IMASO11 ABB Analog Output Module | INFI 90 OPEN 14-Point
Manufacturer: ABB
Product No.: IMASO11
Condition: In stock
Product Type: Analog Output Module
Product Origin: USA
Payment: T/T, Western Union
Weight: 500g
Shipping port: Xiamen
Warranty: 12 months
Estimate delivery times: 12-26 days (International), 3-6 days (United States).
Return within 30 days of purchase. Duties & taxes are non-refundable.
Guaranteed Safe Checkout
ABB IMASO11 INFI 90 OPEN Analog Output Module
The ABB IMASO11 is a 14-channel analog output module designed for the INFI 90 OPEN distributed control system. It converts digital control data into analog signals for field-level process regulation.
Each output supports 1–5 VDC or 4–20 mA operation. The module provides 10-bit digital-to-analog conversion, defined output accuracy, and load limits for voltage and current applications.
Engineers can use the IMASO11 to interface controller output commands with compatible final control elements and analog signal devices. Its LED indicators also help identify communication status and bus-related faults during commissioning and maintenance.
01 | Output Channel Architecture
| Parameter | Specification |
|---|---|
| Product model | IMASO11 |
| Brand | ABB |
| System family | INFI 90 OPEN |
| Module type | Analog output module |
| Number of outputs | 14 |
| Output signal modes | 4–20 mA and 1–5 VDC |
| D/A resolution | 10 bits |
| Voltage output accuracy | ≤0.15% |
| Current output accuracy | ≤0.25% |
02 | Analog Signal Performance
The IMASO11 supports two analog signal formats for different control-system interfaces. Select the appropriate operating mode according to the connected field device and system configuration.
| Output Parameter | Voltage Mode | Current Mode |
|---|---|---|
| Signal range | 1–5 VDC | 4–20 mA |
| D/A resolution | 10 bits | 10 bits |
| Output accuracy | ≤0.15% | ≤0.25% |
| Load requirement | 22 kΩ minimum | 750 Ω maximum |
Engineering considerations:
- Voltage-mode applications require a load impedance of at least 22 kΩ.
- Current-mode applications must keep the total loop load at or below 750 Ω.
- Check cable resistance and connected instrument impedance when calculating the output load.
- Verify the selected signal mode before connecting the field wiring.
- Use the specified accuracy values when evaluating control-loop performance.
03 | Output Protection and Electrical Safety
| Protection Parameter | Specification |
|---|---|
| Output current limiting | Provided |
| Short-circuit protection | Provided |
| Nominal output current limit | 50 mA |
| Output overvoltage category | Category III |
| Reference standard | ANSI/ISA S82.01-1994 |
The module includes output current limiting and short-circuit protection. The specified nominal current limit is 50 mA.
The output circuit uses Overvoltage Category III classification under ANSI/ISA S82.01-1994. Follow the applicable cabinet wiring and installation requirements when integrating the module.
04 | Power Supply and Consumption Budget
The IMASO11 requires multiple DC supply rails. The +24 VDC supply comes from the termination unit or termination module. Check all supply rails before commissioning.
| Supply Rail | Voltage Tolerance | Typical Current | Typical Power Dissipation |
|---|---|---|---|
| +5 VDC | ±5% | 250 mA | 1.5 W |
| +15 VDC | ±5% | 100 mA | 2 W |
| -15 VDC | ±5% | 90 mA | 1.75 W |
| +24 VDC | ±10% | 310 mA | 8 W |
Power supply classification: Category I for power circuits, according to ANSI/ISA S82.01-1994.
Commissioning recommendation: Measure each supply rail under operating conditions. Confirm polarity, voltage tolerance, and termination-unit supply capacity before enabling the module.
05 | Environmental Operating Limits
| Environmental Parameter | Operating Specification |
|---|---|
| Ambient temperature | 0°C to 70°C |
| Relative humidity up to 55°C | 0% to 95%, noncondensing |
| Relative humidity at 70°C | 0% to 45%, noncondensing |
| Pollution degree | I, no condensation |
| Operating altitude | Sea level to 3 km |
| Air quality | Noncorrosive environment |
Maintain the module within its specified temperature and humidity limits. Prevent condensation and exposure to corrosive atmospheres. Confirm cabinet ventilation and installation conditions during system maintenance.
06 | Status LED Diagnostics
Two status LEDs indicate module power, enablement, and communication conditions. Use their combined states to identify the operating condition.
| Red LED | Green LED | Module Status |
|---|---|---|
| OFF | OFF | No power or module not enabled |
| OFF | ON | Enabled and communicating with control module |
| ON | OFF | Bus fault timer error or communication timeout |
| ON | ON | Not an allowed operating state |
Field troubleshooting sequence:
- Check the module supply rails if both LEDs remain OFF.
- Confirm that the control system enables the module.
- Inspect the communication path if the red LED indicates a timeout.
- Check controller status and system bus conditions.
- After correcting the fault, verify that the green LED turns ON and the red LED turns OFF.
07 | CE Compliance and Certification Information
When installed in an INFI 90 OPEN cabinet, the product complies with the following declared EMC and safety requirements:
- EMC Directive: 89/336/EEC
- Low Voltage Directive: 73/23/EEC
- EN 50082-2: Generic Immunity Standard, Industrial Environment
- EN 50081-2: Generic Emission Standard, Industrial Environment
- EN 61010-1: Safety Requirements for Electrical Equipment for Measurement, Control and Laboratory Use
Certification details:
- CSA: Certified for process control equipment in ordinary, nonhazardous locations.
- Nonincendive application categories: Class I, Division 2, Groups A, B, C, D.
- Nonincendive application categories: Class II, Division 2, Groups F, G.
- Factory Mutual (FM): Listed as pending in the supplied technical information.
Confirm the exact approval status and installation conditions against the product nameplate and applicable certification documentation. Do not treat the pending FM status as an issued approval.

Tags
Q: Are these parts 100% original and new?
A: Yes. Every component is guaranteed to be 100% original, brand-new, and factory-sealed. We also provide a 12-month comprehensive warranty for your peace of mind.
Q: How fast is the shipping to my country?
A: For in-stock items, we offer same-day dispatch. International express shipping (DHL/FedEx/UPS) typically delivers within 3–5 business days worldwide.
Q: Can I get a formal quotation with shipping costs?
A: Absolutely. Our sales team is ready to provide a detailed Proforma Invoice (PI) including the most competitive shipping rates for your location.
Q: Do you offer discounts for bulk orders?
A: We provide volume-based pricing for large projects or multiple-item orders. Please contact us to get our Best Price Guarantee.
12-Month Comprehensive Warranty
Every part supplied by Global PLC Spare Hub is covered by a 12-month warranty from the date of invoice.
- Coverage: Functional defects and hardware failures under normal operating conditions.
- Commitment: We provide immediate repair, replacement, or a full refund for any verified defective components to minimize your operational downtime.
Returns & Exchange Policy
We offer a 30-day return policy to ensure you receive the exact part your system requires.
- Eligibility: Returns are accepted for uninstalled items in their original, factory-sealed packaging.
- RMA Process: Please contact our support team to obtain a Return Merchandise Authorization (RMA) number before shipping.
- Fast Processing: Refunds or exchanges are processed within 3–5 business days after the returned item passes our technical inspection.
Need Technical Assistance?Not sure if this part is compatible with your system? [Consult our Engineers] before purchasing to ensure 100% compatibility.