IC694MDL340 Emerson PACSystem RX3i 16-Ch 120VAC Output Module
Manufacturer: GE
Product No.: IC694MDL340
Condition: In stock
Product Type: Discrete Output Module
Product Origin: USA
Payment: T/T, Western Union
Weight: 500g
Shipping port: Xiamen
Warranty: 12 months
Estimate delivery times: 12-26 days (International), 3-6 days (United States).
Return within 30 days of purchase. Duties & taxes are non-refundable.
Guaranteed Safe Checkout
Architectural Overview & Switching Topology
The IC694MDL340 engineered originally by GE Fanuc / GE Intelligent Platforms and currently supported by Emerson Automation operates as a high-density discrete output module within the PACSystem RX3i programmable automation controller platform. This module provides sixteen (16) AC output points arranged in two (2) isolated groups of eight (8) channels, driving 120 VAC industrial loads with robust optical isolation and integrated transient suppression.
Comprehensive Technical Specifications Matrix
| Engineering Parameter | Operational Specification |
|---|---|
| Manufacturer & Brand Heritage | GE Fanuc / Emerson Automation (GE Intelligent Platforms) |
| Model Number & Series | IC694MDL340 / PACSystem RX3i |
| Product Classification | Discrete AC Output Module (16 Channels) |
| Nominal Output Voltage | 120 Volts AC (50/60 Hz operating frequency range: 47 to 63 Hz) |
| Output Signal Voltage Range | 85 to 132 Volts AC |
| Channel Configuration | 16 output points split into 2 isolated groups of 8 channels each |
| Output Current Rating | 0.5 Amperes per individual point; 3.0 Amperes maximum per group |
| Minimum Load Current | 50 mA per channel |
| Maximum Inrush Current | 20 Amperes peak for duration of 1 full AC cycle |
| Output Voltage Drop | 1.5 Volts maximum at rated current |
| Off-State Leakage Current | 2 mA maximum at rated operating voltage |
| Switching Response Time | ON response: ≤ 1 ms maximum; OFF response: ≤ 1/2 cycle maximum |
| Backplane Power Draw | 315 mA nominal from the +5V DC bus (all outputs energized) |
| Galvanic Isolation Rating | 250 VAC continuous group-to-group isolation; 1500 VAC dielectric test for 1 minute |
| Onboard Group Fusing | Two (2) pre-installed 3A fuses (Replacement part equivalent: GE Fanuc 44A724627-111) |
| Operating Thermal Range | 0 °C to +60 °C (+32 °F to +140 °F) cabinet environment |
Environmental Resilience & Mechanical Ratings
- Storage Temperature: -40 °C to +85 °C (-40 °F to +185 °F) non-operating threshold.
- Relative Humidity: 5% to 95% non-condensing tolerance in industrial control enclosures.
- Vibration Tolerance: 10 to 57 Hz with 0.0524 mm (0.006 inches) peak displacement.
- Shock Resistance: 15 G peak acceleration maintained for 11 milliseconds duration.
Installation, Wiring & Commissioning Guide
- Power Supply Sourcing: Provide clean, user-supplied 120 VAC power sources to each isolated group common terminal, allowing multi-phase or single-phase field wiring configurations.
- Transient Suppression: Rely on the onboard built-in RC snubbers across each output group to suppress inductive kickback and electrical noise generated by solenoids and contactors.
- Status Diagnostics: Observe individual green channel LEDs for real-time output switching verification, and monitor the dedicated red "F" diagnostic LED to detect blown group fuses instantly.
- Hot-Insertion Protocol: Power down the RX3i backplane rack before sliding or securing the IC694MDL340 module into position to prevent connector arcing.
Package Contents
- 1 × GE Fanuc / Emerson IC694MDL340 PACSystem RX3i Output Module
- 2 × Pre-installed 3A Group Protection Fuses
- 1 × Hardware Installation & Safety Instruction Sheet
Engineering FAQ & Field Troubleshooting
Q1: Why do connected inductive loads flicker or remain weakly energized when the output channel turns OFF?
A1: High off-state leakage current (up to 2 mA) flowing through small interposing relays or pilot lights can sustain coil holding current. Add a parallel RC load resistor or dummy bleed resistor across the field terminals to drain residual leakage.
Q2: What occurs if a field short-circuit exceeds the 3 Ampere group current threshold?
A2: The corresponding pre-installed group fuse (compatible with GE part 44A724627-111) will blow instantly to protect the internal switching circuitry. Inspect field wiring for insulation faults before replacing the fuse and re-energizing.
Q3: Can the two output groups be connected to completely separate AC power supply phases?
A3: Yes. The module features complete group-to-group optical and electrical isolation rated at 250 VAC continuous, allowing Group 1 and Group 2 to operate on entirely independent 120 VAC supply lines or phases.
Q4: How should technicians troubleshoot a persistent fault ("F") LED on the front faceplate?
A4: The "F" LED illuminates primarily when an internal fuse is blown due to an overcurrent condition or shorted field load. Check continuity across both group fuses and verify that active channel current does not exceed the 0.5A point limit.
Q5: Does this output module require external dc control power from the backplane rack?
A5: The module draws 315 mA strictly from the rack's +5V DC backplane bus to power its internal logic and isolation barriers, while all field-side switching power for connected loads must be supplied externally via user AC lines.
Tags
Q: Are these parts 100% original and new?
A: Yes. Every component is guaranteed to be 100% original, brand-new, and factory-sealed. We also provide a 12-month comprehensive warranty for your peace of mind.
Q: How fast is the shipping to my country?
A: For in-stock items, we offer same-day dispatch. International express shipping (DHL/FedEx/UPS) typically delivers within 3–5 business days worldwide.
Q: Can I get a formal quotation with shipping costs?
A: Absolutely. Our sales team is ready to provide a detailed Proforma Invoice (PI) including the most competitive shipping rates for your location.
Q: Do you offer discounts for bulk orders?
A: We provide volume-based pricing for large projects or multiple-item orders. Please contact us to get our Best Price Guarantee.
12-Month Comprehensive Warranty
Every part supplied by Global PLC Spare Hub is covered by a 12-month warranty from the date of invoice.
- Coverage: Functional defects and hardware failures under normal operating conditions.
- Commitment: We provide immediate repair, replacement, or a full refund for any verified defective components to minimize your operational downtime.
Returns & Exchange Policy
We offer a 30-day return policy to ensure you receive the exact part your system requires.
- Eligibility: Returns are accepted for uninstalled items in their original, factory-sealed packaging.
- RMA Process: Please contact our support team to obtain a Return Merchandise Authorization (RMA) number before shipping.
- Fast Processing: Refunds or exchanges are processed within 3–5 business days after the returned item passes our technical inspection.
Need Technical Assistance?Not sure if this part is compatible with your system? [Consult our Engineers] before purchasing to ensure 100% compatibility.