F3XD16-3F Yokogawa F3 Series DC Input Module 16-Point Control
Manufacturer: Yokogawa
Product No.: F3XD16-3F
Condition: In stock
Product Type: DC Input Module
Product Origin: JP
Payment: T/T, Western Union
Weight: 160g
Shipping port: Xiamen
Warranty: 12 months
Estimate delivery times: 12-26 days (International), 3-6 days (United States).
Return within 30 days of purchase. Duties & taxes are non-refundable.
Guaranteed Safe Checkout
F3XD16-3F | Yokogawa F3 Series DC Input Module
The Yokogawa F3XD16-3F is a 16-point digital input module designed to receive 24 V DC signals from field devices and transfer their states to a compatible control system. Its sink/source input design supports industrial discrete-signal interfaces, while photocoupler isolation separates the input circuits from the module's internal logic.
For applications that require configurable input filtering, the module supports five sampling-time settings: Always (0 μs), 62.5 μs, 250 μs, 1 ms, and 16 ms. Input sampling can be configured to balance response speed and signal stability according to the field signal characteristics and control requirements.
01 | Signal Interface and Operating Limits
| Parameter | Specification |
|---|---|
| Manufacturer | Yokogawa |
| Model | F3XD16-3F |
| Module type | DC digital input module |
| Input configuration | Sink/source |
| Number of input points | 16 |
| Rated input voltage | 24 V DC |
| Rated input current | 4.1 mA per point at 24 V DC |
| Operating voltage range | 20.4–26.4 V DC |
| ON-state threshold | 16.0 V DC minimum; 3.2 mA minimum |
| OFF-state threshold | 5.8 V DC maximum; 0.9 mA maximum |
| Isolation | Photocoupler isolation |
| Simultaneous ON ratio | Up to 100% of input points |
| Common arrangement | 8 points per common |
| External connection | 18-point M3.5 screw terminal block |
| Internal current consumption | 65 mA at 5 V DC |
| Weight | Approx. 160 g |
02 | Input Sampling and Interrupt Configuration
The F3XD16-3F provides configurable sampling intervals for both OFF-to-ON and ON-to-OFF transitions. The selected interval affects how quickly an input state is recognized and how short-duration signal fluctuations are handled.
- Always (0 μs): Select when the application requires the shortest available sampling interval, subject to the system's actual processing behavior.
- 62.5 μs or 250 μs: Consider for relatively fast discrete signals when the field wiring and signal source provide adequate noise immunity.
- 1 ms: A practical option for many general-purpose control signals.
- 16 ms: Consider for slower signals where additional filtering may help reject brief fluctuations.
- Per-point interrupt setting: Interrupt functionality can be specified individually for each input point. Confirm the controller configuration and application requirements before relying on interrupt-driven logic.
Choose the sampling interval based on the signal pulse width, expected transition frequency, wiring environment, and required control response. A longer interval may suppress brief disturbances, but it can also prevent short pulses from being recognized.
03 | Typical Equipment and Application Scenarios
| Equipment or system | Example input signals | Engineering purpose |
|---|---|---|
| PLC-based machine control | Limit switches, selector switches, push buttons | Sequence control and operating-state detection |
| Conveyor and material handling | Photoelectric sensors, proximity switches, position signals | Part detection and movement interlocks |
| Process automation panels | Dry-contact interfaces and compatible 24 V DC status outputs | Equipment status acquisition and sequence supervision |
| Packaging and assembly machinery | Guard switches, presence sensors, machine-ready signals | Discrete event detection and cycle coordination |
| Utility and facility control | Relay status contacts and equipment feedback | Monitoring of pumps, fans, and auxiliary equipment |
Application note: These are representative use cases for a 16-point DC input interface, not a claim that every field device can connect directly. Verify signal polarity, output type, common wiring, voltage levels, and any required interposing interface before installation. Do not use a standard input module as a substitute for a certified safety input system.
04 | Installation, Commissioning, and Maintenance
- Confirm system compatibility. Check the Yokogawa controller or I/O platform, base or mounting arrangement, module position, and supported configuration against the applicable hardware manual.
- Verify the field supply. Confirm that the input supply remains within 20.4–26.4 V DC under actual load conditions.
- Check common grouping. The module uses two groups of eight input points per common arrangement. Review the wiring diagram and ensure that the field-device wiring matches the required sink/source configuration.
- Inspect terminal connections. Tighten the M3.5 screw terminals to the manufacturer's specified torque. Check conductor size, polarity, insulation, and strain relief.
- Set the sampling time. Configure the required sampling interval for each transition direction according to the application. Set per-point interrupt behavior only where needed.
- Test all input points. Operate each connected field device and compare the physical signal with the controller's online input status. Include both ON and OFF transitions in the test.
- Document the baseline. Record point assignments, common wiring, sampling settings, and commissioning results to support future fault isolation.
05 | Diagnostics and Fault Isolation
The F3XD16-3F acquires discrete input states. Its diagnostic value therefore depends on the module's visible input status, the controller or engineering software, and the external field circuit. Do not assume that it independently identifies every wiring fault or sensor failure.
- Input remains OFF: Measure the voltage at the relevant input terminal while the field device is activated. Check the sensor output, supply, common connection, polarity, and terminal continuity.
- Input remains ON: Check for a short circuit, incorrect common wiring, a stuck contact, or residual voltage from the connected device.
- Intermittent input changes: Inspect loose terminals, grounding and routing practices, electrical interference, and whether the selected sampling time is appropriate.
- Short pulses are missed: Verify pulse duration and sampling settings. Confirm that the controller scan, interrupt configuration, and application logic can capture the event.
- Several points fail together: Investigate the shared common, field supply, terminal wiring, and module seating before assuming multiple individual sensor failures.
Before replacing the module, compare the field-terminal voltage with the controller's reported input state. If the voltage is correct but the state is not reflected in the controller, inspect configuration, common wiring, module seating, and system diagnostics. Follow the equipment manufacturer's isolation and electrical safety procedures during testing.
06 | Global PLC Spare HUB's Insight
In a machine-control panel, a 16-point input module may collect limit-switch, photoelectric-sensor, and machine-ready signals. If a fast sensor pulse is missed, immediately replacing the input module may not resolve the problem. The pulse width, sampling interval, wiring quality, and controller processing must be checked together.
For troubleshooting, begin with three measurements: the voltage at the input terminal, the input state reported by the controller, and the timing of the field signal. This approach helps distinguish a field-device problem from a wiring, configuration, or module-level issue.
When purchasing a replacement, match the complete model and suffix code, confirm the host I/O platform, and review the terminal arrangement and configured signal behavior. These checks reduce the risk of installing a module that fits physically but does not meet the system's electrical or configuration requirements.
07 | Ordering, Warranty, and Shipping
- Product: Yokogawa F3XD16-3F DC input module
- Condition: Confirm stock condition and factory packaging status with the sales team before ordering.
- Warranty: 12-month warranty, subject to the seller's warranty terms and conditions.
- Shipping methods: FedEx, UPS, and DHL, subject to destination and service availability.
- Dispatch: Target dispatch within 24–48 hours after order confirmation, subject to stock availability, payment clearance, and order processing.
- Before purchase: Provide the full model number and host system details for a compatibility check and quotation.
08 | Frequently Asked Questions
Q1. How can I confirm that the F3XD16-3F is suitable for my existing Yokogawa system?
Check the controller and I/O platform model, supported module list, mounting arrangement, and configuration software documentation. Send the complete system model and module suffix to the supplier if compatibility is uncertain.
Q2. What should I check if a sensor output is 24 V DC but the input does not turn ON?
Measure the voltage directly at the module terminal while the sensor is active. Confirm that the voltage meets the ON-state threshold, the current is sufficient, and the common and sink/source wiring are correct. A nominal 24 V supply alone does not guarantee a valid input signal.
Q3. Is the 16 ms sampling setting suitable for high-speed counting?
It may be unsuitable for short or frequent pulses because the sampling interval can prevent transitions from being recognized. For pulse counting or fast event capture, evaluate the signal duration and required frequency, then verify whether this input module and the host system meet the application timing requirements.
Q4. Can the module identify an open wire or a failed field sensor by itself?
Do not assume it provides dedicated open-wire or sensor-failure detection. The module primarily reports discrete input states. Additional circuit supervision, controller logic, or compatible field devices may be needed to distinguish a failed sensor from a legitimate OFF state.
Q5. What information should I provide when requesting a quotation for a replacement?
Provide the full part number F3XD16-3F, the host controller or I/O platform model, the required quantity, the delivery destination, and any terminal or wiring constraints. If possible, include a clear photo of the existing module label to help verify the suffix and avoid ordering an incompatible variant.
Technical Reference Summary
The Yokogawa F3XD16-3F is a photocoupler-isolated, 16-point, 24 V DC sink/source input module with configurable sampling intervals and per-point interrupt settings. Its suitability depends on host-system compatibility, field-signal characteristics, and correct common wiring. Verify installation details and configuration against the official documentation for the specific system.

Tags
Q: Are these parts 100% original and new?
A: Yes. Every component is guaranteed to be 100% original, brand-new, and factory-sealed. We also provide a 12-month comprehensive warranty for your peace of mind.
Q: How fast is the shipping to my country?
A: For in-stock items, we offer same-day dispatch. International express shipping (DHL/FedEx/UPS) typically delivers within 3–5 business days worldwide.
Q: Can I get a formal quotation with shipping costs?
A: Absolutely. Our sales team is ready to provide a detailed Proforma Invoice (PI) including the most competitive shipping rates for your location.
Q: Do you offer discounts for bulk orders?
A: We provide volume-based pricing for large projects or multiple-item orders. Please contact us to get our Best Price Guarantee.
12-Month Comprehensive Warranty
Every part supplied by Global PLC Spare Hub is covered by a 12-month warranty from the date of invoice.
- Coverage: Functional defects and hardware failures under normal operating conditions.
- Commitment: We provide immediate repair, replacement, or a full refund for any verified defective components to minimize your operational downtime.
Returns & Exchange Policy
We offer a 30-day return policy to ensure you receive the exact part your system requires.
- Eligibility: Returns are accepted for uninstalled items in their original, factory-sealed packaging.
- RMA Process: Please contact our support team to obtain a Return Merchandise Authorization (RMA) number before shipping.
- Fast Processing: Refunds or exchanges are processed within 3–5 business days after the returned item passes our technical inspection.