VE5009 Emerson DeltaV 24/12 VDC Power Supply Module
Manufacturer: Emerson
Product No.: VE5009
Condition: In stock
Product Type: Power Supply Module
Product Origin: USA
Payment: T/T, Western Union
Weight: 500g
Shipping port: Xiamen
Warranty: 12 months
Estimate delivery times: 12-26 days (International), 3-6 days (United States).
Return within 30 days of purchase. Duties & taxes are non-refundable.
Guaranteed Safe Checkout
VE5009 | DeltaV Enhanced System Power Supply
The VE5009 is an enhanced DC system power supply designed for the DeltaV distributed control system (DCS). It provides regulated power to controller and I/O carrier assemblies through multiple DC output rails.
This module accepts either 12 VDC or 24 VDC primary input. It generates +12 VDC, +5 VDC, and +3.3 VDC outputs for compatible DeltaV system components.
Its enhanced power architecture supports different carrier configurations. Integrated input protection, output overvoltage protection, status indicators, and relay alarm contacts simplify system monitoring.
The VE5009 also supports demanding industrial environments. Its operating temperature range extends from -40 °C to +70 °C, with output derating above 60 °C.
01 | Product Identification and System Architecture
| Item | Specification |
| Product Manufacturer | DeltaV |
| Product Model | VE5009 |
| Product Family | DeltaV Enhanced System Power Supply |
| Product Type | Enhanced DC System Power Supply |
| Input Architecture | 12 VDC / 24 VDC |
| Primary Power Connection | Two-wire DC input |
| Output Rails | +12 VDC, +5 VDC, +3.3 VDC |
| Input Protection | Internal non-replaceable fuse |
| Output Protection | Overvoltage protection |
| Status Indication | Green DC Power Input LED and red Error LED |
| Alarm Interface | Two-wire normally open relay contact |
| Weight | Refer to the applicable manufacturer hardware documentation |
02 | Dual-Voltage Input and Electrical Characteristics
The VE5009 accepts two nominal DC input voltages. This flexibility supports different DeltaV power distribution arrangements.
| Input Parameter | 12 VDC Configuration | 24 VDC Configuration |
| Nominal Input Voltage | 12 VDC | 24 VDC |
| Input Tolerance | -4% to +5% | ±20% |
| Input Current | 14.8 A | 6.1 A |
| Primary Connection | Two-wire DC | Two-wire DC |
Soft-Start Inrush Current:
- 12 VDC input: 12 A peak maximum for 5 ms.
- 24 VDC input: 20 A peak maximum for 5 ms.
The specified 24 VDC inrush value includes the 12 VDC output. The 12 VDC input inrush specification excludes the 12 VDC output.
Engineering Note: Select the upstream DC power source according to the applicable input voltage, continuous current, and transient requirements. Do not size the source using nominal voltage alone.
03 | Output Distribution and Power Ratings
The VE5009 provides three regulated output rails. The available +12 VDC current depends on the primary input voltage and operating temperature.
Output Ratings: -40 °C to +60 °C
| Output Rail | 12 VDC Input | 24 VDC Input |
| +12 VDC | 13 A | 8.0 A |
| +5 VDC | 2.0 A | 2.0 A |
| +3.3 VDC | 2.0 A | 2.0 A |
| Combined +5 VDC and +3.3 VDC Power | 10 W maximum | |
Output Ratings: +60 °C to +70 °C
| Output Rail | 12 VDC Input | 24 VDC Input |
| +12 VDC | 10 A | 6.0 A |
| +5 VDC | 2.0 A | 2.0 A |
| +3.3 VDC | 2.0 A | 2.0 A |
| Combined +5 VDC and +3.3 VDC Power | 10 W maximum | |
Important Power Budget Considerations:
- The +12 VDC output supplies the primary system power rail.
- The +5 VDC and +3.3 VDC outputs share a combined 10 W power budget.
- Do not calculate the auxiliary output capacity by adding both individual current ratings.
- Reduce the +12 VDC load when ambient temperatures exceed 60 °C.
- Check the total carrier power demand before commissioning.
04 | Protection and Power Continuity
The VE5009 integrates several electrical protection mechanisms. These functions help protect the power supply and connected system components.
| Protection Function | Technical Specification |
| Input Protection | Internally fused, non-replaceable |
| Output Overvoltage Protection | 110% to 120% of nominal output voltage |
| Hold-Up Time | 5 ms at full load and minimum input voltage |
| Output Hold-Up Accuracy | Within 5% of nominal output |
| Primary Power | 12 VDC or 24 VDC |
Hold-Up Time Qualification: The 5 ms hold-up specification excludes 12 VDC output current when the primary input is 12 VDC.
The internal fuse cannot be replaced independently. Investigate input wiring, source capacity, and downstream faults before replacing the complete module.
05 | LED Diagnostics and Alarm Relay
Two front-panel indicators provide basic power and fault information. An independent relay contact supports external monitoring.
| Indicator | Status | Meaning |
| Green LED | ON | DC input power is present. The internal fuse and diode are functioning correctly. |
| Red LED | ON | The +5 VDC or +3.3 VDC output is outside its specified tolerance. |
Alarm Contact Specifications:
- Contact arrangement: Two-wire normally open relay.
- Normal condition: Relay closes when +5 VDC and +3.3 VDC outputs remain within ±4% of nominal.
- Contact rating: 2.0 A at 30 VDC.
- AC contact rating: 2.0 A at 250 VAC.
Commissioning Tip: Verify the alarm relay state during startup and under simulated output faults. Connect the relay to an appropriate monitoring circuit when the application requires remote power-status supervision.
06 | Carrier Mounting and System Integration
The VE5009 supports several DeltaV carrier arrangements. Correct slot selection ensures proper electrical and mechanical integration.
| Carrier Type | Permitted Mounting Position |
| 2-Wide Power/Controller Carrier | Either slot |
| VerticalPlus 4-Wide Carrier | Dedicated power slot |
| 4-Wide Power Carrier | Any slot |
Installation Sequence:
- Identify the DeltaV carrier model and available power slots.
- Verify the required 12 VDC or 24 VDC input configuration.
- Calculate the carrier's total power consumption.
- Isolate the DC supply before inserting or removing the module.
- Install the VE5009 into the approved carrier position.
- Connect the two-wire primary DC power input.
- Check connector engagement and module seating.
- Restore power and inspect both LED indicators.
- Verify the alarm relay and downstream system power status.
Installation Warning: Follow the DeltaV carrier installation manual. Confirm the correct power slot and system grounding arrangement before energizing the assembly.
07 | Industrial Environmental Specifications
The VE5009 supports demanding industrial operating conditions. Its temperature and environmental ratings suit installations in process control cabinets and industrial equipment rooms.
| Environmental Parameter | Specification |
| Operating Temperature | -40 °C to +60 °C without derating |
| Extended Operating Temperature | +60 °C to +70 °C with derating |
| Storage Temperature | -40 °C to +70 °C |
| Relative Humidity | 5% to 95%, non-condensing |
| Airborne Contaminants | ISA-S71.04-1985 Class G3 |
| Shock Resistance | 10 g, half-sine wave, 11 ms |
| Vibration, 5–16 Hz | 1 mm peak-to-peak |
| Vibration, 16–150 Hz | 0.5 g |
Environmental Engineering Considerations:
- Maintain cabinet ventilation around the power supply.
- Check actual cabinet temperature under maximum system load.
- Prevent condensation during storage and operation.
- Evaluate airborne contaminants in chemical processing environments.
- Consider output derating when the installation approaches 60 °C.
08 | Hazardous Area Ratings and Compliance
The specified VE5009 environmental classification includes the following hazardous-location ratings:
- FM: Class I, Division 2.
- CENELEC: Zone 2, Gas Groups A, B, C, and D, T4.
- ATEX: Category 3G, IIC, T4, nC.
Verify the exact approval markings on the product nameplate and applicable manufacturer certificates. Installation must follow the hazardous-area requirements for the intended location.
09 | Engineering Troubleshooting Reference
| Observed Condition | Recommended Inspection |
| Green LED OFF | Check primary DC input, polarity, wiring, and internal protection status. |
| Red LED ON | Inspect +5 VDC and +3.3 VDC output loading and voltage levels. |
| System Reset During Startup | Check input inrush capacity and DC source stability. |
| Intermittent Power Fault | Inspect carrier seating, connector engagement, and supply wiring. |
| Power Fault at High Temperature | Review thermal conditions and output derating requirements. |
| Alarm Relay Does Not Close | Measure auxiliary output voltages and inspect relay wiring. |
| Repeated Fuse or Input Failure | Investigate external wiring faults and excessive input current. |
Maintenance Recommendation: Record input voltage, output loading, cabinet temperature, and LED status during scheduled inspections. These measurements help identify developing power-system problems.
10 | Compatibility and Replacement Selection
Before selecting a VE5009 replacement, engineers should verify the complete DeltaV power distribution arrangement.
- Input Voltage: Confirm whether the system uses 12 VDC or 24 VDC.
- Output Demand: Calculate +12 VDC, +5 VDC, and +3.3 VDC consumption.
- Carrier Compatibility: Confirm the installed carrier supports the VE5009.
- Slot Assignment: Check the permitted power supply position.
- Thermal Conditions: Apply the correct output ratings for actual cabinet temperature.
- Alarm Monitoring: Verify the external circuit supports the specified relay contact rating.
- Hazardous Area: Confirm the installation meets the applicable approval requirements.
Do not assume that every DeltaV power supply shares the same pinout, output capacity, or carrier compatibility. Verify the complete part number before replacement.
11 | Package Contents
- 1 × DeltaV VE5009 Enhanced System Power Supply.
- Product configuration according to the specified model number.
Carrier assemblies, external DC power sources, field wiring, and additional installation accessories are not included unless specified in the purchase order.
12 | Frequently Asked Questions
Q1: Can the VE5009 operate from a 24 VDC source while supplying a 12 VDC system rail?
Yes. The module accepts 24 VDC input and provides a regulated +12 VDC output. The rated +12 VDC output current reaches 8 A below 60 °C. It decreases to 6 A between 60 °C and 70 °C.
Q2: Why might a VE5009 show a green LED while the DeltaV system still reports a power-related fault?
The green LED confirms primary DC input and internal fuse/diode status. It does not independently verify every downstream load or carrier connection. Measure the output rails and inspect connector seating, system loading, and distribution wiring.
Q3: Can the VE5009 operate continuously at 70 °C with its full rated output?
No. The module requires output derating above 60 °C. At 70 °C, use the specified reduced output ratings. Check the complete carrier load before approving the installation.
Q4: What should engineers investigate before replacing a VE5009 with a recurring red LED indication?
Measure the +5 VDC and +3.3 VDC rails first. Then isolate downstream loads to identify possible overloads or short circuits. Inspect carrier connections and cabinet temperature. Replace the module only after ruling out external faults.
Q5: Is the VE5009 suitable for redundant DeltaV power arrangements?
Its suitability depends on the carrier architecture and system power design. Check the carrier documentation, source arrangement, load-sharing requirements, and redundancy strategy. Do not assume that two power supplies provide automatic redundancy without the appropriate system configuration.
13 | Warranty, Shipping and Technical Support
We supply the VE5009 DeltaV Enhanced System Power Supply for industrial DCS power distribution and process automation applications.
- Product Condition: New and original.
- Warranty: 12-month warranty.
- Shipping Methods: FedEx, UPS, and DHL.
- Order Verification: Part number and application compatibility checks.
- Technical Assistance: Support with input voltage, output ratings, and carrier selection.
- Quotation: Contact us for current pricing and availability.
Send us your VE5009 part number and DeltaV carrier information. Our team can assist with product identification and replacement selection.
Q: Are these parts 100% original and new?
A: Yes. Every component is guaranteed to be 100% original, brand-new, and factory-sealed. We also provide a 12-month comprehensive warranty for your peace of mind.
Q: How fast is the shipping to my country?
A: For in-stock items, we offer same-day dispatch. International express shipping (DHL/FedEx/UPS) typically delivers within 3–5 business days worldwide.
Q: Can I get a formal quotation with shipping costs?
A: Absolutely. Our sales team is ready to provide a detailed Proforma Invoice (PI) including the most competitive shipping rates for your location.
Q: Do you offer discounts for bulk orders?
A: We provide volume-based pricing for large projects or multiple-item orders. Please contact us to get our Best Price Guarantee.
12-Month Comprehensive Warranty
Every part supplied by Global PLC Spare Hub is covered by a 12-month warranty from the date of invoice.
- Coverage: Functional defects and hardware failures under normal operating conditions.
- Commitment: We provide immediate repair, replacement, or a full refund for any verified defective components to minimize your operational downtime.
Returns & Exchange Policy
We offer a 30-day return policy to ensure you receive the exact part your system requires.
- Eligibility: Returns are accepted for uninstalled items in their original, factory-sealed packaging.
- RMA Process: Please contact our support team to obtain a Return Merchandise Authorization (RMA) number before shipping.
- Fast Processing: Refunds or exchanges are processed within 3–5 business days after the returned item passes our technical inspection.
Need Technical Assistance?Not sure if this part is compatible with your system? [Consult our Engineers] before purchasing to ensure 100% compatibility.