GE Fanuc IC693CPU360 25 MHz Series 90-30 Processor
Manufacturer: GE Fanuc
Product No.: IC693CPU360
Condition: In stock
Product Type: CPU Module
Product Origin: USA
Payment: T/T, Western Union
Weight: 910g
Shipping port: Xiamen
Warranty: 12 months
Estimate delivery times: 12-26 days (International), 3-6 days (United States).
Return within 30 days of purchase. Duties & taxes are non-refundable.
Guaranteed Safe Checkout
Product Overview
The GE Fanuc IC693CPU360 is a high-performance CPU module for the Series 90-30 PLC platform. It executes application logic and coordinates industrial control operations across local and remote I/O systems.
Powered by an 80386EX microprocessor, this controller operates at 25 MHz. It delivers a typical Boolean logic scan rate of 0.22 ms per 1K logic. Its 240 KB user memory supports application programs and control data.
The module occupies one slot in a Series 90-30 baseplate. It supports up to eight baseplates, including the local rack and seven additional I/O baseplates. This architecture provides flexibility for distributed control configurations.
Unlike CPUs with an onboard serial connector, the IC693CPU360 accesses serial communications through the RS-485 port on the power supply. This arrangement supports programming and controller communication through the power supply interface.
Technical Specifications
| Parameter | Specification |
| Brand | GE Fanuc |
| Model | IC693CPU360 |
| Product Series | Series 90-30 |
| Product Type | PLC CPU / Processor Module |
| Processor | 80386EX Microprocessor |
| Processor Clock Speed | 25 MHz |
| User Memory | 240 KB |
| Typical Scan Rate | 0.22 ms per 1K Boolean logic |
| Module Width | Single Slot |
| Backplane Current Consumption | 670 mA |
| Backplane Supply Voltage | 5 VDC |
| Serial Communication | RS-485 via power supply module |
| Integrated CPU Serial Connector | Not provided |
| Ethernet Ports | None |
| Baseplate Capacity | Up to 8 baseplates |
| Discrete Input Capacity | Up to 2,048 points |
| Discrete Output Capacity | Up to 2,048 points |
| Discrete Global Memory | 1,280 points |
| Internal Coils | 4,096 |
| Temporary Outputs | 256 bits |
| Register Memory | 9999 words on pre-Release 9 firmware; configurable on later firmware |
| Timers and Counters | More than 2,000 supported |
| Memory Storage | RAM and Flash |
| Operating Temperature | 0°C to 60°C (32°F to 140°F) |
| Storage Temperature | -40°C to 85°C (-40°F to 185°F) |
| Installation | Series 90-30 PLC baseplate |
Memory Architecture and Processing Capacity
The IC693CPU360 combines program execution, register storage, and discrete data management. Its memory configuration supports different application requirements.
- User Program Memory: 240 KB for application logic and control instructions.
- Discrete Inputs: Up to 2,048 input points.
- Discrete Outputs: Up to 2,048 output points.
- Global Data: 1,280 discrete global memory points.
- Internal Coils: 4,096 internal control bits.
- Temporary Outputs: 256 temporary output bits.
- Timers and Counters: Supports more than 2,000 instructions.
Register memory requires firmware verification. Firmware before Release 9 provides a fixed 9,999-word configuration. Release 9 and later support configurable register memory.
- Logicmaster: 128 to 16,384 words in 128-word increments.
- Control Version 2.2: 128 to 32,640 words in 128-word increments.
Communication and Programming Compatibility
The IC693CPU360 uses the RS-485 communication interface located on the power supply module. Technicians can access this connector by opening the power supply swing door.
Supported programming environments include:
- Logicmaster 90: Supports Series 90-30 PLC programming and configuration.
- Control: Provides controller programming and register configuration functions.
- VersaPro: Supports legacy Series 90-30 application development.
- CIMPLICITY Machine Edition: Provides Logic Developer programming capabilities.
- Hand-Held Programmer (HHP): Supports legacy programming and maintenance operations.
Always verify software versions, firmware compatibility, and communication settings before commissioning.
Installation Guide
- Verify the Rack: Confirm that the baseplate supports the IC693CPU360 processor.
- Check the Power Supply: Verify the 5 VDC backplane supply capacity. Allow at least 670 mA for this CPU.
- Isolate Power: Disconnect rack power before installing or removing the module.
- Inspect the Slot: Check the backplane connector and module alignment.
- Install the CPU: Insert the processor into its designated single-width slot.
- Connect Communications: Access the RS-485 connector on the power supply module.
- Configure the System: Verify rack assignments, I/O addresses, and memory settings.
- Restore Power: Start the controller and check its diagnostic status.
Important: Follow the applicable GE Fanuc installation manual. Confirm the exact baseplate and power supply configuration before installation.
Commissioning and Maintenance
- Power Verification: Check the 5 VDC backplane supply under normal operating conditions.
- Communication Testing: Verify RS-485 wiring, connector condition, and communication parameters.
- Program Validation: Confirm the downloaded application and memory configuration.
- Scan Performance: Monitor scan time during representative machine operation.
- I/O Diagnostics: Compare controller status with field device feedback.
- Backup Management: Maintain verified program copies and configuration records.
- Thermal Inspection: Keep the rack within its specified operating temperature range.
Check firmware and programming software compatibility before changing controller configurations. Record all program modifications during maintenance.
Compatibility and System Integration
| Integration Item | Compatibility Consideration |
| PLC Platform | GE Fanuc Series 90-30 |
| Baseplate | Compatible Series 90-30 rack configuration |
| Power Supply | Must provide sufficient 5 VDC backplane current |
| Remote I/O | Supports up to seven additional baseplates beyond the local rack |
| Programming Interface | RS-485 connector on the power supply |
| Programming Software | Logicmaster 90, Control, VersaPro, Logic Developer, and HHP |
| Ethernet Integration | No integrated Ethernet port; additional communication hardware may be required |
Integration Note: The IC693CPU360 does not provide an onboard Ethernet interface. Confirm the required communication architecture before connecting it to supervisory systems.
Certification and Environmental Information
- Operating Temperature: 0°C to 60°C.
- Storage Temperature: -40°C to 85°C.
- Power Input: 5 VDC backplane supply.
- Electrical Load: 670 mA typical specified backplane current consumption.
- Environmental Installation: Use a suitable industrial control cabinet.
- Certification: Verify applicable approvals against the exact product revision and manufacturer documentation.
Specific EMC, electrical safety, hazardous-area, and environmental protection ratings require confirmation. Do not assume an IP rating or certification without supporting documentation.
Packaging and Delivery
- 1 × GE Fanuc IC693CPU360 CPU Module
- Protective packaging for transportation.
- Product identification and model verification before dispatch.
- 12-month warranty.
- Shipping support through DHL, FedEx, or UPS, subject to destination.
Contact our sales team to confirm stock status, product condition, delivery arrangements, and order requirements.
Frequently Asked Questions
Q1: Can the IC693CPU360 communicate directly through an onboard RS-485 connector?
No. This CPU uses the RS-485 connector on the power supply module. Technicians must access the power supply interface for serial communication.
Q2: What should engineers check when the IC693CPU360 fails to communicate with programming software?
First, inspect the power supply communication connector and cable. Then verify serial parameters, software compatibility, and controller operating status. Incorrect communication settings can prevent successful programming access.
Q3: How does firmware Release 9 affect register memory configuration?
Release 9 introduces configurable register memory. Logicmaster supports up to 16,384 words, while Control Version 2.2 supports up to 32,640 words. Earlier firmware uses a fixed 9,999-word configuration.
Q4: Can the IC693CPU360 control multiple remote I/O racks?
Yes. The controller supports up to eight baseplates. This includes one local rack and seven additional distributed or remote I/O baseplates. Engineers must verify the complete rack architecture and communication requirements.
Q5: Can the IC693CPU360 connect directly to an Ethernet network?
No. This CPU does not include an integrated Ethernet port. Applications requiring Ethernet communication need compatible external communication hardware or an appropriate system-level interface.
Q6: What should buyers verify before replacing an existing Series 90-30 CPU?
Check the complete part number, baseplate configuration, power supply capacity, firmware revision, program memory requirements, and communication interface. Also verify the existing I/O architecture before ordering.
Q7: Is the 240 KB user memory the same as register memory?
No. User memory and register memory serve different purposes. The 240 KB specification describes user program memory, while register memory stores application data in configurable word locations.
Tags
Q: Are these parts 100% original and new?
A: Yes. Every component is guaranteed to be 100% original, brand-new, and factory-sealed. We also provide a 12-month comprehensive warranty for your peace of mind.
Q: How fast is the shipping to my country?
A: For in-stock items, we offer same-day dispatch. International express shipping (DHL/FedEx/UPS) typically delivers within 3–5 business days worldwide.
Q: Can I get a formal quotation with shipping costs?
A: Absolutely. Our sales team is ready to provide a detailed Proforma Invoice (PI) including the most competitive shipping rates for your location.
Q: Do you offer discounts for bulk orders?
A: We provide volume-based pricing for large projects or multiple-item orders. Please contact us to get our Best Price Guarantee.
12-Month Comprehensive Warranty
Every part supplied by Global PLC Spare Hub is covered by a 12-month warranty from the date of invoice.
- Coverage: Functional defects and hardware failures under normal operating conditions.
- Commitment: We provide immediate repair, replacement, or a full refund for any verified defective components to minimize your operational downtime.
Returns & Exchange Policy
We offer a 30-day return policy to ensure you receive the exact part your system requires.
- Eligibility: Returns are accepted for uninstalled items in their original, factory-sealed packaging.
- RMA Process: Please contact our support team to obtain a Return Merchandise Authorization (RMA) number before shipping.
- Fast Processing: Refunds or exchanges are processed within 3–5 business days after the returned item passes our technical inspection.
Need Technical Assistance?Not sure if this part is compatible with your system? [Consult our Engineers] before purchasing to ensure 100% compatibility.