Manufacturer: Allen-Bradley
Product No.: 1769-ASCII
Condition: In stock
Product Type: Communication Module
Product Origin: USA
Payment: T/T, Western Union
Weight: 150g
Shipping port: Xiamen
Warranty: 12 months
Estimate delivery times: 12-26 days (International), 3-6 days (United States).
Return within 30 days of purchase. Duties & taxes are non-refundable.
Guaranteed Safe Checkout
Product Overview
The Allen-Bradley 1769-ASCII is a two-channel ASCII communication module. It connects CompactLogix and MicroLogix 1500 controllers with serial ASCII devices.
The module supports barcode readers, serial instruments, scanners, and other ASCII-compatible equipment. It provides two independently configurable serial ports for data exchange.
Each port supports different communication settings. This allows the controller to communicate with separate serial devices simultaneously.
The module supports RS-232, RS-422, and RS-485 communication modes. Its isolated serial interfaces help separate field communication from the controller backplane.
The 1769-ASCII receives power directly from the 1769 system backplane. It does not require a separate external power supply.
Technical Specifications
| Brand | Allen-Bradley / Rockwell Automation |
| Model | 1769-ASCII |
| Product Series | CompactLogix 1769 |
| Product Type | Specialty Communication Module |
| Communication Function | ASCII Serial Communication |
| Number of Channels | 2 independent serial ports |
| Serial Connectors | 2 × DB-9 male connectors |
| Supported Interfaces | RS-232, RS-422, RS-485 |
| Communication Mode | Full-duplex and half-duplex |
| Hardware Handshaking | RTS/CTS enabled |
| Input Words | 108 |
| Configuration Words | 31 |
| Transaction ID | 0–255 |
| Backplane Power | 5 V DC |
| Backplane Current | 425 mA at 5 V DC |
| Maximum Power Dissipation | 2.13 W |
| Isolation Voltage | 30 V continuous |
| Power Supply Distance Rating | 4 modules |
| Operating Temperature | 0–60°C |
| Storage Temperature | -40–85°C |
| Relative Humidity | 5–95%, non-condensing |
| Operating Vibration | 5 g at 10–500 Hz |
| Operating Shock | 30 g |
| Non-Operating Shock | 50 g |
| Thermal Dissipation | 7.3 BTU/hr |
| Dimensions | 87 × 34 × 118 mm |
| Weight | Approximately 0.18 kg |
| Series Revision | Series A and B |
| UPC / GTIN | 10612598314239 |
Technical Note: The supplied specifications contain conflicting power and current values. The 425 mA at 5 V DC rating corresponds to approximately 2.13 W. The 7.5 W and 33.6 W figures require verification against the applicable hardware documentation. Confirm electrical ratings before system design.
Communication Features and Performance
- Dual Serial Channels: Each port supports independent communication configuration.
- Protocol Support: The module exchanges data through ASCII-based serial protocols.
- Interface Selection: RS-232, RS-422, and RS-485 support different field wiring requirements.
- Hardware Handshaking: RTS/CTS controls serial data transmission between compatible devices.
- Transaction Identification: Transaction IDs range from 0 to 255.
- Diagnostic Monitoring: Status information identifies transmission and reception problems.
Serial Input Signal Levels:
- Logic 0: +3 to +25 V DC relative to signal ground.
- Logic 1: -3 to -25 V DC relative to signal ground.
Diagnostic Status Information:
- TX FIFO overflow
- RX FIFO overflow
- RX parity error
- Handshake error
- New data flag
These indicators help engineers identify communication errors during commissioning and troubleshooting.
Performance Specification Note: The module provides serial data communication. Measurement range, sensor sensitivity, linearity, and measurement resolution do not apply. Baud rate and detailed timing limits require confirmation from the applicable Rockwell Automation documentation.
Installation Guide
The 1769-ASCII mounts directly onto a compatible Compact I/O assembly. It supports DIN rail and panel mounting arrangements.
- Disconnect system power before installation.
- Verify the controller and chassis compatibility.
- Check the available backplane power capacity.
- Install the module within four module positions of the power supply.
- Secure the module to the DIN rail or mounting panel.
- Connect serial devices through the DB-9 connectors.
- Use suitable shielded communication cable, such as Belden 8761 where applicable.
- Check the communication interface and wiring configuration.
- Restore power and verify module operation.
Wiring Considerations:
- Use the correct RS-232, RS-422, or RS-485 wiring arrangement.
- Check signal polarity and signal ground connections.
- Separate serial communication cables from high-voltage power cables.
- Ground cable shields according to the system grounding design.
- Verify RTS/CTS wiring when hardware handshaking is enabled.
Do not assume identical pin assignments across different serial interfaces. Follow the device-specific wiring diagrams.
Environmental and Electrical Considerations
The module operates within specified industrial environmental conditions. Proper installation helps maintain reliable serial communication.
- Operating temperature: 0–60°C.
- Storage temperature: -40–85°C.
- Relative humidity: 5–95%, non-condensing.
- Operating vibration: 5 g at 10–500 Hz.
- Operating shock: 30 g.
- Non-operating shock: 50 g.
Keep the module within its specified operating conditions. Avoid condensation, excessive vibration, and unstable backplane connections.
Certifications and Compliance
The supplied product information does not identify specific certification numbers or approval marks. Please confirm applicable certifications through the product nameplate and official Rockwell Automation documentation.
For projects requiring UL, CE, hazardous-location, or other regulatory approvals, verify the exact catalog number and applicable revision before purchase.
Package Contents
- 1 × Allen-Bradley 1769-ASCII ASCII Communication Module.
- Standard product packaging.
Additional cables, controllers, power supplies, and configuration software are not included unless specified in the order.
Frequently Asked Questions (FAQ)
Q1: What is the primary function of the Allen-Bradley 1769-ASCII?
The 1769-ASCII connects CompactLogix and MicroLogix 1500 controllers with ASCII-compatible serial equipment. Common applications include barcode scanning and serial data acquisition.
Q2: Can both serial ports communicate with different devices simultaneously?
Yes. The module provides two independently configurable communication channels. Each port can exchange data with a separate serial device.
Q3: Does the 1769-ASCII require an external power supply?
No. The module receives operating power from the 1769 backplane. Engineers must verify the available power budget before installation.
Q4: What should engineers check when a barcode reader cannot communicate?
Start with the physical interface and wiring. Then verify baud rate, parity, data bits, and handshake settings. Check the module status information for parity errors and FIFO overflow.
Q5: Can the 1769-ASCII replace a standard Ethernet communication module?
No. The 1769-ASCII provides serial ASCII communication. It does not provide an Ethernet interface or native Ethernet protocol communication.
Q6: What is the difference between RS-232, RS-422, and RS-485?
RS-232 typically connects point-to-point devices. RS-422 supports differential signaling over longer cable distances. RS-485 supports differential multi-device communication. Select the interface according to the field device requirements.
Q7: What should buyers verify before ordering a 1769-ASCII?
Confirm the controller platform, module revision, serial interface, channel requirements, and backplane power capacity. Also check the required cable and connector arrangement. Provide your existing module label for compatibility verification.
Q8: Can a Series A module replace a Series B module?
Do not assume direct interchangeability. Check the hardware revision, controller firmware, and project configuration requirements. Confirm the replacement arrangement before installation.
Q9: What information helps diagnose intermittent serial communication?
Record the connected device model, serial settings, cable length, and error status. Check whether the problem affects one channel or both channels. This information helps identify wiring, configuration, or module-related faults.
Q10: What should I provide when requesting a replacement module?
Provide the complete catalog number, series, existing module photograph, and controller model. Include the connected serial device and required communication interface. These details help reduce ordering errors. application.
Tags
Q: Are these parts 100% original and new?
A: Yes. Every component is guaranteed to be 100% original, brand-new, and factory-sealed. We also provide a 12-month comprehensive warranty for your peace of mind.
Q: How fast is the shipping to my country?
A: For in-stock items, we offer same-day dispatch. International express shipping (DHL/FedEx/UPS) typically delivers within 3–5 business days worldwide.
Q: Can I get a formal quotation with shipping costs?
A: Absolutely. Our sales team is ready to provide a detailed Proforma Invoice (PI) including the most competitive shipping rates for your location.
Q: Do you offer discounts for bulk orders?
A: We provide volume-based pricing for large projects or multiple-item orders. Please contact us to get our Best Price Guarantee.
12-Month Comprehensive Warranty
Every part supplied by Global PLC Spare Hub is covered by a 12-month warranty from the date of invoice.
- Coverage: Functional defects and hardware failures under normal operating conditions.
- Commitment: We provide immediate repair, replacement, or a full refund for any verified defective components to minimize your operational downtime.
Returns & Exchange Policy
We offer a 30-day return policy to ensure you receive the exact part your system requires.
- Eligibility: Returns are accepted for uninstalled items in their original, factory-sealed packaging.
- RMA Process: Please contact our support team to obtain a Return Merchandise Authorization (RMA) number before shipping.
- Fast Processing: Refunds or exchanges are processed within 3–5 business days after the returned item passes our technical inspection.