Home Pepperl+Fuchs KFA6-SR2-Ex1.W.LB NAMUR Switch Amplifier

Pepperl+Fuchs KFA6-SR2-Ex1.W.LB NAMUR Switch Amplifier

  • Manufacturer: Pepperl+Fuchs

  • Product No.: KFA6-SR2-Ex1.W.LB

  • Condition: In stock

  • Product Type: Switch Amplifier

  • Product Origin: DE

  • Payment: T/T, Western Union

  • Weight: 150g

  • Shipping port: Xiamen

  • Warranty: 12 months

Selected quantity: 1
Request a quote

Estimate delivery times: 12-26 days (International), 3-6 days (United States).

Return within 30 days of purchase. Duties & taxes are non-refundable.

Guaranteed Safe Checkout

Visa
PayPal
Mastercard
American Express

Product Introduction

The Pepperl+Fuchs KFA6-SR2-Ex1.W.LB (Part No. 103375) is a single-channel switch amplifier and isolated barrier. It interfaces NAMUR sensors or mechanical dry contacts with control systems. The module provides relay switching, electrical isolation, and field wiring diagnostics.

Designed for industrial applications, this unit monitors digital input signals from hazardous areas. Its integrated Line Fault Detection (LFD) identifies field wiring breaks and short circuits. Two relay outputs support process switching and fault signaling. Engineers can configure the operating mode through onboard switches.

The module operates from a 230 V AC supply and supports safety applications up to SIL 2 according to IEC 61508. Its compact housing supports DIN rail installation inside industrial control cabinets.

Technical Specifications

Brand Pepperl+Fuchs
Model KFA6-SR2-Ex1.W.LB
Part Number 103375
Product Series K-System
Product Type Single-channel Switch Amplifier / Isolated Barrier
Signal Type Digital Input
Channel Count 1 Channel
Input Compatibility NAMUR Sensors / Mechanical Dry Contacts
Output Type Relay Contacts
Additional Output Signal or Fault Indication Relay
Supply Voltage 207–253 V AC
Supply Frequency 45–65 Hz
Power Consumption ≤ 1.3 W
Power Dissipation 1.2 W
Safety Integrity Up to SIL 2, IEC 61508
Line Fault Detection Open-Circuit and Short-Circuit Monitoring
Operating Temperature -20°C to +60°C
Protection Rating IP20
Mounting Method DIN Rail
Dimensions 20 × 119 × 115 mm
Weight Approximately 150 g
Housing Type B2

Input Signal Characteristics

The input circuit accepts NAMUR proximity sensors according to EN 60947-5-6. It also supports compatible mechanical dry contacts.

Input Terminals 1+, 2+, 3-
NAMUR Open-Circuit Voltage Approximately 8 V DC
Short-Circuit Current Approximately 8 mA
Switching Threshold 1.2–2.1 mA
Switching Hysteresis Approximately 0.2 mA
Open-Circuit Detection Input Current ≤ 0.1 mA
Short-Circuit Detection Input Current > 6 mA
Minimum Pulse Duration 20 ms
Minimum Pause Duration 20 ms

Relay Output Characteristics

The module provides two independent relay contact groups. Output I handles the switching signal. Output II provides a switching signal or fault indication.

Output I Terminals 7, 8, 9
Output II Terminals 10, 11, 12
AC Contact Rating 253 V AC / 2 A, cos φ > 0.7
Alternative AC Rating 126.5 V AC / 4 A, cos φ > 0.7
DC Contact Rating 40 V DC / 2 A, Resistive Load
Operate Delay Approximately 20 ms
Release Delay Approximately 20 ms
Maximum Switching Frequency 10 Hz
Mechanical Service Life 10⁷ Switching Cycles

Electrical Isolation and Ex Protection

The KFA6-SR2-Ex1.W.LB provides galvanic isolation between field circuits and control-side connections.

  • Input-to-Output: Safe electrical isolation according to IEC/EN 60079-11.
  • Input-to-Supply: Safe electrical isolation according to IEC/EN 60079-11.
  • Output-to-Supply: Reinforced insulation according to IEC 61140.
  • Output-to-Output: Basic insulation according to IEC 61140.
  • Rated Insulation Voltage: 300 V RMS for the specified output isolation ratings.
  • Ex Input Voltage Uo: 10.6 V.
  • Ex Input Current Io: 19.1 mA.
  • Ex Input Power Po: 51 mW, linear characteristic.
  • Maximum Safe Supply Voltage Um: 253 V AC.

The input circuit supports intrinsically safe field connections. Its protection parameters must match the connected field device and installation requirements.

Core Functional Advantages

  • NAMUR Signal Conditioning: Converts field sensor signals into relay switching outputs for control applications.
  • Integrated LFD: Detects open circuits and short circuits in monitored field wiring.
  • Dual Relay Outputs: Separates process switching from additional signal or fault indication.
  • Reversible Operating Mode: Allows engineers to select the required switching behavior through onboard configuration switches.
  • Configurable Fault Monitoring: Supports adjustment of operating and monitoring functions through designated switches.
  • SIL 2 Capability: Supports safety-related applications when the complete system meets applicable requirements.
  • Compact Installation: Its 20 mm housing width helps conserve cabinet space.

Installation Guide

  1. Check the Model: Confirm the KFA6-SR2-Ex1.W.LB designation and part number 103375.
  2. Verify the Supply: Confirm a 207–253 V AC supply at 45–65 Hz.
  3. Mount the Module: Secure the housing onto a compatible DIN rail.
  4. Connect the Input: Wire the NAMUR sensor or dry contact to terminals 1+, 2+, and 3-.
  5. Connect the Supply: Use terminals 14 and 15 for the AC power connection.
  6. Wire Output I: Connect the process relay circuit to terminals 7, 8, and 9.
  7. Wire Output II: Connect the signal or fault relay circuit to terminals 10, 11, and 12.
  8. Verify Configuration: Check the S1 and S3 switch settings against the application requirements.
  9. Inspect Wiring: Verify terminal tightness, polarity, and circuit separation before energizing.

Safety Note: Qualified personnel must perform installation and commissioning. Follow applicable hazardous-area regulations and intrinsically safe circuit requirements. Disconnect power before changing wiring or configuration switches.

Tags

Q: Are these parts 100% original and new?

A: Yes. Every component is guaranteed to be 100% original, brand-new, and factory-sealed. We also provide a 12-month comprehensive warranty for your peace of mind.

Q: How fast is the shipping to my country?

A: For in-stock items, we offer same-day dispatch. International express shipping (DHL/FedEx/UPS) typically delivers within 3–5 business days worldwide.

Q: Can I get a formal quotation with shipping costs?

A: Absolutely. Our sales team is ready to provide a detailed Proforma Invoice (PI) including the most competitive shipping rates for your location.

Q: Do you offer discounts for bulk orders?

A: We provide volume-based pricing for large projects or multiple-item orders. Please contact us to get our Best Price Guarantee.




12-Month Comprehensive Warranty

Every part supplied by Global PLC Spare Hub is covered by a 12-month warranty from the date of invoice.

  • Coverage: Functional defects and hardware failures under normal operating conditions.
  • Commitment: We provide immediate repair, replacement, or a full refund for any verified defective components to minimize your operational downtime.

Returns & Exchange Policy

We offer a 30-day return policy to ensure you receive the exact part your system requires.

  • Eligibility: Returns are accepted for uninstalled items in their original, factory-sealed packaging.
  • RMA Process: Please contact our support team to obtain a Return Merchandise Authorization (RMA) number before shipping.
  • Fast Processing: Refunds or exchanges are processed within 3–5 business days after the returned item passes our technical inspection.

Need Technical Assistance?Not sure if this part is compatible with your system? [Consult our Engineers] before purchasing to ensure 100% compatibility.