VBS01-CJC Singular AI03 AI04 RTD Thermocouple Terminal Base
Manufacturer: ABB
Product No.: VBS01-CJC
Condition: En stock
Product Type: Terminal Base
Product Origin: USA
Payment: T/T, Western Union
Weight: 500g
Shipping port: Xiamen
Warranty: 12 months
Tiempo estimado de entrega: 12-26 días (Internacional), 3-6 días (Estados Unidos).
Devolución dentro de los 30 días siguientes a la compra. Los aranceles e impuestos no son reembolsables.
Pago Seguro Garantizado
Product Overview
The Singular VBS01-CJC is a full-size mounting base for HN800 analog input systems. It supports the AI03 8-channel RTD and AI04 16-channel TC/mV modules.
This base integrates a built-in RTD temperature sensor for cold junction compensation (CJC). It provides reliable temperature reference measurement for thermocouple applications.
Two 16-point headers support direct field wiring or remote marshaling connections. Engineers can use pluggable terminal blocks or SPK0x_-yy marshaling cables. This arrangement simplifies field wiring and cabinet termination.
- Primary function: Mounting and field termination for analog input modules.
- Supported signals: RTD, thermocouple, and millivolt inputs.
- Channel capacity: 8 RTD channels or 16 TC/mV channels.
- CJC function: Integrated RTD temperature reference.
- Mounting method: 35 mm DIN rail installation.
- System architecture: Singular HN800 I/O configuration.
Technical Specifications
| Parameter | Specification |
| Brand | Singular |
| Model | VBS01-CJC |
| Product Type | Analog Input Module Mounting Base |
| System | HN800 I/O Bus |
| Configuration | Singular |
| Supported Modules | AI03 and AI04 |
| Channel Capacity | 8 RTD or 16 TC/mV channels |
| Built-in Sensor | RTD for Cold Junction Compensation |
| Signal Connections | 2 × Pluggable 16-point Terminal Blocks |
| Alternative Connection | SPK0x_-yy Marshaling Cables |
| Mounting | 35 mm DIN Rail |
| Mounting Orientation | Vertical Column |
| Form Factor | Full Size |
| Dimensions | 218 × 67.5 × 114 mm (H × W × D) |
| Weight | 327 g |
| Hot-Swap Support | No |
| Field Power Connection | Compact |
| Field Power Fusing | Not Applicable |
| Maximum Current | HBX01L/HBX01R pair: 3.0 A maximum at +24 VDC |
| Field Wire Size | #22–14 AWG stranded or solid; #12 AWG stranded |
| Galvanic Isolation Test | 1500 V for up to 1 minute |
| Overvoltage Category | Category I for power |
| HN800 Bus Length | 305 mm |
| MTBF | 8,015,104 hours (MIL-HDBK-217-FN2) |
| MTTR | 8 hours |
| Protection Rating | IP20 |
Environmental and Electrical Performance
The VBS01-CJC supports industrial control cabinet environments. Its specifications address temperature variation, mechanical stress, and electromagnetic interference.
| Environmental Parameter | Rated Performance |
| Operating Temperature | -40 to +70 °C |
| Storage Temperature | -40 to +85 °C |
| Relative Humidity | 20%–95% at 40 °C, non-condensing |
| Operational Vibration | 5–60 Hz: 0.137 mm; 60–150 Hz: 1.0 G |
| Transportation Vibration | 10–500 Hz |
| Storage Shock | 15 G, 11 ms |
| Drop Resistance Test | 100 mm |
| Operating Altitude | Sea level to 3,048 m |
| Storage Altitude | Sea level to 12,192 m |
| Air Quality | ISA S71.04 G1 |
Electromagnetic Compatibility:
- ESD immunity: IEC/EN 61000-4-2, Severity Level 3.
- Surge immunity: IEC/EN 61000-4-5, Severity Level 3.
- Electrical fast transient: IEC/EN 61000-4-4, Severity Level 3.
- Radiated RFI immunity: IEC/EN 61000-4-3, Severity Level 3.
- Conducted immunity: IEC/EN 61000-4-6, Severity Level 3.
- Magnetic field immunity: IEC/EN 61000-4-8, Severity Level 4.
- Voltage dips and interruptions: IEC/EN 61000-4-11.
- Emission limits: CISPR 11, Group 1, Class A.
Important measurement note: The mounting base provides signal termination and CJC reference support. Measurement range, frequency response, sensitivity, linearity, and resolution depend on the installed AI03 or AI04 module. Consult the corresponding module datasheet before finalizing measurement configurations.
Installation Guide
- Verify the hardware: Confirm the base model and supported AI03 or AI04 module.
- Prepare the cabinet: Install a standard 35 mm DIN rail.
- Mount the base: Align the VBS01-CJC with the DIN rail and engage its latching mechanism.
- Check alignment: Ensure the base sits securely in its vertical mounting position.
- Connect field signals: Use the two 16-point headers and compatible terminal blocks.
- Configure marshaling: Use SPK0x_-yy cables when field signals terminate on third-party hardware.
- Install the I/O module: Confirm the correct module type and mechanical keying.
- Inspect wiring: Verify terminal assignments, polarity, and grounding arrangements.
- Complete commissioning: Check signal continuity and CJC operation before process startup.
Safety precaution: Isolate relevant field circuits before installation or wiring changes. This base does not support hot swapping.
Commissioning and Maintenance
Proper commissioning helps maintain reliable temperature measurements and stable analog input connections.
- CJC verification: Check the integrated RTD reference during thermocouple commissioning.
- Channel validation: Confirm each RTD, TC, or mV channel against the control system configuration.
- Wiring inspection: Check terminal tightness and field cable identification.
- Signal troubleshooting: Inspect terminal connections before replacing the I/O module.
- Mechanical inspection: Confirm DIN-rail engagement and base latching.
- Environmental checks: Keep the installation within specified temperature and humidity limits.
- Maintenance planning: Include terminal inspection in routine cabinet maintenance.
Always isolate power before removing modules or changing field wiring. Record terminal assignments before performing maintenance.
Compatibility and Configuration Notes
| Item | Compatibility Information |
| AI03 | Supported; 8-channel RTD analog input module |
| AI04 | Supported; 16-channel TC and mV analog input module |
| HN800 Bus | Designed for Singular HN800 I/O configurations |
| Terminal Blocks | Two pluggable 16-point terminal blocks |
| Marshaling Cables | SPK0x_-yy cable family |
| Mechanical Keying | Optional keying prevents incorrect module insertion |
System integration advantage: Singular and Redundant I/O bases and modules support a common HN800 I/O bus architecture. Compact and Full-size variants also share system compatibility.
However, VBS01-CJC itself is a Singular, Full-size mounting base. Its listed module support remains AI03 and AI04. Confirm the specific base, bus, and module configuration before ordering.
The standard version meets ISA S71.04 G1 air-quality requirements. The VBS01-CJCA variant is available for G3-compliant environments. Verify the required suffix when selecting equipment for corrosive industrial atmospheres.
Certifications and Compliance
- CSA: Certified for ordinary, non-hazardous locations.
- CSA Class I, Division 2: Groups A, B, C, and D nonincendive locations.
- CE: EMC Directive 2004/108/EC and Low Voltage Directive 2006/95/EC.
- RoHS: Directive 2015/863.
- WEEE: Directive 2012/19/EU.
- Electrical safety: Tested according to IEC/EN 61010-1.
- Environmental testing: IEC/EN 60068 and MIL-STD-810G, as applicable.
Certification requirements may depend on the installation configuration and applicable regulations. Verify the product documentation before deployment.
Package Contents
- 1 × Singular VBS01-CJC Analog Input Mounting Base
- Terminal blocks, marshaling cables, and I/O modules are not included unless specified in the order.
- Additional accessories depend on the confirmed purchasing configuration.
Frequently Asked Questions (FAQ)
Q1: What is the primary function of the VBS01-CJC mounting base?
The VBS01-CJC provides mechanical mounting and field signal termination for AI03 and AI04 modules. It also integrates an RTD reference for thermocouple cold junction compensation.
Q2: Can the VBS01-CJC support both RTD and thermocouple applications?
Yes. It supports up to eight 2-, 3-, or 4-wire RTDs with AI03. It also supports sixteen TC or mV signals with AI04.
Q3: Does the integrated RTD replace an external cold junction compensation sensor?
The built-in RTD provides the CJC reference for supported thermocouple configurations. Confirm the AI04 configuration and system engineering requirements before adding external compensation hardware.
Q4: Can engineers replace the I/O module while the system remains powered?
No. The published specification identifies VBS01-CJC as non-hot-swappable. Isolate the relevant power and field circuits before module replacement.
Q5: What should engineers check when thermocouple readings show unexpected temperature deviations?
First, inspect thermocouple polarity and terminal connections. Then verify the AI04 channel configuration and CJC reference. Also check cabinet temperature stability and field wiring integrity.
Q6: Can the VBS01-CJC connect to third-party termination hardware?
Yes. Compatible SPK0x_-yy marshaling cables support connections to third-party termination hardware. Verify the exact cable configuration and terminal assignment before installation.
Q7: Can Singular and Redundant I/O modules share one HN800 bus?
The system architecture supports compatibility across Singular and Redundant, Compact and Full-size I/O products. However, engineers must verify each base and module's individual configuration requirements.
Q8: Which version should engineers select for corrosive environments?
The standard VBS01-CJC meets ISA S71.04 G1 air-quality requirements. Consider VBS01-CJCA when the application requires ISA S71.04 G3 compliance. Confirm the actual site classification before ordering.
Q9: What is the most important check before replacing an existing mounting base?
Verify the exact model, supported I/O module, bus architecture, mounting dimensions, and terminal arrangement. A matching channel count alone does not guarantee electrical or mechanical compatibility.
Q10: What information should buyers provide when requesting a quotation?
Provide the VBS01-CJC model number, required quantity, installed AI03 or AI04 module, and target HN800 configuration. Include environmental requirements when selecting the G1 or G3 version. These details help reduce ordering errors and commissioning delays.
Tags
P: ¿Son estas piezas 100% originales y nuevas?
R: Sí. Cada componente está garantizado como 100% original, completamente nuevo y sellado de fábrica. También ofrecemos una garantía integral de 12 meses para su tranquilidad.
P: ¿Qué tan rápido es el envío a mi país?
R: Para artículos en stock, ofrecemos envío el mismo día. El envío exprés internacional (DHL/FedEx/UPS) generalmente entrega en un plazo de 3 a 5 días hábiles en todo el mundo.
P: ¿Puedo obtener una cotización formal con los costos de envío?
R: Absolutamente. Nuestro equipo de ventas está listo para proporcionar una factura proforma (PI) detallada que incluya las tarifas de envío más competitivas para su ubicación.
P: ¿Ofrecen descuentos por pedidos al por mayor?
R: Ofrecemos precios basados en el volumen para proyectos grandes o pedidos de varios artículos. Póngase en contacto con nosotros para obtener nuestra Garantía de Mejor Precio.
Garantía Integral de 12 Meses
Cada pieza suministrada por Global PLC Spare Hub está cubierta por una garantía de 12 meses a partir de la fecha de la factura.
- Cobertura: Defectos funcionales y fallos de hardware bajo condiciones normales de funcionamiento.
- Compromiso: Ofrecemos reparación, reemplazo o un reembolso completo inmediato para cualquier componente defectuoso verificado, para minimizar su tiempo de ininactividad operativa.
Política de Devoluciones y Cambios
Ofrecemos una política de devolución de 30 días para asegurar que reciba la pieza exacta que su sistema requiere.
- Elegibilidad: Se aceptan devoluciones de artículos sin instalar en su embalaje original sellado de fábrica.
- Proceso de RMA: Póngase en contacto con nuestro equipo de soporte para obtener un número de Autorización de Devolución de Mercancía (RMA) antes del envío.
- Procesamiento Rápido: Los reembolsos o cambios se procesan dentro de 3 a 5 días hábiles después de que el artículo devuelto pasa nuestra inspección técnica.
¿Necesita Asistencia Técnica? ¿No está seguro de si esta pieza es compatible con su sistema? [Consulte a nuestros Ingenieros] antes de comprar para asegurar una compatibilidad del 100%.