HBS01-CJC HN800 Singular I/O Mounting Base | AI03 AI04 RTD TC Solution
Manufacturer: ABB
Product No.: HBS01-CJC
Condition: In stock
Product Type: I/O Mounting Base
Product Origin: USA
Payment: T/T, Western Union
Weight: 288g
Shipping port: Xiamen
Warranty: 12 months
Estimate delivery times: 12-26 days (International), 3-6 days (United States).
Return within 30 days of purchase. Duties & taxes are non-refundable.
Guaranteed Safe Checkout
HBS01-CJC | HN800 Analog Input Mounting Base
HBS01-CJC is a full-size mounting base for Singular AI03 and AI04 analog input modules. It provides field signal termination and mechanical integration within the HN800 I/O system.
Designed for horizontal-row installation, this base supports two analog input configurations:
- AI03: Eight-channel RTD input, supporting 2-wire, 3-wire, and 4-wire sensors.
- AI04: Sixteen-channel thermocouple and millivolt input.
An integrated RTD reference sensor supports Cold Junction Compensation (CJC) for thermocouple measurements. This arrangement provides a local temperature reference without requiring a separate base-mounted compensation sensor.
Two 16-point headers connect field signals through pluggable terminal blocks or compatible SPK0x_-yy marshaling cables. Engineers can select direct wiring or remote termination according to cabinet architecture.
01 | Hardware Architecture and Connection Design
| Design Element | Engineering Function |
| Dual 16-point Headers | Provide two independent field termination interfaces. |
| Pluggable Terminal Blocks | Support direct connection of field signal conductors. |
| SPK0x_-yy Marshaling Cables | Connect the base to third-party termination hardware. |
| Integrated RTD | Provides a temperature reference for thermocouple CJC. |
| Mechanical Keying | Optional feature that helps prevent incorrect module insertion. |
| DIN-Rail Latch | Secures the mounting base to the installation rail. |
| Horizontal Mounting | Supports compact HN800 I/O cabinet arrangements. |
Field wiring capacity:
- Up to 8 RTD channels with AI03.
- Up to 16 TC or mV channels with AI04.
- Compatible with #22–14 AWG stranded or solid conductors.
- Supports #12 AWG stranded conductors.
- Galvanic isolation test voltage: 1500 V for up to one minute.
02 | Technical Data and Identification
| Specification | Value |
| Brand | Singular |
| Model | HBS01-CJC |
| Product Series | HN800 I/O |
| Product Type | Analog Input Mounting Base |
| System Architecture | Singular I/O |
| Supported Modules | AI03, AI04 |
| Input Configuration | 8-channel RTD or 16-channel TC/mV |
| CJC Reference | Integrated RTD |
| Redundancy Compatibility | HN800 common bus architecture supports Singular and Redundant I/O configurations |
| Form Factor | Full-size |
| Mounting Orientation | Horizontal Row |
| Mounting Rail | 35 mm DIN Rail |
| HN800 Bus Length | 150 mm |
| Hot-Swap Capability | No |
| Field Power Connection | Compact |
| Field Power Fusing | Not Applicable |
| Signal Interfaces | 2 × Pluggable 16-point Terminal Blocks |
| Maximum Current | HBX01L/HBX01R pair: 3.0 A maximum at +24 VDC |
| Overvoltage Category | Category I for power |
| MTBF | 5,493,564 hours (MIL-HDBK-217-FN2) |
| MTTR | 8 hours |
| Protection Rating | IP20 |
| Weight | 288 g |
| Dimensions | 203 × 45 × 86 mm (H × W × D) |
03 | Environmental Qualification
The HBS01-CJC supports industrial control environments with defined thermal, humidity, vibration, and mechanical resistance limits.
| Environmental Parameter | Specification |
| Operating Temperature | -40 to +70 °C |
| Storage Temperature | -40 to +85 °C |
| Relative Humidity | 20%–95% at 40 °C, non-condensing |
| Operational Vibration | 5–60 Hz: 0.137 mm; 60–150 Hz: 1.0 G |
| Transportation Vibration | 10–500 Hz |
| Storage Shock | 15 G, 11 ms |
| Drop Test | 100 mm |
| Operating Altitude | Up to 3,048 m |
| Storage Altitude | Up to 12,192 m |
| Protection Class | IP20, EN 60529 |
| Standard Air Quality | ISA S71.04 G1 |
Corrosive atmosphere selection: The HBS01-CJCA variant is available for ISA S71.04 G3-compliant environments. Confirm the required air-quality classification before ordering.
04 | EMC and Electrical Immunity
The mounting base has defined electromagnetic compatibility test levels. These specifications help engineers evaluate its suitability for industrial control cabinets.
| Test Category | Standard and Severity |
| ESD Immunity | IEC/EN 61000-4-2, Level 3 |
| Surge Immunity | IEC/EN 61000-4-5, Level 3 |
| Electrical Fast Transient | IEC/EN 61000-4-4, Level 3 |
| Radiated RFI Immunity | IEC/EN 61000-4-3, Level 3 |
| Conducted Immunity | IEC/EN 61000-4-6, Level 3 |
| Magnetic Field Immunity | IEC/EN 61000-4-8, Level 4 |
| Voltage Dips and Interruptions | IEC/EN 61000-4-11 |
| Radiated Emissions | IEC/EN 61000-6-4, CISPR 11 + A1, Group 1, Class A |
| Conducted Emissions | IEC/EN 61000-6-4, CISPR 11 + A1, Group 1, Class A |
05 | Installation and Commissioning Procedure
Mechanical installation
- Confirm the base identification as HBS01-CJC.
- Check the cabinet layout and available 35 mm DIN-rail space.
- Position the base for horizontal-row installation.
- Engage the DIN-rail latch and verify mechanical retention.
- Check adjacent base alignment and HN800 bus connections.
Electrical connection
- Identify the installed module as AI03 or AI04.
- Prepare field conductors within the specified wire-size limits.
- Connect field signals through the two 16-point interfaces.
- Use compatible marshaling cables for third-party termination systems.
- Verify channel assignments, polarity, and wiring continuity.
- Check the RTD reference configuration when using thermocouples.
Commissioning verification
- Confirm the correct module-to-base combination.
- Verify the HN800 bus configuration and module recognition.
- Check RTD channel readings against a reference source.
- For TC applications, inspect CJC readings and thermocouple polarity.
- For mV applications, verify signal routing and configured input ranges.
- Record the final channel map for maintenance personnel.
Important: The HBS01-CJC does not support hot swapping. Isolate relevant power and field circuits before replacing modules or changing wiring.
06 | Maintenance and Troubleshooting Insights
| Observed Symptom | Recommended Engineering Check |
| Incorrect RTD readings | Inspect sensor wiring and 2-, 3-, or 4-wire configuration. |
| Thermocouple temperature offset | Check polarity, terminal connections, and CJC reference readings. |
| Unstable mV signals | Inspect shielding, grounding, and cable routing. |
| Intermittent channel signals | Check terminal engagement and conductor termination. |
| Module installation problems | Verify mechanical keying and base compatibility. |
| Bus communication problems | Inspect base alignment and HN800 bus connections. |
During preventive maintenance, inspect terminal connections and DIN-rail retention. Keep wiring records updated after every field modification.
07 | System Compatibility and Selection Guidance
The HN800 platform supports a common I/O bus architecture across multiple hardware configurations. Singular and Redundant modules can operate within compatible common bus arrangements. Compact and Full-size products also share platform compatibility.
However, engineers must distinguish platform-level compatibility from individual mounting-base specifications.
- Choose AI03: When the application requires up to eight RTD measurement channels.
- Choose AI04: When the application requires up to sixteen thermocouple or mV channels.
- Choose HBS01-CJC: When the project requires a Singular, Full-size, horizontal-row mounting base.
- Choose HBS01-CJCA: When the installation requires the G3 air-quality variant.
- Check mechanical dimensions: Allow for the 203 mm height and 45 mm width.
- Check bus architecture: Confirm the 150 mm HN800 bus arrangement.
Engineering selection note: The HBS01-CJC is not interchangeable with every HN800 base solely because the platform supports common-bus compatibility. Verify mounting orientation, dimensions, bus layout, and module support.
08 | Certifications and Regulatory Compliance
- CSA: Certified for ordinary, non-hazardous process control locations.
- CSA Class I, Division 2: Groups A, B, C, and D nonincendive locations.
- CE Marking: EMC Directive 2004/108/EC and Low Voltage Directive 2006/95/EC, as specified.
- RoHS: Directive 2015/863.
- WEEE: Directive 2012/19/EU.
- Electrical Safety: IEC/EN 61010-1 testing.
- Environmental Testing: Applicable IEC/EN 60068 and MIL-STD-810G methods.
Confirm the applicable product declaration and certification documents before using the equipment in regulated installations.
09 | Package Contents
- 1 × Singular HBS01-CJC Analog Input Mounting Base.
- Pluggable terminal blocks: confirm inclusion with the supplier.
- Marshaling cables and I/O modules: supplied separately unless specified in the order.
10 | Technical FAQ – Application and Engineering
Q1: How does the horizontal mounting arrangement affect cabinet planning?
The HBS01-CJC uses a horizontal-row layout and measures 203 mm high by 45 mm wide. Engineers should reserve sufficient rail space and check adjacent bus connections before designing the cabinet layout.
Q2: What should engineers consider when connecting multiple RTD sensor types?
Different RTD wiring methods require different terminal assignments. Confirm each sensor's 2-, 3-, or 4-wire configuration before wiring. Incorrect conductor allocation can introduce measurement errors or open-circuit indications.
Q3: Why should thermocouple wiring and CJC verification occur together?
Thermocouple measurements depend on the temperature reference at the connection point. Incorrect polarity, poor terminal contact, or an abnormal CJC reference can produce temperature offsets. Verify both signal wiring and reference readings during commissioning.
Q4: What information helps diagnose intermittent analog input signals?
Record the affected channel, sensor type, signal trend, and module identification. Inspect terminal connections and cable routing first. Then compare the field signal with the controller's reported value to isolate the fault location.
Q5: How can buyers avoid selecting the wrong HN800 mounting base?
Check the complete model number, mounting orientation, dimensions, supported I/O modules, and bus arrangement. The HBS01-CJC uses a 150 mm bus length and horizontal-row mounting. Do not select a replacement based on channel capacity alone.
Tags
Q: Are these parts 100% original and new?
A: Yes. Every component is guaranteed to be 100% original, brand-new, and factory-sealed. We also provide a 12-month comprehensive warranty for your peace of mind.
Q: How fast is the shipping to my country?
A: For in-stock items, we offer same-day dispatch. International express shipping (DHL/FedEx/UPS) typically delivers within 3–5 business days worldwide.
Q: Can I get a formal quotation with shipping costs?
A: Absolutely. Our sales team is ready to provide a detailed Proforma Invoice (PI) including the most competitive shipping rates for your location.
Q: Do you offer discounts for bulk orders?
A: We provide volume-based pricing for large projects or multiple-item orders. Please contact us to get our Best Price Guarantee.
12-Month Comprehensive Warranty
Every part supplied by Global PLC Spare Hub is covered by a 12-month warranty from the date of invoice.
- Coverage: Functional defects and hardware failures under normal operating conditions.
- Commitment: We provide immediate repair, replacement, or a full refund for any verified defective components to minimize your operational downtime.
Returns & Exchange Policy
We offer a 30-day return policy to ensure you receive the exact part your system requires.
- Eligibility: Returns are accepted for uninstalled items in their original, factory-sealed packaging.
- RMA Process: Please contact our support team to obtain a Return Merchandise Authorization (RMA) number before shipping.
- Fast Processing: Refunds or exchanges are processed within 3–5 business days after the returned item passes our technical inspection.
Need Technical Assistance?Not sure if this part is compatible with your system? [Consult our Engineers] before purchasing to ensure 100% compatibility.