F3YD08-6A Yokogawa FA-M3 Transistor Output Module
Manufacturer: Yokogawa
Product No.: F3YD08-6A
Condition: In stock
Product Type: Transistor Output Module
Product Origin: SG
Payment: T/T, Western Union
Weight: 180g
Shipping port: Xiamen
Warranty: 12 months
Estimate delivery times: 12-26 days (International), 3-6 days (United States).
Return within 30 days of purchase. Duties & taxes are non-refundable.
Guaranteed Safe Checkout
Output Control Profile
Yokogawa F3YD08-6A is an 8-point transistor output module designed for industrial digital control applications. It uses sink-type outputs to switch compatible 12–24 V DC loads from a PLC control system.
Each output supports a maximum load current of 1 A, while the shared common group supports up to 4 A. These two limits must be evaluated together during load selection. The module uses photocoupler isolation and active-clamp surge protection to support reliable output switching within its specified operating conditions.
Both OFF-to-ON and ON-to-OFF response times are specified at 1 ms maximum. A 10-point terminal block with M3.5 screw connections provides the external wiring interface.
Electrical Design at a Glance
| Engineering Item | Specification | Selection Significance |
|---|---|---|
| Manufacturer | Yokogawa | Confirm the installed controller platform before ordering. |
| Model | F3YD08-6A | Verify the complete model and suffix. |
| Output Type | Transistor output, sink type | Field wiring must suit a sinking output arrangement. |
| Output Count | 8 points | Supports eight discrete output channels. |
| Rated Load Voltage | 12–24 V DC | Use compatible DC loads within the specified range. |
| Maximum Current per Point | 1 A | Check each load's steady-state and switching current. |
| Maximum Current per Common | 4 A | Calculate the combined current of outputs sharing the common. |
| Isolation | Photocoupler isolation | Provides electrical isolation between the signal interface and internal circuitry. |
| ON-State Voltage | 0.5 V DC maximum | Include output voltage drop when checking the load's operating voltage. |
| OFF-State Leakage Current | 0.1 mA maximum | Consider sensitive loads that may respond to small residual currents. |
| Switching Protection | Active clamp | Provides a specified surge-clamping function; check load requirements. |
| OFF-to-ON Response | 1 ms maximum | Relevant to output timing and sequence design. |
| ON-to-OFF Response | 1 ms maximum | Relevant to release timing and actuator control. |
| Module Current Consumption | 60 mA at 5 V DC | Include in the controller-side power budget. |
| External Power Supply | 12–24 V DC, 10 mA | Verify the specified external supply requirement. |
| External Connection | 10-point terminal block, M3.5 screws | Check terminal condition and wiring arrangement. |
| Weight | 130 g | Useful for replacement and inventory records. |
| Operating Temperature | 0 to 55°C | Keep the installation within the specified range. |
| Storage Temperature | −20 to 75°C | Apply during storage and logistics planning. |
| Operating Humidity | 10–90% RH, non-condensing | Prevent condensation during operation. |
| Storage Humidity | 10–90% RH, non-condensing | Maintain suitable storage conditions. |
| Atmosphere | Free from corrosive gases, flammable gases, and heavy dust | Protect the module and terminal connections from unsuitable environments. |
Load Engineering: Point Current vs. Common Current
Output selection requires two separate current checks. A load can meet the individual channel limit while the combined load on its common group exceeds the module rating.
| Check | Limit | Commissioning Action |
|---|---|---|
| Individual output | 1 A maximum per point | Measure or verify the load current for every channel. |
| Shared common | 4 A maximum per common | Calculate the combined current of the relevant outputs. |
| Load voltage | 12–24 V DC | Confirm supply voltage and load operating requirements. |
| ON-state voltage drop | 0.5 V DC maximum | Check the voltage available at the load when the output is ON. |
| OFF-state leakage | 0.1 mA maximum | Check whether the load is sensitive to residual current. |
Engineering example: Four loads drawing 0.8 A each would total 3.2 A if they share one common group. This is below the 4 A common limit, and each load is below the 1 A point limit. The actual installation must still meet all applicable load, wiring, thermal, and system requirements.
Important: Do not treat the 4 A common rating as a 4 A allowance for every channel. Also verify inrush current and the load manufacturer's switching requirements before connecting inductive or capacitive loads.
Output Behavior and CPU Error Handling
The module's CPU-error output behavior depends on the CPU type. The configuration should be checked before commissioning or replacing an existing module.
| CPU Type | Specified Behavior | Engineering Action |
|---|---|---|
| Sequence CPU | Initial value: RESET | Confirm the configured behavior matches the machine's control strategy. |
| BASIC CPU | No setting function; always set to HOLD | Account for this behavior in the application risk assessment. |
| OS-free CPU | Initial value: HOLD; configurable for each set of 8 points | Verify the selected state for the eight-point group. |
All module outputs can also be set collectively according to the specified configuration function. Do not assume that CPU error handling automatically places every output in a safe state. Confirm the actual behavior against the CPU type, program, machine risk assessment, and applicable Yokogawa documentation.
Where This Module Fits
- Solenoid valve control: Switch compatible DC solenoid loads when current, voltage, and surge requirements are satisfied.
- Relay interface circuits: Drive suitable DC relay coils or interface devices within the output ratings and wiring requirements.
- Machine sequence control: Control discrete outputs used in automated assembly, packaging, and material-handling equipment.
- Auxiliary equipment control: Switch eligible DC loads in industrial machinery and process support systems.
- PLC panel replacement: Replace a matching module after confirming CPU compatibility, terminal wiring, and output behavior.
These examples describe potential uses based on the module's electrical characteristics. They do not establish compatibility with a specific controller, actuator, or machine. Check the installed system documentation before selection.
Field Troubleshooting: Symptom-to-Test Guide
| Observed Symptom | Checks to Perform | Diagnostic Direction |
|---|---|---|
| Output command is ON, but the load does not operate. | Measure the DC supply, inspect terminal wiring, check load continuity, and verify output voltage under load. | Separate a supply or wiring issue from a channel or load fault. |
| Output turns ON but the actuator responds weakly. | Measure voltage at the load and check current draw and common-group loading. | Look for excessive voltage drop, overload, or an unsuitable load. |
| Several outputs stop working together. | Inspect the shared supply, common wiring, terminal tightness, and total common current. | Determine whether the fault affects a group rather than an individual point. |
| Load remains active after the command turns OFF. | Check the PLC output state, field wiring, load circuitry, and residual current sensitivity. | Distinguish a control logic issue from wiring or load behavior. |
| Output behavior changes after a CPU error. | Identify the CPU type and inspect the configured HOLD/RESET behavior. | Compare the observed state with the applicable CPU configuration. |
| Intermittent switching occurs. | Inspect terminal connections, supply stability, temperature, and load inrush characteristics. | Check for loose wiring, unstable power, excessive loading, or unsuitable operating conditions. |
Recommended diagnostic record: Document the channel number, commanded state, measured load voltage, current draw, common-group total, CPU type, and observed behavior during a controlled test. This information helps narrow the fault without immediately replacing the module.
Global PLC Spare HUB's Review
For maintenance teams, the F3YD08-6A should be evaluated as an output switching device rather than simply an eight-channel replacement. The key selection checks are sink-type wiring, 12–24 V DC load compatibility, individual current, common-group current, and CPU-error behavior.
During a field replacement, compare the original terminal arrangement and controller configuration before transferring wiring. If multiple channels fail simultaneously, investigate shared power and common connections first. If the problem appears only during CPU faults, confirm HOLD/RESET behavior before suspecting an output hardware defect.
This model is most appropriate when the existing system requires the specified eight-point transistor output arrangement and its electrical limits match the connected loads. A matching part number is essential, but controller and installation compatibility should still be verified.
Installation and Maintenance Notes
- Isolate the relevant power sources and follow the plant's approved electrical safety procedure before wiring or replacing the module.
- Verify the model suffix and the intended sink-type output wiring.
- Check terminal screws, wire condition, and common connections before energizing the circuit.
- Confirm that each load is within the 1 A per-point limit and each common group remains within 4 A.
- Check load voltage and account for the specified ON-state voltage drop.
- Review the CPU type and error-state configuration before functional testing.
- Test outputs under representative load conditions and record the results for future maintenance.
- Keep the installation within the specified temperature, humidity, and atmospheric conditions.
Frequently Asked Questions
Q1: How can I determine whether this output module is suitable for a DC solenoid valve?
A: Check the valve's rated voltage, steady-state current, inrush behavior, and inductive switching requirements. Confirm that the output's sink-type arrangement matches the wiring design. The 1 A channel rating alone does not prove suitability for every solenoid.
Q2: Why should the shared common current be calculated separately from channel current?
A: The module specifies both a 1 A maximum per output and a 4 A maximum per common. Several individually compliant loads can exceed the common limit when operated together. Calculate the worst-case simultaneous load for each group.
Q3: What information is needed to confirm replacement compatibility?
A: Provide the complete F3YD08-6A model number, the CPU model and type, the installed I/O platform, terminal wiring details, and the load voltage/current. These details help verify the hardware configuration and output behavior.
Q4: What should be investigated if the output stays active during a CPU fault?
A: First identify whether the system uses a Sequence CPU, BASIC CPU, or OS-free CPU. Then verify the documented HOLD/RESET behavior and configured output state. Do not assume that a CPU fault will always de-energize the connected load.
Q5: Can this module directly drive any 12–24 V DC load below 1 A?
A: Not necessarily. Confirm the load type, inrush current, inductive characteristics, OFF-state leakage sensitivity, wiring arrangement, and common-group loading. Use an appropriate interface where required by the load or system design.
Ordering, Warranty and Shipping
- Product: Yokogawa F3YD08-6A transistor output module, sink type, 8 points.
- Warranty: 12-month warranty, subject to the supplier's applicable warranty terms.
- Shipping methods: FedEx, UPS, and DHL, subject to destination and service availability.
- Before ordering: Confirm the full model code, quantity, controller platform, and load requirements.
- Packaging: Suitable protective packaging for transportation; confirm any special packaging requirements when requesting a quotation.
Request a Quote: Contact Global PLC Spare HUB for F3YD08-6A pricing, availability, shipping options, and assistance with replacement compatibility checks.
Tags
Q: Are these parts 100% original and new?
A: Yes. Every component is guaranteed to be 100% original, brand-new, and factory-sealed. We also provide a 12-month comprehensive warranty for your peace of mind.
Q: How fast is the shipping to my country?
A: For in-stock items, we offer same-day dispatch. International express shipping (DHL/FedEx/UPS) typically delivers within 3–5 business days worldwide.
Q: Can I get a formal quotation with shipping costs?
A: Absolutely. Our sales team is ready to provide a detailed Proforma Invoice (PI) including the most competitive shipping rates for your location.
Q: Do you offer discounts for bulk orders?
A: We provide volume-based pricing for large projects or multiple-item orders. Please contact us to get our Best Price Guarantee.
12-Month Comprehensive Warranty
Every part supplied by Global PLC Spare Hub is covered by a 12-month warranty from the date of invoice.
- Coverage: Functional defects and hardware failures under normal operating conditions.
- Commitment: We provide immediate repair, replacement, or a full refund for any verified defective components to minimize your operational downtime.
Returns & Exchange Policy
We offer a 30-day return policy to ensure you receive the exact part your system requires.
- Eligibility: Returns are accepted for uninstalled items in their original, factory-sealed packaging.
- RMA Process: Please contact our support team to obtain a Return Merchandise Authorization (RMA) number before shipping.
- Fast Processing: Refunds or exchanges are processed within 3–5 business days after the returned item passes our technical inspection.
Need Technical Assistance?Not sure if this part is compatible with your system? [Consult our Engineers] before purchasing to ensure 100% compatibility.



