IS200ERBPG1A GE EX2100 Exciter Regulator Backplane Module In Stock
Manufacturer: GE
Product No.: IS200ERBPG1A
Condition: In stock
Product Type: Regulator Backplane Module
Product Origin: USA
Payment: T/T, Western Union
Weight: 500g
Shipping port: Xiamen
Warranty: 12 months
Estimate delivery times: 12-26 days (International), 3-6 days (United States).
Return within 30 days of purchase. Duties & taxes are non-refundable.
Guaranteed Safe Checkout
Overview
The General Electric IS200ERBPG1A is an Exciter Regulator Backplane (ERBP) module designed for the EX2100 excitation control platform and integrated Mark VI turbine automation systems. Serving as the master structural and electrical hub, it houses 3U/6U Eurocard control cards, distributes system power rails, and facilitates high-speed inter-board data routing via standardized DIN connectors across simplex or redundant excitation architectures.
Backplane Architecture & Interconnect Matrix
-
Structural Card Slot Integration:
- Accepts 3U and 6U Versa Module Euro (VME) cards via 96-pin and 128-pin DIN connectors.
- Houses core control hardware including ACLA, DSPX, ERIO, EPSM, ERDD, and EROC cards.
- Distributes regulated power planes directly across inserted control card edge interfaces.
-
Power Distribution Terminals & Fan Interfaces:
- Primary power input wired via bottom heavy-duty posts: TB1 (Positive) and TB2 (Negative).
- Dedicated onboard power taps for cooling fan assemblies via J1F1 and J1F2 headers.
- Auxiliary power outputs interface with ERRR (J5M1), ERRB (J3), and EDCF (J16) boards.
-
Hardware Configuration & Communication ID:
- Integrated Board ID serial bus reads hardware revisions, barcodes, and serial numbers automatically.
- Onboard Master Selection Jumpers enable hardwired selection between Simplex and Redundant operating modes.
- Keypad interface connector (J4) provides local diagnostic display access.
Technical Specifications Parameter Matrix
| Brand / Manufacturer | General Electric (GE Industrial Systems) |
| Part / Model Number | IS200ERBPG1A |
| Functional Acronym | ERBP (Exciter Regulator Backplane) |
| System Platform | EX2100 Excitation / Mark VI Controls |
| Operating Modes | Simplex or Dual/Triple Redundant (Jumper Selectable) |
| Card Slot Connectors | 3U / 6U VME Eurocard (96-pin and 128-pin DIN) |
| Primary Power Input | Terminal Posts TB1 (+V) and TB2 (-V) |
| Auxiliary Taps | Fan Power (J1F1, J1F2), Keypad (J4), ERRR (J5M1), ERRB (J3), EDCF (J16) |
| Communication Support | Ethernet Modbus / Serial (Standalone Retrofit Systems) |
| Hardware Identification | Onboard 1-Wire Serial Board ID Interface |
| Physical Weight | Approx. 3.00 lbs (1.36 kg) |
| Country of Origin | United States (USA) |
Target Applications & System Integration
-
Excitation Control Platforms:
- Serves as the main motherboard rack inside EX2100 generator static excitation systems.
- Integrates with Mark VI turbine control cabinets for unified generator voltage regulation.
-
Industrial Retrofits & Plant Upgrades:
- Deploys into standalone generator control retrofits utilizing Modbus TCP or RTU serial links.
- Operates in gas, steam, and hydro power generation stations requiring high-reliability excitation.
Diagnostic Capabilities & Fault Tracing
-
Serial Board ID Tracing:
- The system controller interrogates the serial ID chip on every inserted card to verify slot alignment and hardware compatibility before initializing power.
-
Hardware Diagnostic Taps:
- Direct connection ports allow oscilloscope signal monitoring across DC feedback loops (EDCF) and power distribution rails without pulling active cards.
Supply Chain & Warranty Guarantees
-
Package Contents:
- One factory-inspected GE IS200ERBPG1A exciter regulator backplane board.
- Anti-static enclosure lined with high-density protective packaging.
-
Warranty Policy:
- Backed by a comprehensive 12-month replacement warranty from date of shipment.
-
Express Shipping Logistics:
- Dispatched within 24 to 48 hours upon order confirmation.
- Global express air freight provided via FedEx, UPS, or DHL.
Global PLC Spare HUB's Insight
When performing maintenance on EX2100 excitation racks, physical installation integrity on the IS200ERBPG1A backplane is critical. Because this motherboard passes high-current power rails alongside delicate high-speed serial bus lines, bent pins on the 96-pin or 128-pin VME DIN connectors are a primary cause of intermittent communication dropouts during card hot-swaps.
During an emergency overhaul at a combined-cycle power plant, a generator failed to synchronize due to a missing DSPX board detection fault on an IS200ERBPG1A. Plant technicians had repeatedly replaced the DSPX card without success. Our field engineers inspected the backplane slot using a borescope and discovered a recessed pin on the J1 DIN connector, caused by forced card insertion during a prior turnaround. Straightening the pin and verifying master selection jumper alignment restored full board ID handshaking immediately. We strongly recommend inspecting all backplane socket pins with optical magnification prior to reseating 3U/6U control modules.
Frequently Asked Questions (FAQ)
Q: What happens if the Master Selection Jumpers on the IS200ERBPG1A are set incorrectly?
A: Incorrect jumper positions cause configuration mismatches between simplex and redundant control logic, leading to boot-up initialization halts or loss of redundant takeover capability.
Q: How are power polarity connections physically verified on TB1 and TB2 on the IS200ERBPG1A?
A: Positive DC power must be landed strictly on terminal TB1, and negative DC power on terminal TB2 at the bottom of the board. Reverse polarity can damage onboard cooling fan drives and option cards.
Q: Can the IS200ERBPG1A backplane be replaced without removing the mounted VME control cards?
A: No. All inserted daughter cards (DSPX, ACLA, ERIO, EPSM) must be unlatched and removed first before unbolting the backplane assembly from the enclosure subpanel.
Q: Why does the system report a missing card alarm when a card is firmly seated in the IS200ERBPG1A slot?
A: This indicates a failure in the 1-Wire Board ID device read path, caused by corrosion on the DIN edge connector, a damaged serial bus trace, or an unseated connector pin.
Q: How can field engineers test fan power output terminals J1F1 and J1F2 during a shutdown?
A: Disconnect fan plugs J1F1/J1F2 and measure DC voltage across the pins with main system power applied to TB1/TB2. Zero voltage indicates blown backplane power traces or upstream supply failure.
Tags
Q: Are these parts 100% original and new?
A: Yes. Every component is guaranteed to be 100% original, brand-new, and factory-sealed. We also provide a 12-month comprehensive warranty for your peace of mind.
Q: How fast is the shipping to my country?
A: For in-stock items, we offer same-day dispatch. International express shipping (DHL/FedEx/UPS) typically delivers within 3–5 business days worldwide.
Q: Can I get a formal quotation with shipping costs?
A: Absolutely. Our sales team is ready to provide a detailed Proforma Invoice (PI) including the most competitive shipping rates for your location.
Q: Do you offer discounts for bulk orders?
A: We provide volume-based pricing for large projects or multiple-item orders. Please contact us to get our Best Price Guarantee.
12-Month Comprehensive Warranty
Every part supplied by Global PLC Spare Hub is covered by a 12-month warranty from the date of invoice.
- Coverage: Functional defects and hardware failures under normal operating conditions.
- Commitment: We provide immediate repair, replacement, or a full refund for any verified defective components to minimize your operational downtime.
Returns & Exchange Policy
We offer a 30-day return policy to ensure you receive the exact part your system requires.
- Eligibility: Returns are accepted for uninstalled items in their original, factory-sealed packaging.
- RMA Process: Please contact our support team to obtain a Return Merchandise Authorization (RMA) number before shipping.
- Fast Processing: Refunds or exchanges are processed within 3–5 business days after the returned item passes our technical inspection.
Need Technical Assistance?Not sure if this part is compatible with your system? [Consult our Engineers] before purchasing to ensure 100% compatibility.