VF702 | Yokogawa V net Communication Interface
The VF702 is a V net control bus interface card manufactured by Yokogawa. It provides communication between a host computer's PCI Express interface and the Yokogawa V net control bus.
The card uses a PCI Express x1 interface and supports 10BASE-2 coaxial bus communication. It connects to the control network through a BNC connector and a YCB146 T-type connector.
The VF702 supports mixed installations with VF701 interface cards. Engineers can operate both card types on the same V net control bus. The VF702 supports system software revision R3.05 or later.
01 | Hardware Architecture & Interface Overview
| Manufacturer | Yokogawa |
| Model | VF702 |
| Product Type | V net Control Bus Interface Card |
| Interface Category | PCI Express Communication Card |
| Network | Yokogawa V net |
| Host Interface | PCI Express x1 |
| Bus Transmission | 10BASE-2 |
| Physical Connector | BNC |
| External Connector | YCB146 T-type Connector |
| Maximum Cable Distance | 185 m with 10BASE-2 cable only |
| VF701 Compatibility | Supported |
| Minimum Software Revision | R3.05 |
02 | Communication Interface Specifications
V net Control Bus Connection
| Connection Method | Coaxial cable connection |
| Compatible Cable Connector | YCB146 T-type connector |
| Transmission Standard | 10BASE-2 |
| Physical Connector | BNC connector |
| Maximum Transmission Distance | 185 m |
The BNC connector provides the physical connection to the V net control bus through the T-type connector. The specified 185 m distance applies when using 10BASE-2 cable only.
Engineering Consideration: Follow the applicable V net network topology and coaxial cable installation requirements. Do not treat the 185 m specification as a general Ethernet cable distance.
03 | PCI Express Host Interface
| Interface Standard | PCI Express CEM Specification 1.0a |
| Link Configuration | x1 |
| Signaling Rate | 2.5 GT/s |
| Supported Slot Sizes | PCI Express x1 to x16 |
| PCI Slot Compatibility | Not supported |
The VF702 uses a PCI Express x1 electrical interface. It can operate in compatible PCI Express slots from x1 through x16.
Important: A conventional PCI slot is not compatible. Verify the motherboard slot type before ordering or installing the card.
04 | Electrical & Power Requirements
| Power Supply Voltage | 3.3 V DC ±9% |
| Maximum Current Consumption | 2.4 A |
| Power Interface | PCI Express Slot |
The card receives its operating power through the PCI Express interface. Check the host system's available 3.3 V power capacity before installation.
05 | Front Panel Indicators & Hardware Functions
| Component | Function |
| RCV Lamp | Lights when the card detects signals on the control bus. |
| SND Lamp | Lights when the card transmits signals to the control bus. |
| BNC Connector | Connects the YCB146 T-type connector to the control bus. |
The RCV and SND indicators provide direct communication activity information. Maintenance personnel can use these indicators during initial network checks.
- RCV: Indicates received control bus signals.
- SND: Indicates transmitted control bus signals.
- BNC: Provides the coaxial network connection.
06 | VF701 Migration & System Compatibility
The VF702 maintains V net interface compatibility with the earlier VF701 card. Both card types can operate on the same control bus.
| Compatibility Item | Specification |
| VF701 V net Interface | Compatible |
| Mixed Card Installation | VF701 and VF702 stations can share one control bus. |
| Domain Number Configuration | Same configuration method as VF701 |
| Station Number Configuration | Same configuration method as VF701 |
| Minimum System Revision | R3.05 |
Migration Advantage: Existing VF701 installations can introduce VF702-equipped stations without requiring a different V net interface configuration method.
Engineers should still verify the complete system configuration and supported host hardware before upgrading.
07 | Mechanical Dimensions & Installation Requirements
| Width | 22 mm |
| Height | 126.5 mm |
| Depth | 193.54 mm |
| Weight | Approximately 0.15 kg |
| Additional Connector Weight | T-type connector excluded |

Tags
Q: Are these parts 100% original and new?
A: Yes. Every component is guaranteed to be 100% original, brand-new, and factory-sealed. We also provide a 12-month comprehensive warranty for your peace of mind.
Q: How fast is the shipping to my country?
A: For in-stock items, we offer same-day dispatch. International express shipping (DHL/FedEx/UPS) typically delivers within 3–5 business days worldwide.
Q: Can I get a formal quotation with shipping costs?
A: Absolutely. Our sales team is ready to provide a detailed Proforma Invoice (PI) including the most competitive shipping rates for your location.
Q: Do you offer discounts for bulk orders?
A: We provide volume-based pricing for large projects or multiple-item orders. Please contact us to get our Best Price Guarantee.
12-Month Comprehensive Warranty
Every part supplied by Global PLC Spare Hub is covered by a 12-month warranty from the date of invoice.
- Coverage: Functional defects and hardware failures under normal operating conditions.
- Commitment: We provide immediate repair, replacement, or a full refund for any verified defective components to minimize your operational downtime.
Returns & Exchange Policy
We offer a 30-day return policy to ensure you receive the exact part your system requires.
- Eligibility: Returns are accepted for uninstalled items in their original, factory-sealed packaging.
- RMA Process: Please contact our support team to obtain a Return Merchandise Authorization (RMA) number before shipping.
- Fast Processing: Refunds or exchanges are processed within 3–5 business days after the returned item passes our technical inspection.
Need Technical Assistance?Not sure if this part is compatible with your system? [Consult our Engineers] before purchasing to ensure 100% compatibility.