Home KFD2-SL2-Ex1.LK Pepperl+Fuchs Solenoid Driver | ATEX Safe Output Module

KFD2-SL2-Ex1.LK Pepperl+Fuchs Solenoid Driver | ATEX Safe Output Module

  • Manufacturer: Pepperl+Fuchs

  • Product No.: KFD2-SL2-Ex1.LK

  • Condition: In stock

  • Product Type: Safe Output Module

  • Product Origin: DE

  • Payment: T/T, Western Union

  • Weight: 150g

  • Shipping port: Xiamen

  • Warranty: 12 months

Selected quantity: 1
Request a quote

Estimate delivery times: 12-26 days (International), 3-6 days (United States).

Return within 30 days of purchase. Duties & taxes are non-refundable.

Guaranteed Safe Checkout

Visa
PayPal
Mastercard
American Express

1. Product Overview | Intrinsically Safe Solenoid Actuation

The KFD2-SL2-Ex1.LK from Pepperl+Fuchs is a single-channel isolated solenoid driver for industrial process control and hazardous-area applications.

This K-System interface transfers digital control signals from safe-area controllers to intrinsically safe field loads. It drives compatible solenoid valves and other approved field actuators with an output of up to 45 mA at a minimum of 11.2 V DC.

The module accepts non-polarized logic inputs and supports line fault detection. A separate fault relay provides diagnostic signaling to the control system.

Its design combines intrinsically safe output protection, configurable operating logic, and SIL 2 functional safety suitability. Engineers can install the module on a standard 35 mm DIN rail.

Core Engineering Functions:

  • One intrinsically safe digital output channel.
  • Non-polarized control-side logic input.
  • 45 mA maximum output current.
  • Minimum output voltage of 11.2 V DC.
  • Open-circuit and short-circuit monitoring.
  • Separate fault indication relay.
  • SIL 2 suitability according to IEC 61508.

2. Product Identification and Functional Architecture

Manufacturer Pepperl+Fuchs
Model KFD2-SL2-Ex1.LK
Product Family K-System
Product Type Solenoid Driver / Isolated Barrier
Signal Classification Digital Output
Channel Configuration 1 Channel
Field-Side Function Intrinsically Safe Solenoid Actuation
Control-Side Input Non-Polarized Logic Input
Diagnostic Function Line Fault Detection and Fault Relay
Functional Safety SIL 2
Housing Type B2
Mounting 35 mm DIN Rail

3. Electrical Supply and Control-Side Input

The module receives operating power through Power Rail or dedicated supply terminals. The control-side input accepts standard DC logic signals.

Supply Connection Power Rail or Terminals 14+, 15-
Rated Supply Voltage 19–30 V DC
Maximum Power Dissipation 1.5 W
Maximum Power Consumption 2 W at 45 mA output current
Control Input Terminals 7, 8
Input Current Approximately 3 mA
Input Polarity Non-Polarized
Logic 1 16–30 V DC
Logic 0 0–5 V DC

Control Interface Note: The input requires a valid DC logic level. Check the controller output voltage and available drive current before connecting terminals 7 and 8.

4. Intrinsically Safe Output and Solenoid Drive Performance

The field-side output supplies the energy required to operate compatible intrinsically safe loads. Its electrical limits determine actuator selection and field-circuit design.

Output Channel Output I
Output Terminals 1+, 2- or 3-
Internal Resistance 270 Ω
Maximum Output Current 45 mA
Minimum Output Voltage 11.2 V DC
Minimum Open-Circuit Voltage 23.5 V
Energizing Delay ≤ 20 ms
De-energizing Delay ≤ 20 ms
Output Classification Intrinsically Safe Ex ia

Load Selection: Confirm the solenoid's pickup voltage, holding current, coil resistance, and minimum operating power. The field load must remain within the driver's electrical output limits.

Do not select an actuator using current rating alone. Its voltage requirement and intrinsic safety parameters also determine compatibility.

5. Line Fault Detection and Diagnostic Relay

The KFD2-SL2-Ex1.LK monitors the field output circuit for wiring abnormalities. This function helps maintenance teams distinguish load-circuit faults from normal operating conditions.

Short-Circuit Detection RB below 50 Ω
Lead-Break Detection RB above 10 kΩ
LFD Test Current Below 650 µA
Fault Output Terminals 10, 11, 12
Fault Output Type Relay Contact
Relay Energizing Delay ≤ 20 ms
Relay De-energizing Delay ≤ 20 ms

Diagnostic Relay Contact Ratings:

  • 253 V AC / 2 A at cos φ greater than 0.7.
  • 40 V DC / 2 A with resistive load.
  • Mechanical service life: 2 × 107 switching cycles.
  • The fault relay output is non-intrinsically safe.

Engineering Note: The LFD circuit uses a low test current. Verify the connected actuator and field wiring arrangement against the manufacturer's documentation. Do not assume that every solenoid load supports identical fault-detection behavior.

6. Galvanic Isolation and Electrical Separation

Input / Power Supply Basic insulation according to IEC/EN 61010-1
Input / Supply Insulation Voltage 50 Veff
Output I / Output II Reinforced insulation
Output I / Output II Insulation Voltage 300 Veff
Output II / Power Supply Reinforced insulation
Output II / Supply Insulation Voltage 300 Veff
Output I / Other Circuits Safe electrical isolation according to IEC/EN 60079-11
Peak Isolation Voltage 375 V

These insulation specifications define the electrical separation between functional circuits. Maintain the specified wiring separation during panel installation.

7. Hazardous-Area Certifications and Safety Parameters

The module supports intrinsically safe field output applications in hazardous gas, dust, and mining environments. Its approval data includes ATEX, IECEx, and CSA references.

ATEX Examination Certificate ZELM 99 ATEX 0015
ATEX Gas Marking II (1)G [Ex ia Ga] IIC
ATEX Dust Marking II (1)D [Ex ia Da] IIIC
Mining Marking I (M1) [Ex ia Ma] I
Output Protection Ex ia
Maximum Output Voltage Uo 28 V
Maximum Output Current Io 110 mA
Maximum Output Power Po 770 mW
Output Characteristic Linear
ATEX Certificate for Output II TÜV 02 ATEX 1820 X
Output II Marking II 3G Ex nA nC IIC T4 Gc
IECEx Certificate IECEx ZLM 14.0001
IECEx Marking [Ex ia Ga] IIC, [Ex ia Da] IIIC, [Ex ia Ma] I
CSA Approval Control Drawing 116-0362

Maximum Safe Voltage Limits:

  • Power supply Um: 40 V.
  • Control input Um: 60 V.
  • Collective fault message Um: 40 V.

Important Safety Distinction: The 28 V Uo, 110 mA Io, and 770 mW Po values describe the intrinsic safety output parameters. They do not represent the normal solenoid operating voltage and current. The normal output specifications remain 11.2 V minimum and 45 mA maximum.

Always check the current certificate, control drawing, entity parameters, and installation conditions before connecting hazardous-area equipment.

8. Mechanical Design and Environmental Conditions

Operating Temperature -20 to +60 °C (-4 to +140 °F)
Enclosure Protection IP20
Housing Type B2
Dimensions 20 × 119 × 115 mm
Approximate Weight 150 g
Electrical Connections Screw Terminals
Mounting Standard EN 60715:2001
Mounting Method 35 mm DIN Rail

Tags

Q: Are these parts 100% original and new?

A: Yes. Every component is guaranteed to be 100% original, brand-new, and factory-sealed. We also provide a 12-month comprehensive warranty for your peace of mind.

Q: How fast is the shipping to my country?

A: For in-stock items, we offer same-day dispatch. International express shipping (DHL/FedEx/UPS) typically delivers within 3–5 business days worldwide.

Q: Can I get a formal quotation with shipping costs?

A: Absolutely. Our sales team is ready to provide a detailed Proforma Invoice (PI) including the most competitive shipping rates for your location.

Q: Do you offer discounts for bulk orders?

A: We provide volume-based pricing for large projects or multiple-item orders. Please contact us to get our Best Price Guarantee.




12-Month Comprehensive Warranty

Every part supplied by Global PLC Spare Hub is covered by a 12-month warranty from the date of invoice.

  • Coverage: Functional defects and hardware failures under normal operating conditions.
  • Commitment: We provide immediate repair, replacement, or a full refund for any verified defective components to minimize your operational downtime.

Returns & Exchange Policy

We offer a 30-day return policy to ensure you receive the exact part your system requires.

  • Eligibility: Returns are accepted for uninstalled items in their original, factory-sealed packaging.
  • RMA Process: Please contact our support team to obtain a Return Merchandise Authorization (RMA) number before shipping.
  • Fast Processing: Refunds or exchanges are processed within 3–5 business days after the returned item passes our technical inspection.

Need Technical Assistance?Not sure if this part is compatible with your system? [Consult our Engineers] before purchasing to ensure 100% compatibility.