PAC8000 System Architecture & Carrier Design
The 8710-CA-04 functions as a rugged 4-module carrier engineered for the GE Fanuc PAC8000 I/O platform. Built from modified polyphenylene oxide molding with an integrated epoxy resin glass laminate printed wiring board, this carrier supports up to four general-purpose I/O modules and field terminals while managing a 32-slot address bus. It distributes internal DC power, routes bussed field power, and carries critical control signals and data streams across the high-speed Railbus backplane.
Core Specifications & Engineering Matrix
| Parameter Classification | Technical Specification Details |
|---|---|
| Manufacturer & Series | GE Fanuc | PAC8000 I/O Series |
| Model Number & Type | Model: 8710-CA-04 (4-Module DIN/Panel Carrier) |
| Module Capacity | Accepts up to four general-purpose I/O modules and corresponding field terminals. |
| Address Bus Range | 32-slot address bus capability with individual module address range spanning 1–32. |
| Railbus Interconnects | Equipped with female-in and male-out Railbus connectors for daisy-chain data distribution. |
| Bussed Field Power Supply | Optional 8-pin connector situated at the top rear routes external supplies through specific I/O modules to power field instruments. |
| Earthing & Shield Protection | Integrated isolated earthing bar designed for secure cable screen and shield termination. |
| Physical Dimensions & Weight | 178 mm (Width) × 170 mm (Depth) × 22 mm (Height); Net weight: 350 g. |
Hazardous Area & Environmental Compliance
- Node Classification: Approved for Class 1, Div 2, Groups A, B, C, D T4 and Zone 2, IIC T4 hazardous operating locations.
- Field Wiring Location: Certified for installation matching the primary node hazardous area classification.
- Thermal Operating Envelope: Continuous operation rated from –40°C to +70°C; storage temperature range from –40°C to +85°C.
- Humidity Tolerance: Supports 5% to 95% relative humidity under non-condensing operating conditions.
- Mechanical Resilience: Built to withstand industrial vibration and shock profiles as defined in system specifications.
Mechanical Mounting Guidelines
- Mounting Flexibility: Supports flat panel screw mounting or snap-on DIN-rail installation inside control enclosures.
- Compatible Rail Profiles: Accepts standard 'top hat' 35 x 7.5 mm or 35 x 15 mm rails (EN 50022) as well as G-section rails (EN 50035).
Frequently Asked Questions (FAQ)
Q: How does the 8710-CA-04 carrier distribute power to connected field instrumentation?
A: An 8-pin connector located at the top rear of the carrier accepts external power supplies, routing them through specific I/O modules to energize field loops without separate marshalling strips.
Q: Can this 4-module carrier be installed directly into Class 1 Div 2 hazardous locations?
A: Yes, the unit carries official certification for Class 1, Div 2, Groups A, B, C, D T4 and Zone 2, IIC T4 hazardous areas when deployed within a compliant system architecture.
Q: What is the primary function of the isolated earthing bar on the carrier housing?
A: The isolated earthing bar provides a dedicated mechanical and electrical tie-point for cable screens and shields, effectively mitigating electromagnetic interference in industrial environments.
Q: Which DIN-rail standards are supported by the mechanical mounting brackets?
A: The enclosure accommodates standard 35 mm 'top hat' rails conforming to EN 50022 and G-section rails conforming to EN 50035, alongside direct flat panel mounting.
Q: How do connected modules interface with the 32-slot address bus architecture?
A: Each module slot maps into a designated segment of the 32-slot address range (1–32), transmitting control signals and diagnostic data deterministically over the integrated Railbus backplane.
Procurement & System Integration Guidance
When expanding your PAC8000 I/O architecture with the 8710-CA-04 carrier, verify your cabinet DIN-rail profile and ensure bussed field power connections match your loop voltage requirements. Contact our engineering sales team today to request a formal quotation, verify live factory inventory, and secure rapid logistics delivery for your automation project.

Tags
Q: Are these parts 100% original and new?
A: Yes. Every component is guaranteed to be 100% original, brand-new, and factory-sealed. We also provide a 12-month comprehensive warranty for your peace of mind.
Q: How fast is the shipping to my country?
A: For in-stock items, we offer same-day dispatch. International express shipping (DHL/FedEx/UPS) typically delivers within 3–5 business days worldwide.
Q: Can I get a formal quotation with shipping costs?
A: Absolutely. Our sales team is ready to provide a detailed Proforma Invoice (PI) including the most competitive shipping rates for your location.
Q: Do you offer discounts for bulk orders?
A: We provide volume-based pricing for large projects or multiple-item orders. Please contact us to get our Best Price Guarantee.
12-Month Comprehensive Warranty
Every part supplied by Global PLC Spare Hub is covered by a 12-month warranty from the date of invoice.
- Coverage: Functional defects and hardware failures under normal operating conditions.
- Commitment: We provide immediate repair, replacement, or a full refund for any verified defective components to minimize your operational downtime.
Returns & Exchange Policy
We offer a 30-day return policy to ensure you receive the exact part your system requires.
- Eligibility: Returns are accepted for uninstalled items in their original, factory-sealed packaging.
- RMA Process: Please contact our support team to obtain a Return Merchandise Authorization (RMA) number before shipping.
- Fast Processing: Refunds or exchanges are processed within 3–5 business days after the returned item passes our technical inspection.
Need Technical Assistance?Not sure if this part is compatible with your system? [Consult our Engineers] before purchasing to ensure 100% compatibility.