Yokogawa SAI143-H63 16-Channel SAI143 Input Module
Manufacturer: Yokogawa
Product No.: SAI143-H63
Condition: En stock
Product Type: Analog Input Module
Product Origin: SG
Payment: T/T, Western Union
Weight: 350g
Shipping port: Xiamen
Warranty: 12 months
Tiempo estimado de entrega: 12-26 días (Internacional), 3-6 días (Estados Unidos).
Devolución dentro de los 30 días siguientes a la compra. Los aranceles e impuestos no son reembolsables.
Pago Seguro Garantizado
Yokogawa SAI143-H63 16-Channel Analog Input Module
Product Overview
The Yokogawa SAI143-H63 is a 16-channel analog input module for industrial process control. It accepts standard 4–20 mA signals from field transmitters. The module provides isolated input channels and updates data every 40 ms. The module supports individual 2-wire or 4-wire channel settings. Its transmitter power supply supports 2-wire transmitters. Users can switch this supply on or off across all 16 channels simultaneously. The SAI143-H accuracy specification supports input currents from 0.05 to 23 mA. This range includes low-current signals below the standard 4–20 mA operating range. **Important product identification:** The supplied specifications describe the SAI143 analog input family. They do not confirm every suffix-specific feature of the SAI143-H63. Verify the complete model code against the applicable Yokogawa hardware documentation before installation.Technical Specifications
| Parameter | Specification |
|---|---|
| Manufacturer | Yokogawa |
| Model | SAI143-H63 |
| Product family | SAI143 |
| Module type | 16-channel analog current input module |
| Input channels | 16, with module isolation |
| Rated input range | 4–20 mA |
| Permissible input range | 0–25 mA |
| SAI143-H rated accuracy | ±16 µA over 0.05–23 mA |
| Data update frequency | 40 ms per update |
| Input impedance during power-on | 250 Ω plus the input protection circuit voltage drop |
| Input impedance during power-off | 500 kΩ minimum |
| Temperature drift | ±16 µA per 10°C |
| Transmitter supply voltage | 16.15 V minimum at 20 mA; 26.4 V maximum at 0 mA |
| Transmitter output current limit | 25 mA |
| Channel wiring configuration | Individual 2-wire or 4-wire setting |
| Transmitter supply switching | Available for all 16 channels together in 2-wire mode |
| Withstand voltage | 1.5 kV AC between input signal and system for one minute |
| 5 V system current consumption | 320 mA maximum |
| 24 V system current consumption | 550 mA maximum |
| PRM support | Available for SAI143-H |
| External connection | Pressure clamp terminal, MIL cable, or dedicated signal cable |
| Approximate weight | 0.34 kg with pressure clamp terminal block or MIL cable; 0.39 kg with signal cable interface adapter |
Measurement Performance and Signal Integrity
- Current measurement: The module reads standard 4–20 mA process signals.
- Input tolerance: The permissible range extends from 0 to 25 mA.
- Specified accuracy: The SAI143-H variant provides ±16 µA accuracy across its documented range.
- Update interval: The module refreshes input data every 40 ms.
- Channel isolation: Module isolation helps separate field signals from the system.
- Electrical withstand: The specified isolation withstands 1.5 kV AC for one minute.
Key Functions and Engineering Benefits
- Multi-channel acquisition: One module collects signals from up to 16 transmitters.
- Flexible transmitter wiring: Engineers can configure each channel for 2-wire or 4-wire operation.
- Integrated transmitter supply: The module can power supported 2-wire transmitters.
- Group supply control: The transmitter supply switching function controls all 16 channels together.
- Process data refresh: A 40 ms update interval supports routine monitoring of changing process values.
- Electrical separation: Isolation helps reduce unwanted electrical interaction between field signals and system circuits.
Typical Industrial Applications
- Process plants: Collect flow, pressure, level, and temperature transmitter signals.
- Power generation: Monitor boiler pressure, cooling-water flow, and auxiliary process measurements.
- Oil and gas: Acquire instrument signals from pipelines, separation equipment, and utility systems.
- Chemical production: Monitor process variables across reactors, tanks, and treatment units.
- Water treatment: Read flow, pressure, and other 4–20 mA instrument outputs.
Installation and Commissioning Guide
- Confirm the hardware: Check the complete model code and system compatibility.
- Review the system manual: Confirm the approved slot, base unit, and installation requirements.
- Isolate power: Follow site procedures before inserting or removing the module.
- Set channel wiring: Configure each channel for its transmitter's 2-wire or 4-wire connection.
- Check transmitter supply: Confirm the field device's voltage and current requirements.
- Connect field signals: Use the approved terminal block, MIL cable, or dedicated signal cable.
- Verify polarity: Check loop polarity and wiring against the transmitter and system drawings.
- Configure input scaling: Set the engineering range to match the connected instrument.
- Test each channel: Apply known current values and compare readings with expected values.
- Record commissioning results: Document channel assignments, scaling, and measured deviations.
Commissioning Example: Pressure Transmitter
A plant connects a 4–20 mA pressure transmitter to channel 1. The transmitter represents 0–10 bar.- At 4 mA, the expected pressure is 0 bar.
- At 12 mA, the expected pressure is 5 bar.
- At 20 mA, the expected pressure is 10 bar.
Diagnostics and Maintenance
The module supports analog signal acquisition. The supplied specifications do not confirm specific onboard wire-break alarms, channel fault indicators, or diagnostic codes. Use the following field checks when a channel reports an unexpected value:- Zero or low reading: Measure loop current and check transmitter power, polarity, and wiring continuity.
- High reading: Verify the current against the 25 mA permissible limit and inspect the transmitter output.
- Unstable reading: Check shield termination, grounding, cable routing, and electrical interference.
- Incorrect scaling: Compare the configured engineering range with the transmitter's calibrated range.
- Multiple channel issues: Inspect common power, system connections, and group transmitter supply settings.
- Periodic maintenance: Check terminal tightness, cable condition, and calibration records.
Compatibility and Selection Notes
The SAI143-H63 belongs to the Yokogawa SAI143 analog input family. Confirm compatibility with the installed control system before ordering. Check these items with your system engineer:- Control system model and I/O subsystem.
- Supported module type and installation position.
- Terminal block or cable interface requirements.
- Required 2-wire or 4-wire transmitter configuration.
- System power capacity and field transmitter supply requirements.
- Applicable hardware revision and configuration software.
Certifications and Environmental Information
The supplied product information specifies a 1.5 kV AC withstand test between input signals and the system. It does not identify specific CE, UKCA, ATEX, IECEx, or hazardous-area approvals. Confirm required certifications, operating temperature, humidity limits, and environmental ratings against the exact model's official documentation.Packaging and Order Information
- Product: Yokogawa SAI143-H63 analog input module.
- Packaging: Protective packaging suitable for industrial electronic equipment.
- Included accessories: Confirm terminal blocks, cables, and interface adapters with the sales team.
- Warranty: 12-month factory warranty, subject to the applicable sales terms.
- Shipping: FedEx, UPS, and DHL options are available.
- Dispatch: Target shipping within 24–48 hours after order confirmation and stock verification.
Global PLC Spare HUB's Insight
The SAI143-H63 suits installations that require multiple current-loop measurements in a compact I/O configuration. Its 40 ms update interval supports routine process monitoring. Engineers should still assess the response requirements of fast control loops separately. In field commissioning, verify the transmitter supply before connecting a full group of 2-wire instruments. For example, a maintenance team may replace one pressure transmitter while other channels remain active. The group supply switching function affects all 16 channels, so technicians should plan the work around that shared control. For reliable measurements, compare injected current values with system readings. Check the entire signal path, including transmitter calibration, loop wiring, input scaling, and control-system configuration.Frequently Asked Questions
1. Is the SAI143-H63 a digital output module? No. The provided specifications describe a 16-channel analog current input module. It receives 4–20 mA signals from field transmitters. 2. Can the module connect to 2-wire and 4-wire transmitters? Yes. The SAI143 family supports individual 2-wire or 4-wire channel settings. Confirm the exact wiring procedure in the applicable hardware manual. 3. Can I switch transmitter power on only one channel? The specified transmitter supply ON/OFF function applies to all 16 channels together in 2-wire mode. It does not provide individual channel switching through this function. 4. What should I check when a 4–20 mA reading appears incorrect? First, measure the actual loop current. Then verify polarity, transmitter supply, channel wiring, and configured scaling. Compare the reading with a calibrated current source when practical. 5. How should I select a replacement for an existing SAI143 module? Match the complete model code, system compatibility, interface hardware, and wiring configuration. Ask the supplier to confirm the H63 suffix and applicable hardware revision before placing an order.Tags
P: ¿Son estas piezas 100% originales y nuevas?
R: Sí. Cada componente está garantizado como 100% original, completamente nuevo y sellado de fábrica. También ofrecemos una garantía integral de 12 meses para su tranquilidad.
P: ¿Qué tan rápido es el envío a mi país?
R: Para artículos en stock, ofrecemos envío el mismo día. El envío exprés internacional (DHL/FedEx/UPS) generalmente entrega en un plazo de 3 a 5 días hábiles en todo el mundo.
P: ¿Puedo obtener una cotización formal con los costos de envío?
R: Absolutamente. Nuestro equipo de ventas está listo para proporcionar una factura proforma (PI) detallada que incluya las tarifas de envío más competitivas para su ubicación.
P: ¿Ofrecen descuentos por pedidos al por mayor?
R: Ofrecemos precios basados en el volumen para proyectos grandes o pedidos de varios artículos. Póngase en contacto con nosotros para obtener nuestra Garantía de Mejor Precio.
Garantía Integral de 12 Meses
Cada pieza suministrada por Global PLC Spare Hub está cubierta por una garantía de 12 meses a partir de la fecha de la factura.
- Cobertura: Defectos funcionales y fallos de hardware bajo condiciones normales de funcionamiento.
- Compromiso: Ofrecemos reparación, reemplazo o un reembolso completo inmediato para cualquier componente defectuoso verificado, para minimizar su tiempo de ininactividad operativa.
Política de Devoluciones y Cambios
Ofrecemos una política de devolución de 30 días para asegurar que reciba la pieza exacta que su sistema requiere.
- Elegibilidad: Se aceptan devoluciones de artículos sin instalar en su embalaje original sellado de fábrica.
- Proceso de RMA: Póngase en contacto con nuestro equipo de soporte para obtener un número de Autorización de Devolución de Mercancía (RMA) antes del envío.
- Procesamiento Rápido: Los reembolsos o cambios se procesan dentro de 3 a 5 días hábiles después de que el artículo devuelto pasa nuestra inspección técnica.
¿Necesita Asistencia Técnica? ¿No está seguro de si esta pieza es compatible con su sistema? [Consulte a nuestros Ingenieros] antes de comprar para asegurar una compatibilidad del 100%.