ABB Bailey IMDSI02 Infi 90 PLC Digital Input Interface Module
Manufacturer: ABB
Product No.: IMDSI02
Condition: In stock
Product Type: Digital Input Interface Module
Product Origin: USA
Payment: T/T, Western Union
Weight: 500g
Shipping port: Xiamen
Warranty: 12 months
Estimate delivery times: 12-26 days (International), 3-6 days (United States).
Return within 30 days of purchase. Duties & taxes are non-refundable.
Guaranteed Safe Checkout
Product Overview | ABB Bailey IMDSI02
The ABB Bailey IMDSI02 is a 16-channel Digital Slave Input Module for the Infi 90 Process Management System.
It acquires discrete field signals and transfers their states to the system for control and monitoring. Typical signal sources include contact closures, switches, and solenoid-operated devices.
The module supports three nominal input voltage classes: 24 VDC, 125 VDC, and 120 VAC. Individual input jumpers configure the voltage selection and response characteristics.
DC channels offer fast and slow response settings. These settings help engineers manage contact bounce and field-device switching behavior. Front-panel LEDs provide visual channel status during commissioning and maintenance.
The IMDSI02 occupies one slot in a standard Infi 90 Module Mounting Unit. Its modular design supports installation and removal without shutting down the entire system.
Technical Specifications | Electrical and Functional Data
| Manufacturer | ABB Bailey |
| Brand | ABB |
| Model | IMDSI02 |
| Product Series | Infi 90 |
| Product Type | Digital Slave Input Module |
| Functional Category | Digital Input / Discrete Signal Acquisition |
| Number of Channels | 16 independent digital inputs |
| Supported Input Voltages | 24 VDC, 125 VDC, 120 VAC |
| 24 VDC Tolerance | ±10% |
| 125 VDC Tolerance | ±10% |
| 120 VAC Tolerance | ±10% |
| Typical Input Current | 4.5 mA at 24 VDC; 5.0 mA at 125 VDC; 7.0 mA at 120 VAC, 60 Hz |
| DC Fast Response | 1.5 ms |
| DC Slow Response | 17 ms |
| Logic Supply Voltage | 5 VDC ±5% |
| Typical Logic Current | 55 mA at 5 VDC |
| Maximum Logic Current | 79 mA |
| Input-to-Logic Isolation | 300 V RMS |
| Input-to-Input Isolation | 300 V RMS |
| Mounting | One slot in a standard Infi 90 Module Mounting Unit |
| Operating Temperature | 0°C to 70°C |
| Certification | CSA, ordinary non-hazardous locations |
Input Signal Thresholds | Switching Characteristics
The IMDSI02 uses defined ON and OFF voltage thresholds. These values help engineers evaluate field signal compatibility.
| Input Class | Minimum Turn-On Voltage | Maximum Turn-Off Voltage |
| 24 VDC | 21.4 VDC | 12 VDC |
| 125 VDC | 95.0 VDC | 60 VDC |
| 120 VAC | 85.0 VAC | 42 VAC |
Maximum Input Current at Minimum Turn-On Voltage
- 24 VDC: 3 mA at 21.4 VDC.
- 125 VDC: 3 mA at 95.0 VDC.
- 120 VAC: 5 mA at 85.0 VAC, 60 Hz.
Maximum OFF-State Leakage Current
- 24 VDC: 10 μA at input voltages up to 12 VDC.
- 125 VDC: 10 μA at input voltages up to 60 VDC.
- 120 VAC: 1.6 mA at input voltages up to 42 VAC, 60 Hz.
The voltage difference between ON and OFF thresholds provides switching hysteresis. Engineers should verify field-device output levels against both thresholds.
Response Configuration | Fast and Slow DC Inputs
The module provides two selectable DC response modes. Individual input jumpers determine the configured response behavior.
| Response Setting | Response Time | Typical Application |
| Fast | 1.5 ms | Faster discrete signal detection |
| Slow | 17 ms | Mechanical contacts with longer bounce periods |
Engineering Selection Guidelines
- Select fast response for signals requiring quicker state recognition.
- Select slow response when field contacts produce mechanical bounce.
- Check the switching characteristics of connected sensors and relays.
- Match response settings with the required control sequence.
- Verify every input jumper before returning the system to operation.
Response time affects signal recognition. It does not define the complete system scan time or control-loop execution time.
Isolation and Communication Architecture
The IMDSI02 uses a passive contact input interface. A Multi-Function Processor or Logic Master Module reads its input states through the slave expander bus.
Communication Structure
- Field devices provide discrete electrical signals.
- The input circuitry detects the corresponding signal states.
- Front-panel LEDs indicate individual input conditions.
- The slave expander bus carries input information to the master module.
- The master module processes the acquired information.
Electrical Isolation
- Input-to-logic circuitry isolation: 300 V RMS.
- Input-to-input isolation: 300 V RMS.
- CSA approval covers the specified 300 V isolation.
This isolation helps separate field signal circuits from logic circuitry. It also reduces unwanted electrical interaction between input circuits.
Typical Industrial Applications
| Process Monitoring | Collects discrete status signals from industrial field equipment. |
| Motor Control | Monitors contactor feedback and auxiliary contact conditions. |
| Valve Control Systems | Acquires limit-switch and solenoid-related status signals. |
| Equipment Interlocking | Transfers switch and contact states to control logic. |
| Power System Monitoring | Monitors compatible DC and AC discrete signals. |
| Industrial Alarm Systems | Collects equipment status and process alarm inputs. |
Installation Guide | Mounting and Configuration
The module occupies one slot in a standard Infi 90 Module Mounting Unit.
- Confirm the system uses a compatible Infi 90 mounting unit.
- Check the module identification and physical condition.
- Review the field signal voltage for each input.
- Set individual voltage jumpers according to the application.
- Select fast or slow response for applicable DC inputs.
- Verify all jumper positions against the wiring documentation.
- Install the module in the designated mounting slot.
- Connect the field signal wiring according to the system drawings.
- Restore or maintain system operation according to approved procedures.
- Check front-panel LEDs and confirm input status.
Hot-Swapping Capability: The module supports installation and removal without powering down the system. Follow the approved site maintenance procedure before handling any module.
Commissioning, Diagnostics and Maintenance
The front-panel LED indicators simplify channel-level inspection. Engineers can compare physical field conditions with the displayed input states.
Recommended Commissioning Checks
- Verify the input voltage class for every channel.
- Measure field voltage under actual operating conditions.
- Check ON and OFF switching thresholds.
- Confirm the selected DC response mode.
- Compare LED indications with field-device states.
- Verify communication through the slave expander bus.
Preventive Maintenance
- Inspect module seating and mounting contacts.
- Check field wiring for loose or damaged connections.
- Review jumper positions after wiring modifications.
- Investigate unexpected LED status changes.
- Check for excessive electrical noise or unstable field supplies.
- Record input assignments and configuration changes.
Compatibility and System Integration
| Control System | ABB Bailey Infi 90 Process Management System |
| Module Family | Infi 90 Digital Slave Input |
| Master Modules | Multi-Function Processor or Logic Master Module |
| Communication Interface | Slave expander bus |
| Input Capacity | 16 digital input signals |
| Supported Signals | 24 VDC, 125 VDC, and 120 VAC |
| Mounting Interface | Standard Infi 90 Module Mounting Unit |
Compatibility Note: Verify the system generation, mounting unit, master module, and expander bus configuration before ordering. Also confirm the required voltage and response settings for every field channel.
Environmental Specifications and Certifications
| Operating Temperature | 0°C to 70°C (32°F to 158°F) |
| Relative Humidity | 0–95% up to 55°C, non-condensing |
| High-Temperature Humidity | 0–45% at 70°C, non-condensing |
| Atmospheric Pressure | Sea level to 3 km altitude |
| Air Quality | Non-corrosive atmosphere |
| Electrical Isolation | 300 V RMS |
| Certification | CSA certified |
| Approved Location | Ordinary, non-hazardous locations |
The CSA certification applies to process control equipment in ordinary locations. Do not assume hazardous-area approval without separate documentation.
Packaging and Commercial Information
- 1 × ABB Bailey IMDSI02 Digital Slave Input Module.
- Product identification and model verification.
- Condition: New & Original in Factory Packing.
- Warranty: Factory Warranty: 12 Months.
- Shipping: FedEx, UPS, and DHL available.
- Additional accessories: Confirm separately according to order requirements.
Frequently Asked Questions | Engineering and Selection
Q1: Can the IMDSI02 monitor AC and DC signals within the same installation?
Yes. The module supports 24 VDC, 125 VDC, and 120 VAC input classes. Engineers must configure each input using the appropriate voltage jumper. Always verify the channel wiring and jumper arrangement before energizing the circuit.
Q2: How should engineers select the correct input voltage configuration?
Start with the field device's nominal output voltage. Then check its actual operating range against the module's ON and OFF thresholds. Consider supply variation and voltage drop across long cables. Select the corresponding input configuration only after confirming these values.
Q3: What should engineers investigate when an input LED remains ON after the field contact opens?
Measure the voltage at the module input terminal. Compare the reading with the specified maximum OFF threshold. Check leakage current from electronic sensors, relay contacts, and connected suppression components. Also inspect wiring for unintended voltage coupling.
Q4: Does the hot-swap feature eliminate all electrical maintenance precautions?
No. Hot-swapping allows module replacement without shutting down the entire system. However, field circuits may still carry hazardous voltage. Follow site isolation procedures and verify the electrical safety requirements before removing or installing the module.
Q5: What details should buyers provide when sourcing an IMDSI02 replacement?
Provide the complete model number and existing system configuration. Include the required input voltage classes and DC response settings. Confirm the mounting unit and master module compatibility. These details help prevent incorrect selection and reduce commissioning delays.

Tags
Q: Are these parts 100% original and new?
A: Yes. Every component is guaranteed to be 100% original, brand-new, and factory-sealed. We also provide a 12-month comprehensive warranty for your peace of mind.
Q: How fast is the shipping to my country?
A: For in-stock items, we offer same-day dispatch. International express shipping (DHL/FedEx/UPS) typically delivers within 3–5 business days worldwide.
Q: Can I get a formal quotation with shipping costs?
A: Absolutely. Our sales team is ready to provide a detailed Proforma Invoice (PI) including the most competitive shipping rates for your location.
Q: Do you offer discounts for bulk orders?
A: We provide volume-based pricing for large projects or multiple-item orders. Please contact us to get our Best Price Guarantee.
12-Month Comprehensive Warranty
Every part supplied by Global PLC Spare Hub is covered by a 12-month warranty from the date of invoice.
- Coverage: Functional defects and hardware failures under normal operating conditions.
- Commitment: We provide immediate repair, replacement, or a full refund for any verified defective components to minimize your operational downtime.
Returns & Exchange Policy
We offer a 30-day return policy to ensure you receive the exact part your system requires.
- Eligibility: Returns are accepted for uninstalled items in their original, factory-sealed packaging.
- RMA Process: Please contact our support team to obtain a Return Merchandise Authorization (RMA) number before shipping.
- Fast Processing: Refunds or exchanges are processed within 3–5 business days after the returned item passes our technical inspection.
Need Technical Assistance?Not sure if this part is compatible with your system? [Consult our Engineers] before purchasing to ensure 100% compatibility.