Overview
The TSXDSY16T2 is a high-density 16-point discrete transistor output module engineered for the Schneider Electric Modicon Premium automation platform. Delivering 24 VDC source (PNP) operation across two isolated groups of 8 channels, the TSXDSY16T2 module provides precise low-latency control for industrial field actuators, solenoid valves, and intermediate relays.
Technical Architecture and Specifications
| Manufacturer Brand | Schneider Electric |
| Part Number | TSXDSY16T2 |
| Product Family | Modicon Premium Series |
| Module Type | Discrete Transistor PNP Solid-State Output Module |
| Channel Capacity | 16 channels (arranged in 2 isolated groups of 8) |
| Output Logic & Voltage | Source (PNP), 24 VDC nominal field supply |
| Current Rating | 0.5 A continuous per channel (max 4 A per group of 8) |
| Response Time | 0.5 ms typical (turn-on / turn-off propagation delay) |
| Channel Isolation | 1500 VAC channel-to-bus dielectric strength (>10 MΩ @ 500 VDC) |
| Backplane Power | 5 VDC @ 80 mA (total module power dissipation 1.1 W) |
| Thermal Tolerances | Operating: 0 °C to +60 °C; Storage: -40 °C to +85 °C |
| Physical Footprint | 140 × 35 × 80 mm; Weight: 0.15 kg; Rack slots required: 1 slot |
| Enclosure Protection | IP20 ingress resistance rating |
Target Equipment and Operational Scenarios
- Direct driving of 24 VDC pneumatic directional control valves and high-speed solenoid banks.
- Interfacing with pilot relays, magnetic contactors, and digital annunciators in batch control systems.
- Packaging, material handling conveyers, and automotive body shop assembly cells managed by Premium PLCs.
- Upgrading legacy TSX57 rack configurations requiring fast 0.5 ms signal commutation.
Integrated Protection and Self-Diagnostics
- Electronic Overload & Short-Circuit Protection: Each channel group automatically trips upon detecting thermal or current spikes, resetting safely upon system reactivation.
- Bus Isolation Shielding: 1500 VAC dielectric rating prevents severe high-voltage field transients from damaging backplane CPU components.
- Status Annunciation: Front-panel diagnostic LEDs give field technicians immediate visual indication of channel logic state and field power integrity.
Global PLC Spare HUB's Insight
In automated packaging installations, field technicians often mistake inductive kickback trip conditions on the TSXDSY16T2 for internal module failure. When driving un-suppressed 24 VDC solenoid coils, inductive voltage spikes can exceed the internal 0.5 A thermal threshold during rapid cycling, triggering auto-trip protection. Installing flyback diodes directly across DC inductive loads eliminates false overload trips and extends channel output stage longevity.
Selection Guide and Engineering Considerations
- Load Compatibility: Confirm that your downstream field devices operate on 24 VDC PNP (sourcing) wiring topology rather than NPN (sinking).
- Current Density: Ensure total group current does not exceed thermal limits when high duty-cycle actuators trigger simultaneously.
- Backplane Power Budget: Account for the 80 mA 5 VDC draw on the rack backplane power supply when adding expansion modules.
Commercial Guarantees and Shipping Logistics
- Warranty Coverage: Backed by a full 12-month operational warranty.
- Dispatch Lead Time: Ships within 24 to 48 hours post-order verification.
- Global Express Courier: Worldwide expedited shipping via FedEx, UPS, and DHL.
Frequently Asked Questions (FAQ)
What is the maximum continuous current capacity per output point on this module?
Each channel delivers up to 0.5 A at 24 VDC continuously under nominal operating temperatures.
How does the short-circuit protection mechanism handle a fault event on a field cable?
The electronic protection trips the affected output channel immediately to prevent transistor destruction, restoring output capability upon fault removal and power reactivation.
Is an external auxiliary power supply required to drive connected field loads?
Yes, an external 24 VDC field power supply must be connected to feed the transistor output switching stage.
Can I mix PNP and NPN field devices on the same module rack location?
This unit strictly provides PNP (sourcing) output logic; NPN (sinking) loads require an external interface relay or a dedicated sinking module.
What preventative check should be performed before replacing a tripped module in service?
Measure the coil resistance of connected solenoids and verify field wire insulation integrity to rule out shorted field components that caused the original protection trip.
Tags
Q: Are these parts 100% original and new?
A: Yes. Every component is guaranteed to be 100% original, brand-new, and factory-sealed. We also provide a 12-month comprehensive warranty for your peace of mind.
Q: How fast is the shipping to my country?
A: For in-stock items, we offer same-day dispatch. International express shipping (DHL/FedEx/UPS) typically delivers within 3–5 business days worldwide.
Q: Can I get a formal quotation with shipping costs?
A: Absolutely. Our sales team is ready to provide a detailed Proforma Invoice (PI) including the most competitive shipping rates for your location.
Q: Do you offer discounts for bulk orders?
A: We provide volume-based pricing for large projects or multiple-item orders. Please contact us to get our Best Price Guarantee.
12-Month Comprehensive Warranty
Every part supplied by Global PLC Spare Hub is covered by a 12-month warranty from the date of invoice.
- Coverage: Functional defects and hardware failures under normal operating conditions.
- Commitment: We provide immediate repair, replacement, or a full refund for any verified defective components to minimize your operational downtime.
Returns & Exchange Policy
We offer a 30-day return policy to ensure you receive the exact part your system requires.
- Eligibility: Returns are accepted for uninstalled items in their original, factory-sealed packaging.
- RMA Process: Please contact our support team to obtain a Return Merchandise Authorization (RMA) number before shipping.
- Fast Processing: Refunds or exchanges are processed within 3–5 business days after the returned item passes our technical inspection.
Need Technical Assistance?Not sure if this part is compatible with your system? [Consult our Engineers] before purchasing to ensure 100% compatibility.