KFA6-SR2-Ex1.W Pepperl+Fuchs 1-Channel NAMUR Relay Barrier
Manufacturer: Pepperl+Fuchs
Product No.: KFA6-SR2-Ex1.W
Condition: In stock
Product Type: Relay Barrier
Product Origin: DE
Payment: T/T, Western Union
Weight: 150g
Shipping port: Xiamen
Warranty: 12 months
Estimate delivery times: 12-26 days (International), 3-6 days (United States).
Return within 30 days of purchase. Duties & taxes are non-refundable.
Guaranteed Safe Checkout
Product Overview
The Pepperl+Fuchs KFA6-SR2-Ex1.W is a 1-channel isolated switch amplifier for industrial signal transmission. It connects NAMUR sensors or dry contacts to control systems through a relay output.
The module operates with a 230 V AC supply and provides galvanic isolation between the field input, control output, and power supply. Its integrated Line Fault Detection (LFD) identifies open circuits and short circuits in the field wiring.
The amplifier supports reversible operating modes. Engineers can configure the switching behavior to match the required control logic. Its safety characteristics support applications up to SIL 2 under IEC/EN 61508 and IEC/EN 61511.
The KFA6-SR2-Ex1.W suits industrial automation systems that require reliable NAMUR signal evaluation and isolated relay switching.
Key Features
- Brand: Pepperl+Fuchs
- Model: KFA6-SR2-Ex1.W
- Product Type: 1-channel isolated switch amplifier
- Input: NAMUR sensor or dry contact
- Output: Electromechanical relay contact
- Power Supply: 230 V AC
- Fault Monitoring: Integrated Line Fault Detection
- Operating Mode: Reversible switching behavior
- Functional Safety: Up to SIL 2
- Mounting: 35 mm DIN rail
- Isolation: Reinforced galvanic isolation
Technical Specifications
| Parameter | Specification |
|---|---|
| Brand | Pepperl+Fuchs |
| Model | KFA6-SR2-Ex1.W |
| Product Type | Switch Amplifier / Isolated Barrier |
| Signal Type | Digital Input |
| Number of Channels | 1 |
| Safety Integrity Level | SIL 2 |
| Input Compatibility | NAMUR Sensors / Dry Contacts |
| Input Terminals | 1+, 2+, 3- |
| Open-Circuit Voltage | Approximately 8 V DC |
| Short-Circuit Current | Approximately 8 mA |
| Switching Point | 1.2–2.1 mA |
| Switching Hysteresis | Approximately 0.2 mA |
| LFD – Line Breakage | Current ≤ 0.1 mA |
| LFD – Short Circuit | Current > 6 mA |
| Minimum Pulse Duration | 20 ms |
| Minimum Pause Duration | 20 ms |
| Output Type | Relay Contact |
| Output Terminals | 7, 8, 9 |
| Maximum Switching Frequency | Less than 10 Hz |
| Operating Delay | Approximately 20 ms |
| Release Delay | Approximately 20 ms |
| Mechanical Service Life | 10⁷ switching cycles |
| Relay Contact Rating | 253 V AC / 2 A, cos φ > 0.7 |
| Relay Contact Rating | 126.5 V AC / 4 A, cos φ > 0.7 |
| DC Contact Rating | 40 V DC / 2 A, resistive load |
| Power Supply Terminals | 14, 15 |
| Rated Supply Voltage | 207–253 V AC |
| Supply Frequency | 45–65 Hz |
| Power Consumption | Maximum 1 W |
| Power Dissipation | 1 W |
| Input/Output Isolation | Reinforced insulation, 300 Veff |
| Input/Supply Isolation | Reinforced insulation, 300 Veff |
| Output/Supply Isolation | Reinforced insulation, 300 Veff |
| Operating Temperature | -20 to +60 °C |
| Protection Rating | IP20 |
| Connection Type | Screw Terminals |
| Housing Type | B2 |
| Dimensions (W × H × D) | 20 × 119 × 115 mm |
| Weight | Approximately 150 g |
| Mounting | 35 mm DIN Rail, EN 60715 |
Signal Characteristics and Functional Performance
1. NAMUR Input Evaluation
- The input follows EN 60947-5-6.
- The module evaluates current changes from NAMUR sensors.
- The switching threshold ranges from 1.2 to 2.1 mA.
- Approximately 0.2 mA hysteresis helps prevent unstable switching.
2. Line Fault Detection
- The module monitors the field circuit for wiring faults.
- Current at or below 0.1 mA indicates a line break.
- Current above 6 mA indicates a short circuit.
- These thresholds help maintenance teams identify field wiring problems.
3. Relay Switching Performance
- The relay provides isolated contact switching.
- Operate and release delays are approximately 20 ms.
- The maximum switching frequency is below 10 Hz.
- Mechanical life reaches 10 million switching cycles.
4. Electrical Isolation
- Reinforced insulation separates input, output, and power circuits.
- The rated insulation voltage is 300 Veff.
- This arrangement reduces direct electrical coupling between circuit sections.
Note: The manufacturer does not specify measurement accuracy, linearity, resolution, or analog frequency response for this digital switching device. These parameters do not apply to its intended signal evaluation function.
Installation Guide
1. DIN Rail Installation
- Install the KFA6-SR2-Ex1.W on a 35 mm DIN rail.
- Choose a cabinet location with suitable ventilation.
- Maintain the required clearance for wiring and maintenance.
- Check the operating temperature range before installation.
2. Electrical Connections
| Terminal | Connection Function |
|---|---|
| 1+, 2+, 3- | Field-side sensor input |
| 7, 8, 9 | Control-side relay output |
| 14, 15 | AC power supply |
- Connect the NAMUR sensor or dry contact to the field terminals.
- Connect the relay contacts to the receiving control circuit.
- Apply a supply voltage between 207 and 253 V AC.
- Verify terminal assignments before energizing the module.
3. Hazardous Area Installation
- Use the module as an associated apparatus for intrinsically safe circuits.
- Follow the approved hazardous-area installation drawings.
- Verify sensor entity parameters against the barrier output parameters.
- Check cable capacitance and inductance against the applicable certification limits.
- Use qualified personnel for hazardous-area wiring and inspection.
Hazardous Area Certification and Compliance
| Certification Parameter | Specification |
|---|---|
| EU-Type Examination Certificate | PTB 00 ATEX 2081 |
| Gas Protection Marking | II (1)G [Ex ia Ga] IIC |
| Dust Protection Marking | II (1)D [Ex ia Da] IIIC |
| Mining Protection Marking | I (M1) [Ex ia Ma] I |
| Intrinsic Safety Protection | Ex ia |
| Maximum Output Voltage Uo | 10.6 V |
| Maximum Output Current Io | 19.1 mA |
| Maximum Output Power Po | 51 mW |
| Maximum Safe Supply Voltage Um | 253 V AC |
| EMC Directive | 2014/30/EU |
| Low Voltage Directive | 2014/35/EU |
| EMC Standard | EN 61326-1:2013 |
| Electrical Safety Standard | EN 61010-1:2010 |
| NAMUR Input Standard | EN 60947-5-6:2000 |
| EMC Recommendation | NE 21:2006 |
| Enclosure Protection Standard | IEC 60529:2001 |
| Functional Safety Standards | IEC/EN 61508 and IEC/EN 61511 |
Important Safety Information: The SIL 2 capability applies to the specified safety function and its assessed operating conditions. Verify the safety manual, failure data, proof-test requirements, and system architecture before use in a safety instrumented function.
The Um value represents the maximum safe voltage. It does not represent the normal rated supply voltage.

Tags
Q: Are these parts 100% original and new?
A: Yes. Every component is guaranteed to be 100% original, brand-new, and factory-sealed. We also provide a 12-month comprehensive warranty for your peace of mind.
Q: How fast is the shipping to my country?
A: For in-stock items, we offer same-day dispatch. International express shipping (DHL/FedEx/UPS) typically delivers within 3–5 business days worldwide.
Q: Can I get a formal quotation with shipping costs?
A: Absolutely. Our sales team is ready to provide a detailed Proforma Invoice (PI) including the most competitive shipping rates for your location.
Q: Do you offer discounts for bulk orders?
A: We provide volume-based pricing for large projects or multiple-item orders. Please contact us to get our Best Price Guarantee.
12-Month Comprehensive Warranty
Every part supplied by Global PLC Spare Hub is covered by a 12-month warranty from the date of invoice.
- Coverage: Functional defects and hardware failures under normal operating conditions.
- Commitment: We provide immediate repair, replacement, or a full refund for any verified defective components to minimize your operational downtime.
Returns & Exchange Policy
We offer a 30-day return policy to ensure you receive the exact part your system requires.
- Eligibility: Returns are accepted for uninstalled items in their original, factory-sealed packaging.
- RMA Process: Please contact our support team to obtain a Return Merchandise Authorization (RMA) number before shipping.
- Fast Processing: Refunds or exchanges are processed within 3–5 business days after the returned item passes our technical inspection.
Need Technical Assistance?Not sure if this part is compatible with your system? [Consult our Engineers] before purchasing to ensure 100% compatibility.