1746-OX8 Allen-Bradley SLC 500 Digital Contact Output Module
Manufacturer: Allen-Bradley
Product No.: 1746-OX8
Condition: In stock
Product Type: Relay Output Module
Product Origin: USA
Payment: T/T, Western Union
Weight: 540g
Shipping port: Xiamen
Warranty: 12 months
Estimate delivery times: 12-26 days (International), 3-6 days (United States).
Return within 30 days of purchase. Duties & taxes are non-refundable.
Guaranteed Safe Checkout
1746-OX8 | Eight-Point Individually Isolated Relay Output
The Allen-Bradley 1746-OX8 is an eight-point digital contact output module for the SLC 500 programmable controller system.
Unlike common-group relay modules, this unit provides individual electrical isolation for each output point. This arrangement allows engineers to switch separate AC and DC load circuits through one module.
Each channel uses a normally open (N.O.) relay contact. The module supports operating voltages from 5 to 265 V AC and 5 to 125 V DC.
The 1746-OX8 targets high-current switching applications that require independent output circuits. Typical loads include contactor coils, solenoid valves, motor control interfaces, and industrial alarm devices.
Product Identification
| Manufacturer | Rockwell Automation |
| Brand | Allen-Bradley |
| Catalog Number | 1746-OX8 |
| Product Family | SLC 500 |
| Module Category | Digital Contact Output Module |
| Output Technology | Electromechanical Relay |
| Output Configuration | 8 Normally Open Contacts |
| Isolation | Individually Isolated Outputs |
| Mounting | Compatible SLC 500 Chassis |
| Enclosure Type | Open-Type Module |
| UPC | 662073896623 |
Electrical Ratings and Contact Performance
Contact selection requires more than checking the nominal operating voltage. Engineers must evaluate switching current, continuous current, and load characteristics.
| Parameter | Technical Rating |
|---|---|
| Number of Outputs | 8 |
| Contact Configuration | N.O. Relay |
| AC Operating Voltage | 5–265 V AC |
| DC Operating Voltage | 5–125 V DC |
| Inductive Load Rating | 3 A at 120 V AC; 1.2 A at 24 V DC |
| Minimum Load Current | 10 mA at 5 V DC |
| Maximum Off-State Leakage | 0 mA |
| Maximum Resistive Load Delay | 10 ms ON / 10 ms OFF |
| Backplane Current at 5 V DC | 85 mA |
| Backplane Current at 24 V DC | 90 mA |
| I/O to Logic Isolation | 1500 V |
Relay Contact Ratings by Load Voltage
The following ratings distinguish contact switching capacity from continuous operating current.
| Contact Voltage | Maximum Make Current | Maximum Break Current | Continuous Current |
|---|---|---|---|
| 120 V AC | 30 A | 3 A | 5 A |
| 240 V AC | 15 A | 1.5 A | 1 A |
| 125 V DC | 0.22 A | 0.22 A | 1 A |
| 24 V DC | 1.2 A | 1.2 A | 2 A |
Important Load Limitation: The total continuous module load must remain within 1440 VA. Individual contact ratings also apply. Never use the make-current rating as a continuous load rating.
Mechanical and Environmental Performance
| Operating Temperature | 0 to 60°C |
| Storage Temperature | -40 to 85°C |
| Operating Shock | 10 g |
| Vibration, 5–57 Hz | 0.015-inch peak displacement |
| Vibration, 57–2000 Hz | 2.5 g acceleration |
| Heat Dissipation per Point | 0.825 W |
| Minimum Heat Dissipation | 2.590 W |
| Total Heat Dissipation | 8.60 W |
Channel Isolation and Load Protection
The 1746-OX8 uses individually isolated relay contacts. Each output can switch a separate external circuit within its rated electrical limits.
- Independent Circuits: Separate output points support different load voltages.
- AC/DC Switching: Relay contacts support specified AC and DC applications.
- Electrical Isolation: The module provides 1500 V isolation between I/O terminals and control logic.
- Zero Off-State Leakage: The specified maximum off-state leakage is 0 mA.
- Contact Protection: External surge suppression helps protect relay contacts from inductive switching transients.
Field Engineering Note: Relay contacts experience electrical arcing when switching inductive loads. Install suitable suppression across external coils. This helps reduce contact erosion and extends relay service life.
Installation and Field Wiring
- Isolate Power: Remove power from the chassis before installing or removing the module.
- Verify the Chassis: Confirm compatibility with the SLC 500 rack configuration.
- Inspect Terminals: Check the removable terminal block and contact condition.
- Identify Load Circuits: Confirm the voltage and current requirements for every output.
- Wire Individual Channels: Maintain separate circuit identification for each isolated relay point.
- Install Suppression: Add suitable protection for inductive loads where required.
- Check Wiring: Verify terminal tightness, polarity where applicable, and circuit isolation.
- Restore Power: Apply power after completing installation checks.
Safety Warning: Never insert or remove the module while chassis power is applied. Follow the official installation instructions and site electrical safety procedures.
Commissioning and Maintenance Strategy
Relay output diagnostics require both PLC-side checks and field-side electrical measurements.
- Output Command: Confirm that the PLC program issues the expected output command.
- Channel Status: Check the corresponding module status indicator.
- Contact Continuity: Test relay contact operation with the circuit safely isolated.
- Load Current: Measure actual current under operating conditions.
- Contact Wear: Inspect for signs of overheating, pitting, or abnormal switching behavior.
- Suppression Components: Check external surge suppressors and coil protection devices.
- Thermal Conditions: Confirm that cabinet ventilation supports the module's heat dissipation.
Maintenance Recommendation: If the PLC command changes but the field load does not respond, check the external supply and relay contact path. Do not immediately assume a CPU or program fault.
System Compatibility and Application Selection
The 1746-OX8 belongs to the Allen-Bradley SLC 500 digital output family.
- Controller Platform: Designed for compatible SLC 500 chassis configurations.
- Output Interface: Eight individually isolated N.O. relay contacts.
- Load Compatibility: Supports specified AC and DC load circuits.
- Control Applications: Suitable for switching contactors, solenoids, alarms, and auxiliary equipment.
- Replacement Checks: Verify chassis compatibility, terminal arrangement, load ratings, and wiring before substitution.
This module is particularly useful when output circuits require different voltage levels. Its isolated contacts also help separate external control circuits.
Certifications and Compliance
- The manufacturer provides product-specific regulatory and certification information.
- Historical installation documentation identifies CSA Class I, Division 2 certification for applicable configurations.
- Verify the module label and applicable certification documents before hazardous-area installation.
- Follow local electrical codes and enclosure requirements.
Package Contents
- 1 × Allen-Bradley 1746-OX8 Digital Contact Output Module.
- Terminal block or additional accessories: Confirm according to the specific order configuration.
- Technical documentation: Available upon request, subject to availability.
Professional FAQ – Relay Output Engineering
Q1: Why can an output indicator change state while the connected contactor remains inactive?
The indicator reflects the module's control status, not necessarily successful load energization. Check the external AC/DC supply, terminal wiring, fuse protection, and relay contact continuity. A worn contact or an open field circuit can prevent the contactor from operating.
Q2: What happens when a relay output switches a contactor coil without surge suppression?
Inductive energy can generate voltage transients when the relay opens. These transients increase electrical arcing across the contacts. Repeated switching can accelerate contact wear. Select an appropriate suppression device for the coil voltage and circuit type.
Q3: Can all eight channels switch their maximum rated current simultaneously?
Not automatically. Each contact has its own switching limits. The complete module must also remain within the 1440 VA continuous power limitation. Calculate the combined load before commissioning. Consider the load duty cycle and switching frequency during the assessment.
Q4: Why might a small electronic load fail to operate reliably through a mechanical relay?
Mechanical contacts require a suitable minimum load for reliable contact performance. The specified minimum load is 10 mA at 5 V DC. Very low-current electronic inputs may require an interposing relay or another suitable interface. Check the actual load characteristics before connection.
Q5: How should engineers evaluate relay output suitability for frequent switching?
Start with the load's inrush current, operating voltage, switching frequency, and inductive characteristics. Compare these values with the contact make, break, and continuous ratings. Also consider relay mechanical and electrical life. For high-frequency switching, evaluate a solid-state output alternative when the application permits.
Tags
Q: Are these parts 100% original and new?
A: Yes. Every component is guaranteed to be 100% original, brand-new, and factory-sealed. We also provide a 12-month comprehensive warranty for your peace of mind.
Q: How fast is the shipping to my country?
A: For in-stock items, we offer same-day dispatch. International express shipping (DHL/FedEx/UPS) typically delivers within 3–5 business days worldwide.
Q: Can I get a formal quotation with shipping costs?
A: Absolutely. Our sales team is ready to provide a detailed Proforma Invoice (PI) including the most competitive shipping rates for your location.
Q: Do you offer discounts for bulk orders?
A: We provide volume-based pricing for large projects or multiple-item orders. Please contact us to get our Best Price Guarantee.
12-Month Comprehensive Warranty
Every part supplied by Global PLC Spare Hub is covered by a 12-month warranty from the date of invoice.
- Coverage: Functional defects and hardware failures under normal operating conditions.
- Commitment: We provide immediate repair, replacement, or a full refund for any verified defective components to minimize your operational downtime.
Returns & Exchange Policy
We offer a 30-day return policy to ensure you receive the exact part your system requires.
- Eligibility: Returns are accepted for uninstalled items in their original, factory-sealed packaging.
- RMA Process: Please contact our support team to obtain a Return Merchandise Authorization (RMA) number before shipping.
- Fast Processing: Refunds or exchanges are processed within 3–5 business days after the returned item passes our technical inspection.
Need Technical Assistance?Not sure if this part is compatible with your system? [Consult our Engineers] before purchasing to ensure 100% compatibility.