Product Overview
The Pepperl+Fuchs KFD2-ST2-EX2 is a 2-channel isolated switch amplifier for industrial signal conditioning and hazardous-area applications.
This interface accepts dry contact or NAMUR sensor signals from field devices. It converts input states into active transistor outputs for control systems.
The module provides Line Fault Detection (LFD) for input circuit monitoring. Engineers can configure reversible operating modes through front-mounted DIP switches.
Its reinforced galvanic isolation protects signal circuits from electrical interference. The module also supports SIL 2 applications under IEC/EN 61508.
The KFD2-ST2-EX2 supports Power Rail or direct terminal power connections. Its compact B2 housing fits standard 35 mm DIN mounting rails.
Technical Specifications
| Brand | Pepperl+Fuchs |
| Model | KFD2-ST2-EX2 |
| Product Number | 181000 |
| Product Series | K-System |
| Product Type | 2-Channel Switch Amplifier / Isolated Barrier |
| Signal Type | Digital Input |
| Input Compatibility | Dry Contact and NAMUR Sensors |
| Output Type | Two Active Electronic Transistor Outputs |
| Safety Integrity Level | SIL 2 |
| Line Fault Detection | Input Circuit Breakage and Short-Circuit Monitoring |
| Configuration | Front-Mounted DIP Switches |
| Mounting | 35 mm DIN Rail |
| Housing | B2 |
1. Power Supply and Electrical Input
| Supply Connection | Power Rail or Terminals 14+, 15- |
| Rated Supply Voltage | 20–30 V DC |
| Ripple | ≤ 10% |
| Rated Current | ≤ 50 mA |
| Field Input Terminals | 1+, 2+, 3- / 4+, 5+, 6- |
| NAMUR Standard | EN 60947-5-6 |
| Open-Circuit Voltage | Approximately 8 V DC |
| Short-Circuit Current | Approximately 8 mA |
| Switching Threshold | 1.2–2.1 mA |
| Switching Hysteresis | Approximately 0.2 mA |
2. Output and Signal Performance
| Output Channels | 2 |
| Output I Connection | Terminal 7+ |
| Output II Connection | Terminal 9+ |
| Output Technology | Active Electronic Transistor |
| Logic 1 Signal | (L+) - 3.5 V at 100 mA |
| Logic 0 Signal | Switched Off |
| Off-State Current | ≤ 10 µA |
| Output Protection | Short-Circuit Protected |
| Maximum Switching Frequency | ≤ 5 kHz |
| Collective Fault Indication | Power Rail |
3. Galvanic Isolation and Safety Performance
- Input / Output: Reinforced insulation according to IEC 62103.
- Input / Power Supply: Reinforced insulation according to IEC 62103.
- Rated Insulation Voltage: 300 Vrms.
- Input / Input: No galvanic isolation.
- Output / Output: No galvanic isolation.
- Output / Power Supply: No galvanic isolation.
- Common Pole: Terminal 14+.
- Functional Safety: SIL 2.
Engineering Note: The input channels share a common electrical reference. Both outputs also share a common pole. Do not treat these channels as independently isolated circuits.
4. Hazardous-Area Parameters and Certifications
| EU-Type Examination Certificate | PTB 00 ATEX 2035 |
| ATEX Gas Marking | II (1) G [Ex ia] IIC |
| ATEX Dust Marking | II (1) D [Ex ia] IIIC |
| Input Protection | Ex ia IIC / Ex ia IIIC |
| Maximum Output Voltage Uo | 10.5 V |
| Maximum Output Current Io | 13 mA |
| Maximum Output Power Po | 34 mW |
| Power Characteristic | Linear |
| Maximum Safe Supply Voltage Um | 40 V DC |
| Maximum Safe Output Voltage Um | 40 V DC |
Important: The 40 V DC Um value represents a maximum safe voltage. It does not replace the 20–30 V DC rated supply requirement.
Verify the complete intrinsically safe circuit parameters before connecting field devices. Check sensor entity parameters, cable capacitance, and cable inductance against the applicable installation requirements.
5. Environmental and Mechanical Specifications
| Operating Temperature | -20 to +60 °C (-4 to +140 °F) |
| Protection Rating | IP20 |
| Terminal Type | Screw Terminals |
| Housing Dimensions | 20 × 119 × 115 mm (W × H × D) |
| Housing Type | B2 |
| Approximate Weight | 150 g |
| Mounting Standard | EN 60715:2001 |
| Mounting Method | 35 mm DIN Rail |
6. Indicators and Configuration
- LED Indicators: Provide visual operating status information.
- DIP Switches: Configure the operating mode.
- Reversible Operation: Supports selectable signal logic.
- Front Labeling Area: Allows equipment identification.
- Power Rail: Supports supply distribution and collective fault signaling.
Installation Guide
Step 1 – Verify Installation Conditions
- Confirm the model number matches KFD2-ST2-EX2.
- Check the cabinet temperature and available DIN rail space.
- Verify the 20–30 V DC supply voltage.
- Review hazardous-area wiring requirements before installation.
Step 2 – Mount the Interface
- Install the module on a standard 35 mm DIN rail.
- Ensure secure mechanical engagement.
- Maintain sufficient space for wiring and ventilation.
- Protect the IP20 enclosure from moisture and conductive contamination.
Step 3 – Connect Field Sensors
- Connect channel 1 using terminals 1+, 2+, and 3-.
- Connect channel 2 using terminals 4+, 5+, and 6-.
- Observe the correct polarity for NAMUR sensors.
- Use suitable resistor arrangements for compatible dry-contact LFD monitoring.
Step 4 – Connect Control-Side Outputs
- Connect output I through terminal 7+.
- Connect output II through terminal 9+.
- Check the shared electrical reference at terminal 14+.
- Verify PLC input compatibility with active transistor outputs.
Step 5 – Apply Power
- Connect the supply through Power Rail or terminals 14+ and 15-.
- Verify supply polarity and voltage.
- Inspect LED indications after energization.
- Test each input and its corresponding output.

Tags
Q: Are these parts 100% original and new?
A: Yes. Every component is guaranteed to be 100% original, brand-new, and factory-sealed. We also provide a 12-month comprehensive warranty for your peace of mind.
Q: How fast is the shipping to my country?
A: For in-stock items, we offer same-day dispatch. International express shipping (DHL/FedEx/UPS) typically delivers within 3–5 business days worldwide.
Q: Can I get a formal quotation with shipping costs?
A: Absolutely. Our sales team is ready to provide a detailed Proforma Invoice (PI) including the most competitive shipping rates for your location.
Q: Do you offer discounts for bulk orders?
A: We provide volume-based pricing for large projects or multiple-item orders. Please contact us to get our Best Price Guarantee.
12-Month Comprehensive Warranty
Every part supplied by Global PLC Spare Hub is covered by a 12-month warranty from the date of invoice.
- Coverage: Functional defects and hardware failures under normal operating conditions.
- Commitment: We provide immediate repair, replacement, or a full refund for any verified defective components to minimize your operational downtime.
Returns & Exchange Policy
We offer a 30-day return policy to ensure you receive the exact part your system requires.
- Eligibility: Returns are accepted for uninstalled items in their original, factory-sealed packaging.
- RMA Process: Please contact our support team to obtain a Return Merchandise Authorization (RMA) number before shipping.
- Fast Processing: Refunds or exchanges are processed within 3–5 business days after the returned item passes our technical inspection.
Need Technical Assistance?Not sure if this part is compatible with your system? [Consult our Engineers] before purchasing to ensure 100% compatibility.