YOKOGAWA F3YD14-5A | FA-M3 Transistor Output Module

The YOKOGAWA F3YD14-5A is a 14-point transistor output module for the FA-M3 programmable controller platform. It provides sink-type DC outputs for controlling compatible field loads.

Photocoupler isolation separates the output circuitry from the internal control circuitry. Each output supports a rated load voltage of 12–24 V DC and a maximum load current of 0.5 A per point.

The module groups its 14 outputs into two common circuits. One common serves eight points, while the other serves six points. This arrangement helps engineers plan field wiring and distribute output loads.

Output Architecture and Electrical Performance

Parameter Specification Engineering Note
Output technology Transistor contact, sink type Designed for compatible DC load circuits
Number of outputs 14 points Two output groups
Points per common 8 points / 6 points Plan wiring by common group
Isolation Photocoupler Provides electrical isolation
Rated load voltage 12–24 V DC Use a compatible external supply
Maximum load current 0.5 A per point Maximum 2 A per common
OFF-to-ON response 1 ms maximum Fast output switching
ON-to-OFF response 1 ms maximum Supports responsive load control
Maximum ON voltage 0.5 V DC Check voltage drop at the connected load
OFF-state leakage current 0.1 mA maximum Consider leakage when selecting sensitive loads
Surge protection Active clamp Integrated output protection feature
Output life Not specified Confirm load-related service requirements

Power, Wiring and Physical Interface

  • Internal current consumption: 120 mA at 5 V DC.
  • External power supply: 12–24 V DC, 20 mA.
  • External connection: 18-point terminal block with M3.5 screws.
  • Module weight: 160 g.

The 18-point terminal block provides the field connection interface. Engineers should verify terminal assignments and common-group wiring against the applicable FA-M3 hardware documentation before commissioning.

CPU Error Output Behavior

The module supports HOLD or RESET behavior for output handling during CPU errors. The available behavior depends on the connected CPU type.

CPU Type Output Behavior
Sequence CPU Initial value: RESET
BASIC CPU No setting function; always HOLD
OS-free CPU Initial value: HOLD; configurable for each group of eight points

The module can also apply a collective setting to all outputs. Confirm the actual CPU configuration and output response requirements before changing these settings.

Environmental and Operating Conditions

Environmental Parameter Operating Range Storage Range
Ambient temperature 0 to 55°C -20 to 75°C
Relative humidity 10–90% RH, non-condensing 10–90% RH, non-condensing
Atmosphere Free from corrosive gases, flammable gases and heavy dust

Install the module inside an appropriate control enclosure. Avoid locations with condensation, conductive dust or chemically aggressive atmospheres.

Installation and Commissioning Recommendations

  1. Check the hardware: Confirm the F3YD14-5A model and FA-M3 system compatibility before installation.
  2. Verify the load circuit: Confirm that each field load accepts the specified 12–24 V DC output arrangement.
  3. Calculate group loading: Keep each point within 0.5 A and each common within 2 A.
  4. Check polarity and wiring: Follow the sink-type output circuit and terminal assignment in the official wiring documentation.
  5. Test switching behavior: Verify ON/OFF response, load operation and output status during commissioning.
  6. Review CPU error settings: Confirm HOLD or RESET behavior against the machine's shutdown and restart sequence.

Maintenance and Fault Diagnosis

  • Unexpected load activation: Check the OFF-state leakage current and the connected load's input threshold.
  • Output voltage drop: Measure the ON-state voltage under the actual load condition.
  • Intermittent output operation: Inspect terminal tightness, common wiring and external supply stability.
  • Multiple outputs affected: Check the shared common circuit and its total current.
  • Unexpected CPU-error response: Review the CPU type and configured HOLD/RESET behavior.

Package Information

  • 1 × YOKOGAWA F3YD14-5A Transistor Output Module
  • Additional accessories and connection components: confirm separately according to the order configuration.

Frequently Asked Questions

Q1: How should engineers distribute loads across the two output commons?

Allocate loads according to the eight-point and six-point groups. Keep each common below 2 A, even when individual points remain below 0.5 A.

Q2: What should engineers check when a low-current load remains active after an OFF command?

Measure the load input current and compare its threshold with the module's maximum 0.1 mA OFF-state leakage. Sensitive electronic inputs may require an appropriate interface solution.

Q3: Can the output module directly replace a relay output module?

Not automatically. Check the field device's voltage, current, polarity and switching requirements. A transistor output and a relay output have different electrical characteristics.

Q4: Why should commissioning tests include the actual field load?

Actual load testing reveals voltage drop, common-current distribution and unexpected input behavior. A no-load test alone cannot confirm reliable operation under working conditions.

Q5: What should maintenance teams record after replacing this module?

Record the model, terminal wiring, common-group loading, external supply voltage and CPU error response. These details help technicians compare future faults against the original commissioning condition.

Tags

Q: Are these parts 100% original and new?

A: Yes. Every component is guaranteed to be 100% original, brand-new, and factory-sealed. We also provide a 12-month comprehensive warranty for your peace of mind.

Q: How fast is the shipping to my country?

A: For in-stock items, we offer same-day dispatch. International express shipping (DHL/FedEx/UPS) typically delivers within 3–5 business days worldwide.

Q: Can I get a formal quotation with shipping costs?

A: Absolutely. Our sales team is ready to provide a detailed Proforma Invoice (PI) including the most competitive shipping rates for your location.

Q: Do you offer discounts for bulk orders?

A: We provide volume-based pricing for large projects or multiple-item orders. Please contact us to get our Best Price Guarantee.




12-Month Comprehensive Warranty

Every part supplied by Global PLC Spare Hub is covered by a 12-month warranty from the date of invoice.

  • Coverage: Functional defects and hardware failures under normal operating conditions.
  • Commitment: We provide immediate repair, replacement, or a full refund for any verified defective components to minimize your operational downtime.

Returns & Exchange Policy

We offer a 30-day return policy to ensure you receive the exact part your system requires.

  • Eligibility: Returns are accepted for uninstalled items in their original, factory-sealed packaging.
  • RMA Process: Please contact our support team to obtain a Return Merchandise Authorization (RMA) number before shipping.
  • Fast Processing: Refunds or exchanges are processed within 3–5 business days after the returned item passes our technical inspection.

Need Technical Assistance?Not sure if this part is compatible with your system? [Consult our Engineers] before purchasing to ensure 100% compatibility.