DS200CTBAG1A GE Mark V Analog Termination Board - Turbine Control
Manufacturer: GE
Product No.: DS200CTBAG1A
Condition: In stock
Product Type: Termination Board
Product Origin: USA
Payment: T/T, Western Union
Weight: 500g
Shipping port: Xiamen
Warranty: 12 months
Estimate delivery times: 12-26 days (International), 3-6 days (United States).
Return within 30 days of purchase. Duties & taxes are non-refundable.
Guaranteed Safe Checkout
Product Overview
The DS200CTBAG1A serves as a sophisticated Analog Termination Module (CTBA) within the General Electric Mark V LM turbine control environment. Engineered for the R5 core, this printed circuit board manages critical I/O signals, including shaft parameters and analog loops. It acts as the primary link between the controller and the plant field instrumentation, ensuring reliable data acquisition and command distribution.
Technical Specifications
- Brand/Manufacturer: General Electric
- Series: Mark V LM
- Part Number: DS200CTBAG1A
- Board Function: Analog Termination (CTBA)
- Revision: 1 A
- Dimensions: 6.25 in x 4.25 in
- Operating Temperature: -28°C to 55°C
- Protection: Integrated resistors, capacitors, and 23 MOV (Metal Oxide Varistors) for voltage surge suppression
- Communication Ports: RS-232 9-pin D-shell (TIMN diagnostics), IONET, and ARCNET
Diagnostic and Control Capabilities
The DS200CTBAG1A board is designed for robust system oversight. The integrated RS-232 port facilitates deep-level TIMN diagnostic access, allowing technicians to verify signal integrity in real-time. The board features a sophisticated bypass relay mechanism; should internal power fail, the relay ensures continuous COREBUS communication to maintain operational availability. Its onboard hardware jumpers (BJ1-BJ15) allow for precise field-level configuration of signal references and DCOM isolation.
Connectivity and Integration
This module acts as a central hub for inter-board communication. Key interface points include:
- Signal Management: JAA (4-20 mA output) and JBB (Shaft data/4-20 mA input) interfaces to the TCCA board.
- Networking: 8PL (IONET to STCA), JX (IONET to TCDA), and JAI/JAJ (COREBUS to QTBA).
- Power Management: JPD connector for TCPD board 24V dc power monitoring.
Global PLC Spare HUB's Insight
In our experience, the DS200CTBAG1A is prone to environmental stressors due to its location in the turbine core. We recommend periodic inspection of the 23 red varistors for thermal degradation. When integrating this board, always verify that termination resistors are present on unused COREBUS ports (JAI/JAJ) to prevent signal reflections that cause erratic turbine readings.
Typical Applications
- Gas, Steam, and Wind Turbine Automated Drive Assemblies
- Speedtronic Control System Upgrades and Retrofits
- Precision Analog Loop Monitoring
- Critical Turbine Core Data Processing
Ordering and Logistics
- Warranty: 12-month standard replacement warranty.
- Shipping: Expedited global logistics via FedEx, UPS, and DHL.
- Processing: Rapid 24-48 hour dispatch window.
- Package Includes: DS200CTBAG1A PCB, factory-tested and ready for installation.
Frequently Asked Questions
What is the purpose of the 6PL connector on this board?
The 6PL connector is a vestigial structure and remains unused during the standard operation of the DS200CTBAG1A module.
How can I confirm if my board is properly referencing DCOM?
Use the hardware jumpers BJ1 through BJ14 to connect the negative terminal of your mA inputs to the DCOM reference, ensuring a stable signal ground.
Should I be concerned about signal interference on the COREBUS?
If you are not utilizing the JAI or JAJ ports, you must install an external termination resistor to ensure bus impedance remains within the Mark V specifications.
Why does the board include so many varistors?
The 23 integrated varistors provide essential protection against transient voltage spikes, which are common in heavy-duty turbine control cabinets.
What is the best way to verify if the bypass relay has triggered?
If the board loses primary power, the diagnostic system will reflect a failure in COREBUS communication status; check the 24V dc input at the JPD connector first.
Procurement and Selection Guide
- Verify your current hardware revision is compatible with the 1A suffix.
- Always inspect the physical pins on D-shell and COREBUS connectors for oxidation before insertion.
- Ensure your maintenance team has the GEH-6153 manual available for mapping jumper settings to specific turbine configurations.
Tags
Q: Are these parts 100% original and new?
A: Yes. Every component is guaranteed to be 100% original, brand-new, and factory-sealed. We also provide a 12-month comprehensive warranty for your peace of mind.
Q: How fast is the shipping to my country?
A: For in-stock items, we offer same-day dispatch. International express shipping (DHL/FedEx/UPS) typically delivers within 3–5 business days worldwide.
Q: Can I get a formal quotation with shipping costs?
A: Absolutely. Our sales team is ready to provide a detailed Proforma Invoice (PI) including the most competitive shipping rates for your location.
Q: Do you offer discounts for bulk orders?
A: We provide volume-based pricing for large projects or multiple-item orders. Please contact us to get our Best Price Guarantee.
12-Month Comprehensive Warranty
Every part supplied by Global PLC Spare Hub is covered by a 12-month warranty from the date of invoice.
- Coverage: Functional defects and hardware failures under normal operating conditions.
- Commitment: We provide immediate repair, replacement, or a full refund for any verified defective components to minimize your operational downtime.
Returns & Exchange Policy
We offer a 30-day return policy to ensure you receive the exact part your system requires.
- Eligibility: Returns are accepted for uninstalled items in their original, factory-sealed packaging.
- RMA Process: Please contact our support team to obtain a Return Merchandise Authorization (RMA) number before shipping.
- Fast Processing: Refunds or exchanges are processed within 3–5 business days after the returned item passes our technical inspection.
Need Technical Assistance?Not sure if this part is compatible with your system? [Consult our Engineers] before purchasing to ensure 100% compatibility.