KFD0-SD2-EX1.1045 Pepperl+Fuchs Solenoid Driver | K-System Safety Barrier
Manufacturer: Pepperl+Fuchs
Product No.: KFD0-SD2-EX1.1045
Condition: In stock
Product Type: Solenoid Driver
Product Origin: DE
Payment: T/T, Western Union
Weight: 150g
Shipping port: Xiamen
Warranty: 12 months
Estimate delivery times: 12-26 days (International), 3-6 days (United States).
Return within 30 days of purchase. Duties & taxes are non-refundable.
Guaranteed Safe Checkout
01 | Product Identity & Operating Principle
The KFD0-SD2-EX1.1045 is a single-channel solenoid driver from Pepperl+Fuchs. It belongs to the K-System isolated barrier family.
This module transfers digital output signals from control equipment to hazardous-area field devices. It provides an intrinsically safe output for compatible solenoid valves and other suitable loads.
The device uses a loop-powered architecture. It operates with a 20–35 V DC control-side supply. Its output limits current to 45 mA while maintaining at least 10 V DC under specified operating conditions.
Its compact B1 housing supports DIN rail installation. LED indication helps technicians identify operating conditions. Reinforced application design supports functional safety requirements up to SIL 3.
02 | Core Technical Data
| Manufacturer | Pepperl+Fuchs |
| Model | KFD0-SD2-EX1.1045 |
| Product Series | K-System |
| Product Type | Solenoid Driver / Isolated Barrier |
| Signal Classification | Digital Output |
| Channel Count | 1 Channel |
| Power Architecture | Loop Powered |
| Supply Voltage | 20–35 V DC |
| Maximum Output Current | 45 mA |
| Minimum Output Voltage | 10 V DC |
| Maximum Internal Resistance | 282 Ω |
| Functional Safety | SIL 3 |
| Hazardous Area Protection | Intrinsic Safety Ex ia |
| Mounting | 35 mm DIN Rail |
| Protection Rating | IP20 |
03 | Electrical Performance & Output Characteristics
Control-Side Input
| Connection Terminals | 7, 8 |
| Rated Input Voltage | 20–35 V DC |
| Input Current at 20 V | 72 mA with 220 Ω load |
| Input Current at 35 V | 50 mA with 220 Ω load |
| Inrush Current | ≤ 200 mA after 100 µs |
| Power Dissipation | < 1.05 W at ≤ 30 V |
Field-Side Output
| Connection Terminals | 1+, 2- |
| Maximum Internal Resistance | 282 Ω |
| Output Current | ≤ 45 mA |
| Minimum Output Voltage | ≥ 10 V |
| Minimum Open-Loop Voltage | 22.7 V |
| Rated Operating Current | 45 mA |
Switching Response
| Single Operation Energized Delay | Typical 1.7 ms |
| Single Operation De-energized Delay | 50 µs |
| Periodic Operation Energized Delay | Typical 5 µs |
| Periodic Operation De-energized Delay | 50 µs |
These electrical values apply within the specified 20–35 V DC operating range. Check the actual field load before selecting the driver.
04 | Intrinsic Safety & Hazardous Area Parameters
The KFD0-SD2-EX1.1045 provides an intrinsically safe field interface. Its certified output parameters help engineers evaluate compatible hazardous-area loads.
| EU-Type Examination Certificate | BASEEFA 06 ATEX 0252 |
| Additional Certificate | TÜV 99 ATEX 1499 X |
| Gas Classification | II (1)G [Ex ia Ga] IIC |
| Dust Classification | II (1)D [Ex ia Da] IIIC |
| Mining Classification | I (M1) [Ex ia Ma] I |
| Output Voltage Uo | 25.2 V |
| Output Current Io | 93 mA |
| Output Power Po | 590 mW |
| Maximum Safe Input Voltage Um | 250 V |
| Input/Output Isolation | 375 V peak value |
| Isolation Standard | IEC/EN 60079-11 |
Additional Ex nA Marking
- Certificate: TÜV 99 ATEX 1499 X.
- Classification: II 3G Ex nA II T4.
Important Engineering Note: Uo, Io, and Po are safety assessment parameters. They are not normal operating output values. Verify the complete intrinsic safety loop, including cable capacitance, inductance, and field-device ratings.
05 | International Approvals & Compliance
| ATEX Certificate | BASEEFA 06 ATEX 0252 |
| Additional ATEX Certificate | TÜV 99 ATEX 1499 X |
| IECEx Certificate | IECEx BAS 06.0058 |
| IECEx Certificate | IECEx CML 19.0093X |
| FM Approval | Control Drawing 116-0309 |
| UL Approval | E106378 |
| cULus Control Drawing | 116-0316 |
| EMC Directive | 2014/30/EU |
| EMC Standard | EN 61326-1:2013 |
| EMC Recommendation | NE 21:2006 |
| Electrical Shock Protection | UL 61010-1:2004 |
| Ingress Protection Standard | IEC 60529:2001 |
| ATEX Directive | 2014/34/EU |
| Explosion Protection Standards | EN IEC 60079-0:2018+AC:2020, EN 60079-11:2012, EN 60079-15:2010 |
06 | Mechanical Design & Environmental Limits
| Housing Type | B1 |
| Dimensions (W × H × D) | 20 × 107 × 115 mm |
| Weight | Approximately 100 g |
| Operating Temperature | -20 to +60 °C (-4 to +140 °F) |
| Protection Rating | IP20 |
| Electrical Connection | Screw Terminals |
| Mounting Method | 35 mm DIN Rail |
| Mounting Standard | EN 60715:2001 |
| Status Display | LED |
| Front Labeling | Labeling Space Available |
07 | Application Scenarios & Control Functions
- Solenoid Valve Control: Drives compatible intrinsically safe solenoid loads from control-side digital outputs.
- Process Shutdown Systems: Supports suitable safety-related output circuits in process installations.
- Hazardous Area Equipment: Interfaces field devices in certified gas, dust, and mining environments.
- Industrial Valve Automation: Controls compatible pneumatic valve actuators through solenoid interfaces.
- PLC Digital Outputs: Connects control-system output channels to suitable field-side loads.
- Safety Instrumented Systems: Supports SIL 3 applications when the complete safety loop meets required conditions.
08 | Wiring & Commissioning Reference
Terminal Assignment
| Terminal | Connection Side | Function |
| 7, 8 | Control Side | Digital control input |
| 1+, 2- | Field Side | Intrinsically safe output |

Tags
Q: Are these parts 100% original and new?
A: Yes. Every component is guaranteed to be 100% original, brand-new, and factory-sealed. We also provide a 12-month comprehensive warranty for your peace of mind.
Q: How fast is the shipping to my country?
A: For in-stock items, we offer same-day dispatch. International express shipping (DHL/FedEx/UPS) typically delivers within 3–5 business days worldwide.
Q: Can I get a formal quotation with shipping costs?
A: Absolutely. Our sales team is ready to provide a detailed Proforma Invoice (PI) including the most competitive shipping rates for your location.
Q: Do you offer discounts for bulk orders?
A: We provide volume-based pricing for large projects or multiple-item orders. Please contact us to get our Best Price Guarantee.
12-Month Comprehensive Warranty
Every part supplied by Global PLC Spare Hub is covered by a 12-month warranty from the date of invoice.
- Coverage: Functional defects and hardware failures under normal operating conditions.
- Commitment: We provide immediate repair, replacement, or a full refund for any verified defective components to minimize your operational downtime.
Returns & Exchange Policy
We offer a 30-day return policy to ensure you receive the exact part your system requires.
- Eligibility: Returns are accepted for uninstalled items in their original, factory-sealed packaging.
- RMA Process: Please contact our support team to obtain a Return Merchandise Authorization (RMA) number before shipping.
- Fast Processing: Refunds or exchanges are processed within 3–5 business days after the returned item passes our technical inspection.
Need Technical Assistance?Not sure if this part is compatible with your system? [Consult our Engineers] before purchasing to ensure 100% compatibility.