WE 77/Ex-1 Pepperl+Fuchs NAMUR Barrier WE 77 Series
Manufacturer: Pepperl+Fuchs
Product No.: WE 77/Ex-1
Condition: In stock
Product Type: Isolated Switch Amplifier
Product Origin: DE
Payment: T/T, Western Union
Weight: 150g
Shipping port: Xiamen
Warranty: 12 months
Estimate delivery times: 12-26 days (International), 3-6 days (United States).
Return within 30 days of purchase. Duties & taxes are non-refundable.
Guaranteed Safe Checkout
Product Identification & Engineering Overview
Pepperl+Fuchs WE 77/Ex-1 is a single-channel isolated switch amplifier for intrinsically safe industrial control circuits. It transfers switching signals from hazardous-area sensors to non-intrinsically safe control equipment.
The module accepts NAMUR sensors and mechanical contacts according to EN 60947-5-6. Its input circuit supports lead breakage monitoring and reversible operating modes.
On the control side, an electromechanical relay provides one changeover contact. This interface supports alarm circuits, equipment status feedback, and industrial interlocking applications.
The WE 77 Series design combines field signal evaluation, intrinsic safety isolation, and relay-based signal transmission. Its 230 V AC supply supports industrial cabinet installations.
01 | Functional Architecture
Signal Path: Field Sensor → Intrinsically Safe Input → Signal Evaluation → Relay Output → Control System
| Functional Section | Engineering Description |
|---|---|
| Field Input | One NAMUR sensor or mechanical contact circuit |
| Input Evaluation | Digital switching signal detection |
| Fault Supervision | Lead breakage monitoring |
| Operating Logic | Reversible operating mode |
| Output Interface | One electromechanical changeover relay contact |
| Electrical Protection | Intrinsically safe EEx ia IIC field circuit |
| Power Architecture | 198–253 V AC, 45–65 Hz |
Important: The relay output is non-intrinsically safe. Only the designated field input circuit provides the specified intrinsic safety protection.
02 | Electrical and Mechanical Specifications
| Parameter | Technical Specification |
|---|---|
| Manufacturer | Pepperl+Fuchs |
| Model | WE 77/Ex-1 |
| Product Series | WE 77 |
| Product Type | Isolated Switch Amplifier |
| Channel Configuration | 1 Channel |
| Input Signal | NAMUR Sensor / Mechanical Contact |
| Input Standard | EN 60947-5-6 |
| Input Terminals | 1-, 2+ |
| Pulse/Pause Ratio | ≥ 0.5 ms / ≥ 0.5 ms |
| Line Monitoring | Lead Breakage Detection |
| Lead Breakage Threshold | Current ≤ 0.1 mA |
| Operating Mode | Reversible |
| Output Type | Electromechanical Relay |
| Relay Configuration | 1 Changeover Contact |
| Output Terminals | 7, 8, 9 |
| Relay Contact Rating | 250 V AC / 4 A / 500 VA / cos φ > 0.7 |
| DC Contact Rating | 220 V DC / 0.1 A |
| DC Contact Rating | 60 V DC / 0.6 A |
| DC Contact Rating | 24 V DC / 4 A |
| Operate Delay | Approximately 10 ms |
| Release Delay | Approximately 20 ms |
| Mechanical Life | 10⁷ Switching Cycles |
| Maximum Switching Frequency | < 10 Hz |
| Supply Terminals | 11, 12 |
| Rated Supply Voltage | 198–253 V AC |
| Supply Frequency | 45–65 Hz |
| Power Consumption | Approximately 3.5 VA |
| Operating Temperature | -25 to +60 °C |
| Protection Rating | IP20 |
| Dimensions (W × H × D) | 40 × 104 × 110 mm |
| Weight | Approximately 390 g |
Supply Variant Note: The specifications above describe the 230 V AC version. The WE 77 product family also has a 115 V AC variant. Confirm the exact ordering designation before selecting a replacement.
03 | Intrinsic Safety Parameters & Hazardous Area Interface
The WE 77/Ex-1 provides an intrinsically safe field interface for approved hazardous-area installations. Its output characteristics determine the permissible electrical parameters of connected field devices.
| Ex Parameter | Specification |
|---|---|
| Protection Concept | EEx ia / EEx ib |
| Explosion Protection Group | IIB / IIC |
| Open-Circuit Voltage Uo | 13.5 V DC |
| Short-Circuit Current Io | 31 mA |
| Output Power Po | 125 mW |
| Ex Examination Certificate | PTB No. Ex-79/2043X |
Permitted External Capacitance and Inductance
| Protection Type | Gas Group | External Capacitance | External Inductance |
|---|---|---|---|
| EEx ia | IIB | 0.929 µF | 5 mH |
| EEx ia | IIC | 0.23 µF | 3 mH |
| EEx ib | IIB | 2.929 µF | 115 mH |
| EEx ib | IIC | 0.609 µF | 31 mH |
04 | Installation and Terminal Connection
Terminal Assignment
| Terminal | Connection | Installation Notes |
|---|---|---|
| 1- | Field Input Negative | Connect according to the NAMUR input circuit. |
| 2+ | Field Input Positive | Connect the approved sensor or contact circuit. |
| 7, 8, 9 | Relay Output | Connect the receiving control circuit. |
| 11, 12 | AC Power Supply | Connect the specified 198–253 V AC supply. |
Installation Sequence
- Check the complete model designation and supply voltage.
- Inspect the housing and terminal condition.
- Install the module according to the manufacturer's mounting instructions.
- Route intrinsically safe and non-intrinsically safe wiring separately.
- Connect the field sensor to terminals 1- and 2+.
- Connect the relay circuit to terminals 7, 8, and 9.
- Connect the AC supply to terminals 11 and 12.
- Verify wiring and insulation before energizing the equipment.
Installation Precautions
- Follow the manufacturer's hazardous-area installation requirements.
- Use approved wiring practices for intrinsically safe circuits.
- Maintain the required separation between circuit types.
- Protect the module from moisture, conductive dust, and mechanical damage.
- Check cabinet ventilation and ambient temperature.
05 | Commissioning and Field Diagnostics
Correct commissioning helps prevent false switching and unnecessary field troubleshooting.
| Inspection Item | Recommended Field Check |
|---|---|
| Power Supply | Measure the AC supply at terminals 11 and 12. |
| Sensor Circuit | Check NAMUR sensor wiring and current characteristics. |
| Lead Monitoring | Simulate an open circuit under approved test conditions. |
| Relay Switching | Verify contact transitions with a suitable test instrument. |
| Operating Logic | Compare relay states with the configured control logic. |
| Field Cable | Check continuity and insulation condition. |
06 | Certification and Environmental Compliance
| Item | Reference |
|---|---|
| Manufacturer | Pepperl+Fuchs |
| Ex Certificate | PTB No. Ex-79/2043X |
| Hazardous Area Protection | [EEx ia] / [EEx ib] |
| Explosion Groups | IIB / IIC |
| Input Standard | EN 60947-5-6 |
| Protection Rating | IP20 |
| Operating Temperature | -25 to +60 °C |
Verify the applicable certificate revision and installation conditions before using the device in a hazardous area. The original certification documentation takes precedence over general product summaries.
Tags
Q: Are these parts 100% original and new?
A: Yes. Every component is guaranteed to be 100% original, brand-new, and factory-sealed. We also provide a 12-month comprehensive warranty for your peace of mind.
Q: How fast is the shipping to my country?
A: For in-stock items, we offer same-day dispatch. International express shipping (DHL/FedEx/UPS) typically delivers within 3–5 business days worldwide.
Q: Can I get a formal quotation with shipping costs?
A: Absolutely. Our sales team is ready to provide a detailed Proforma Invoice (PI) including the most competitive shipping rates for your location.
Q: Do you offer discounts for bulk orders?
A: We provide volume-based pricing for large projects or multiple-item orders. Please contact us to get our Best Price Guarantee.
12-Month Comprehensive Warranty
Every part supplied by Global PLC Spare Hub is covered by a 12-month warranty from the date of invoice.
- Coverage: Functional defects and hardware failures under normal operating conditions.
- Commitment: We provide immediate repair, replacement, or a full refund for any verified defective components to minimize your operational downtime.
Returns & Exchange Policy
We offer a 30-day return policy to ensure you receive the exact part your system requires.
- Eligibility: Returns are accepted for uninstalled items in their original, factory-sealed packaging.
- RMA Process: Please contact our support team to obtain a Return Merchandise Authorization (RMA) number before shipping.
- Fast Processing: Refunds or exchanges are processed within 3–5 business days after the returned item passes our technical inspection.
Need Technical Assistance?Not sure if this part is compatible with your system? [Consult our Engineers] before purchasing to ensure 100% compatibility.