage, system and I/O bus readings, cabinet temperature, fan speed, and module status together. Check whether alarms occur during startup, under higher load, or after a module change. This timing helps narrow the investigation to supply stability, cooling, load distribution, or a specific module.
Tags
Q: Are these parts 100% original and new?
A: Yes. Every component is guaranteed to be 100% original, brand-new, and factory-sealed. We also provide a 12-month comprehensive warranty for your peace of mind.
Q: How fast is the shipping to my country?
A: For in-stock items, we offer same-day dispatch. International express shipping (DHL/FedEx/UPS) typically delivers within 3–5 business days worldwide.
Q: Can I get a formal quotation with shipping costs?
A: Absolutely. Our sales team is ready to provide a detailed Proforma Invoice (PI) including the most competitive shipping rates for your location.
Q: Do you offer discounts for bulk orders?
A: We provide volume-based pricing for large projects or multiple-item orders. Please contact us to get our Best Price Guarantee.
12-Month Comprehensive Warranty
Every part supplied by Global PLC Spare Hub is covered by a 12-month warranty from the date of invoice.
- Coverage: Functional defects and hardware failures under normal operating conditions.
- Commitment: We provide immediate repair, replacement, or a full refund for any verified defective components to minimize your operational downtime.
Returns & Exchange Policy
We offer a 30-day return policy to ensure you receive the exact part your system requires.
- Eligibility: Returns are accepted for uninstalled items in their original, factory-sealed packaging.
- RMA Process: Please contact our support team to obtain a Return Merchandise Authorization (RMA) number before shipping.
- Fast Processing: Refunds or exchanges are processed within 3–5 business days after the returned item passes our technical inspection.
Need Technical Assistance?Not sure if this part is compatible with your system? [Consult our Engineers] before purchasing to ensure 100% compatibility.