Pepperl+Fuchs KFA6-SR2-Ex1.W.LB NAMUR Switch Amplifier
Manufacturer: Pepperl+Fuchs
Product No.: KFA6-SR2-Ex1.W.LB
Condition: In stock
Product Type: Switch Amplifier
Product Origin: DE
Payment: T/T, Western Union
Weight: 150g
Shipping port: Xiamen
Warranty: 12 months
Estimate delivery times: 12-26 days (International), 3-6 days (United States).
Return within 30 days of purchase. Duties & taxes are non-refundable.
Guaranteed Safe Checkout
Product Introduction
The Pepperl+Fuchs KFA6-SR2-Ex1.W.LB (Part No. 103375) is a single-channel switch amplifier and isolated barrier. It interfaces NAMUR sensors or mechanical dry contacts with control systems. The module provides relay switching, electrical isolation, and field wiring diagnostics.
Designed for industrial applications, this unit monitors digital input signals from hazardous areas. Its integrated Line Fault Detection (LFD) identifies field wiring breaks and short circuits. Two relay outputs support process switching and fault signaling. Engineers can configure the operating mode through onboard switches.
The module operates from a 230 V AC supply and supports safety applications up to SIL 2 according to IEC 61508. Its compact housing supports DIN rail installation inside industrial control cabinets.
Technical Specifications
| Brand | Pepperl+Fuchs |
| Model | KFA6-SR2-Ex1.W.LB |
| Part Number | 103375 |
| Product Series | K-System |
| Product Type | Single-channel Switch Amplifier / Isolated Barrier |
| Signal Type | Digital Input |
| Channel Count | 1 Channel |
| Input Compatibility | NAMUR Sensors / Mechanical Dry Contacts |
| Output Type | Relay Contacts |
| Additional Output | Signal or Fault Indication Relay |
| Supply Voltage | 207–253 V AC |
| Supply Frequency | 45–65 Hz |
| Power Consumption | ≤ 1.3 W |
| Power Dissipation | 1.2 W |
| Safety Integrity | Up to SIL 2, IEC 61508 |
| Line Fault Detection | Open-Circuit and Short-Circuit Monitoring |
| Operating Temperature | -20°C to +60°C |
| Protection Rating | IP20 |
| Mounting Method | DIN Rail |
| Dimensions | 20 × 119 × 115 mm |
| Weight | Approximately 150 g |
| Housing Type | B2 |
Input Signal Characteristics
The input circuit accepts NAMUR proximity sensors according to EN 60947-5-6. It also supports compatible mechanical dry contacts.
| Input Terminals | 1+, 2+, 3- |
| NAMUR Open-Circuit Voltage | Approximately 8 V DC |
| Short-Circuit Current | Approximately 8 mA |
| Switching Threshold | 1.2–2.1 mA |
| Switching Hysteresis | Approximately 0.2 mA |
| Open-Circuit Detection | Input Current ≤ 0.1 mA |
| Short-Circuit Detection | Input Current > 6 mA |
| Minimum Pulse Duration | 20 ms |
| Minimum Pause Duration | 20 ms |
Relay Output Characteristics
The module provides two independent relay contact groups. Output I handles the switching signal. Output II provides a switching signal or fault indication.
| Output I Terminals | 7, 8, 9 |
| Output II Terminals | 10, 11, 12 |
| AC Contact Rating | 253 V AC / 2 A, cos φ > 0.7 |
| Alternative AC Rating | 126.5 V AC / 4 A, cos φ > 0.7 |
| DC Contact Rating | 40 V DC / 2 A, Resistive Load |
| Operate Delay | Approximately 20 ms |
| Release Delay | Approximately 20 ms |
| Maximum Switching Frequency | 10 Hz |
| Mechanical Service Life | 10⁷ Switching Cycles |
Electrical Isolation and Ex Protection
The KFA6-SR2-Ex1.W.LB provides galvanic isolation between field circuits and control-side connections.
- Input-to-Output: Safe electrical isolation according to IEC/EN 60079-11.
- Input-to-Supply: Safe electrical isolation according to IEC/EN 60079-11.
- Output-to-Supply: Reinforced insulation according to IEC 61140.
- Output-to-Output: Basic insulation according to IEC 61140.
- Rated Insulation Voltage: 300 V RMS for the specified output isolation ratings.
- Ex Input Voltage Uo: 10.6 V.
- Ex Input Current Io: 19.1 mA.
- Ex Input Power Po: 51 mW, linear characteristic.
- Maximum Safe Supply Voltage Um: 253 V AC.
The input circuit supports intrinsically safe field connections. Its protection parameters must match the connected field device and installation requirements.
Core Functional Advantages
- NAMUR Signal Conditioning: Converts field sensor signals into relay switching outputs for control applications.
- Integrated LFD: Detects open circuits and short circuits in monitored field wiring.
- Dual Relay Outputs: Separates process switching from additional signal or fault indication.
- Reversible Operating Mode: Allows engineers to select the required switching behavior through onboard configuration switches.
- Configurable Fault Monitoring: Supports adjustment of operating and monitoring functions through designated switches.
- SIL 2 Capability: Supports safety-related applications when the complete system meets applicable requirements.
- Compact Installation: Its 20 mm housing width helps conserve cabinet space.
Installation Guide
- Check the Model: Confirm the KFA6-SR2-Ex1.W.LB designation and part number 103375.
- Verify the Supply: Confirm a 207–253 V AC supply at 45–65 Hz.
- Mount the Module: Secure the housing onto a compatible DIN rail.
- Connect the Input: Wire the NAMUR sensor or dry contact to terminals 1+, 2+, and 3-.
- Connect the Supply: Use terminals 14 and 15 for the AC power connection.
- Wire Output I: Connect the process relay circuit to terminals 7, 8, and 9.
- Wire Output II: Connect the signal or fault relay circuit to terminals 10, 11, and 12.
- Verify Configuration: Check the S1 and S3 switch settings against the application requirements.
- Inspect Wiring: Verify terminal tightness, polarity, and circuit separation before energizing.
Safety Note: Qualified personnel must perform installation and commissioning. Follow applicable hazardous-area regulations and intrinsically safe circuit requirements. Disconnect power before changing wiring or configuration switches.
Tags
Q: Are these parts 100% original and new?
A: Yes. Every component is guaranteed to be 100% original, brand-new, and factory-sealed. We also provide a 12-month comprehensive warranty for your peace of mind.
Q: How fast is the shipping to my country?
A: For in-stock items, we offer same-day dispatch. International express shipping (DHL/FedEx/UPS) typically delivers within 3–5 business days worldwide.
Q: Can I get a formal quotation with shipping costs?
A: Absolutely. Our sales team is ready to provide a detailed Proforma Invoice (PI) including the most competitive shipping rates for your location.
Q: Do you offer discounts for bulk orders?
A: We provide volume-based pricing for large projects or multiple-item orders. Please contact us to get our Best Price Guarantee.
12-Month Comprehensive Warranty
Every part supplied by Global PLC Spare Hub is covered by a 12-month warranty from the date of invoice.
- Coverage: Functional defects and hardware failures under normal operating conditions.
- Commitment: We provide immediate repair, replacement, or a full refund for any verified defective components to minimize your operational downtime.
Returns & Exchange Policy
We offer a 30-day return policy to ensure you receive the exact part your system requires.
- Eligibility: Returns are accepted for uninstalled items in their original, factory-sealed packaging.
- RMA Process: Please contact our support team to obtain a Return Merchandise Authorization (RMA) number before shipping.
- Fast Processing: Refunds or exchanges are processed within 3–5 business days after the returned item passes our technical inspection.
Need Technical Assistance?Not sure if this part is compatible with your system? [Consult our Engineers] before purchasing to ensure 100% compatibility.