Home KFD2-GUT-Ex1.D Pepperl+Fuchs Temperature Converter K-System Isolated Barrier

KFD2-GUT-Ex1.D Pepperl+Fuchs Temperature Converter K-System Isolated Barrier

  • Manufacturer: Pepperl+Fuchs

  • Product No.: KFD2-GUT-Ex1.D

  • Condition: In stock

  • Product Type: Isolated Barrier Module

  • Product Origin: USA

  • Payment: T/T, Western Union

  • Weight: 200g

  • Shipping port: Xiamen

  • Warranty: 12 months

Selected quantity: 1
Request a quote

Estimate delivery times: 12-26 days (International), 3-6 days (United States).

Return within 30 days of purchase. Duties & taxes are non-refundable.

Guaranteed Safe Checkout

Visa
PayPal
Mastercard
American Express

Engineering Overview & Architecture

The KFD2-GUT-Ex1.D temperature converter by Pepperl+Fuchs operates as a premier 1-channel intrinsically safe isolated barrier designed for hazardous process environments. It bridges field-level thermal sensors with control room systems by converting diverse input signals into a proportional 0/4 mA to 20 mA analog transmission stream alongside dual relay trip channels. Built for DIN-rail deployment, the unit integrates seamlessly into modern process automation networks requiring SIL 2 functional safety compliance.

Core Operational Metrics

Performance Parameter Technical Specification
Manufacturer & Series Pepperl+Fuchs | K-System Ex-Barrier
Exact Model Number KFD2-GUT-Ex1.D
Input Sensor Compatibility RTD (Pt100, Pt500, Pt1000, Ni100, Ni1000 in 2-, 3-, 4-wire), Thermocouples (Types B, E, J, K, L, N, R, S, T), Potentiometers (0.8 to 20 kΩ), and DC Voltage (up to 10 V).
Analog Output Range 0 to 20 mA or 4 to 20 mA sourcing with NAMUR NE43 fault downscale/upscale logic. Maximum load resistance up to 650 Ω.
Relay Switching Limits Two independent electromechanical relays rated up to 250 V AC / 2 A (cos φ ≥ 0.7) and 40 V DC / 2 A resistive load.
Supply Voltage & Power 20 to 30 V DC, nominal 24 V DC via terminals or Power Rail feed module, consuming less than 2.2 W.
System Accuracy & Drift Input drift of 0.005 %/K (50 ppm) of span; RTD measurement deviation within 0.2 % of span. Sampling rate approx. 700 ms.
Galvanic Isolation Rating Safe galvanic isolation up to 375 V peak value between input, output, power supply, and interface circuits.
Environmental Envelope Operating temperature range from -20 °C to 60 °C with IP20 enclosure protection. Weight approx. 300 g.
Hazardous Area Approvals ATEX certification TÜV 03 ATEX 2140 [Ex ia] IIC / [Ex iaD] and Ex nA nC IIC T4 X compliance.

Mechanical Deployment Guidelines

  • Snap the unit directly onto a standard 35 mm DIN mounting rail conforming to DIN EN 60715 inside the control cabinet.
  • Utilize the optional Power Rail feed backbone to distribute 24 V DC power across adjacent modules and enable collective error messaging.
  • Attach a removable cold junction compensation terminal block directly to the unit faceplate when deploying thermocouples with internal reference tracking.
  • Maintain adequate vertical spacing above and below the enclosure to optimize natural thermal dissipation across the specified ambient range.

Configuration & Diagnostic Procedures

  • Program measurement parameters, span scaling, and trip thresholds locally using the integrated front-panel push buttons and LCD screen.
  • Connect an RS-232 interface cable to execute advanced parameter mapping and diagnostic logging via PACTware™ software.
  • Monitor real-time sensor health through built-in line fault detection (LFD), sensor burnout tracking, and short-circuit diagnostics.
  • Evaluate collective error flags instantly via the Power Rail bus without requiring individual diagnostic wiring loops.

Frequently Asked Questions (FAQ)

Q: How does the device handle internal versus external cold junction compensation for thermocouples?

A: Engineers can choose internal compensation by mounting a dedicated K-CJC terminal block onto the unit, or wire an external reference junction directly into the input terminals.

Q: What occurs to the analog output signal when a sensor wire breaks in the field?

A: The unit drives the current output down to less than or equal to 3.6 mA or up to greater than or equal to 21 mA in compliance with NAMUR NE43 standards based on user configuration.

Q: Can the KFD2-GUT-Ex1.D process redundant thermocouple inputs simultaneously?

A: Yes, the unit supports redundant thermocouple configurations to ensure uninterrupted measurement continuity should a primary sensing element fail.

Q: What precautions are necessary when switching inductive DC loads with the relay outputs?

A: Technicians must install appropriate arc suppression networks or freewheeling diodes across inductive loads to prevent contact pitting and extend mechanical relay life.

Q: Is it possible to configure this unit offline before installing it into a live control cabinet?

A: Yes, engineers can use PACTware™ and a suitable interface cable to configure all operational parameters on a workbench prior to physical panel deployment.

Procurement & Inquiry Guidance

To integrate the KFD2-GUT-Ex1.D temperature converter into your industrial automation infrastructure, verify your hazardous area classification and sensor input types. Contact our sales engineering team today to request a formal quotation, check current factory stock levels, and secure rapid logistics dispatch for your project requirements.

Tags

Q: Are these parts 100% original and new?

A: Yes. Every component is guaranteed to be 100% original, brand-new, and factory-sealed. We also provide a 12-month comprehensive warranty for your peace of mind.

Q: How fast is the shipping to my country?

A: For in-stock items, we offer same-day dispatch. International express shipping (DHL/FedEx/UPS) typically delivers within 3–5 business days worldwide.

Q: Can I get a formal quotation with shipping costs?

A: Absolutely. Our sales team is ready to provide a detailed Proforma Invoice (PI) including the most competitive shipping rates for your location.

Q: Do you offer discounts for bulk orders?

A: We provide volume-based pricing for large projects or multiple-item orders. Please contact us to get our Best Price Guarantee.




12-Month Comprehensive Warranty

Every part supplied by Global PLC Spare Hub is covered by a 12-month warranty from the date of invoice.

  • Coverage: Functional defects and hardware failures under normal operating conditions.
  • Commitment: We provide immediate repair, replacement, or a full refund for any verified defective components to minimize your operational downtime.

Returns & Exchange Policy

We offer a 30-day return policy to ensure you receive the exact part your system requires.

  • Eligibility: Returns are accepted for uninstalled items in their original, factory-sealed packaging.
  • RMA Process: Please contact our support team to obtain a Return Merchandise Authorization (RMA) number before shipping.
  • Fast Processing: Refunds or exchanges are processed within 3–5 business days after the returned item passes our technical inspection.

Need Technical Assistance?Not sure if this part is compatible with your system? [Consult our Engineers] before purchasing to ensure 100% compatibility.