Home 140DAI35300 Schneider Electric Quantum 24V AC Module
140DAI35300 Schneider Electric Quantum 24V AC Module
140DAI35300 Schneider Electric Quantum 24V AC Module
140DAI35300 Schneider Electric Quantum 24V AC Module
140DAI35300 Schneider Electric Quantum 24V AC Module
140DAI35300 Schneider Electric Quantum 24V AC Module
140DAI35300 Schneider Electric Quantum 24V AC Module

140DAI35300 Schneider Electric Quantum 24V AC Module

  • Manufacturer: Schneider Electric

  • Product No.: 140DAI35300

  • Condition: In stock

  • Product Type: AC Input Module

  • Product Origin: DE

  • Payment: T/T, Western Union

  • Weight: 300g

  • Shipping port: Xiamen

  • Warranty: 12 months

Selected quantity: 1
Request a quote

Estimate delivery times: 12-26 days (International), 3-6 days (United States).

Return within 30 days of purchase. Duties & taxes are non-refundable.

Guaranteed Safe Checkout

Visa
PayPal
Mastercard
American Express

Product Overview

The Schneider Electric Modicon Quantum 140DAI35300 module captures 32 discrete 24 V AC field inputs.

Process control systems rely on this high-density card for continuous signal monitoring.

The hardware divides input signals into four isolated channels of eight points each.

Internal filters isolate sensitive backplane electronics from harsh alternating current transients.

Technical Specifications

System Parameter Category Specification Attribute Technical Value
Identity & Architecture Brand & Series Schneider Electric Modicon Quantum
Identity & Architecture Model Number 140DAI35300
Identity & Architecture Format & Weight Standard Quantum Slot / 0.75 lb (0.34 kg)
Input Voltage & Logic Channel Count & Type 32 Discrete VAC Inputs (4 Isolated Groups of 8)
Input Voltage & Logic Nominal Operating Voltage 24 V AC Discrete Logic
Input Voltage & Logic Network Frequency Limits 47 Hz to 63 Hz Line Frequency
Voltage Thresholds (57-63 Hz) State 1 Guaranteed / State 0 Guaranteed 12 to 30 V AC / 0 to 5 V AC
Voltage Thresholds (47-53 Hz) State 1 Guaranteed / State 0 Guaranteed 14 to 30 V AC / 0 to 5 V AC
Current & Impedance Limits Input Current Load 11.1 mA (57-63 Hz) / 13.2 mA (47-53 Hz)
Current & Impedance Limits Input Impedance & Leakage 2600 Ohm (60 Hz) / 3100 Ohm (50 Hz) / 1.9 mA max leakage
Current & Impedance Limits Absolute Maximum Input Voltage 30 V continuous / 32 V for 10 s / 50 V for 1 cycle
Signal Dynamics & Power Response Time (Off-to-On / On-to-Off) 4.9 to 0.75 ms x line cycle / 7.3 to 12.3 ms
Signal Dynamics & Power Addressing & Bus Requirements 2 Input Words (32 bits) / 250 mA Backplane Bus Current
Signal Dynamics & Power Maximum Power Dissipation 10.9 W maximum operational thermal output
Protection & Isolation Dielectric Isolation Limits 1780 Vrms for 1 min (Group-to-Group & Group-to-Bus)
Environmental Tolerance Operating & Storage Temperature 32°F to 140°F (0°C to 60°C) / -40°F to 185°F (-40°C to 85°C)
Environmental Tolerance ESD & Field Noise Resistance 4 kV contact / 8 kV air ESD / 10 V/m (80-2000 MHz)

Installation Guide

  • Power down the Quantum backplane before inserting or removing any I/O card.
  • Align the module housing precisely along the rack guide rails during installation.
  • Wire 24 V AC field signals using proper wire gauges to minimize line voltage drops.
  • Ground the cabinet shield lines securely to eliminate AC line noise coupling.

Commissioning & Maintenance

Task Phase Operational Action
Pre-Power Check Verify field AC voltage levels stay within the 12 to 30 V AC window.
Logic Verification Monitor real-time input status using the front-panel status LEDs.
Diagnostic Audit Check the active bus communications LED for steady green light illumination.
Routine Maintenance Inspect terminal screw tightness annually to prevent high-resistance contacts.

System Compatibility & Software Support

  • Integrates directly into standard Schneider Electric Modicon Quantum backplane racks.
  • Supports logic configuration within EcoStruxure Control Expert (Unity Pro) software suites.
  • Maintains full compatibility with legacy Concept programming tools.
  • Configures seamlessly within ProWORX 32 industrial programming environments.

Certifications & Compliance

Agency / Standard Compliance Standard Details
UL Certification UL 508 Standard for Industrial Control Equipment
CSA Certification CSA C22.2 No 142 Process Control Equipment
Hazardous Location FM Class 1 Division 2 Non-Incendive Rating
Global Standards CE Marked & cUL Listed for International Safety

Suitable Equipment & Typical Applications

  • Monitoring limit switches on industrial AC motor control centers (MCC).
  • Sensing field contact states on legacy 24 V AC safety interlock circuits.
  • Processing discrete push-button signals in municipal water treatment pump stations.
  • Reading auxiliary contact status from heavy-duty power circuit breakers.

Diagnostic Capabilities & Indication

  • A dedicated green LED signals active bus communication status across the backplane.
  • A prominent red LED alerts operators to external fault conditions immediately.
  • 32 individual green LEDs provide direct visual verification for each AC input channel.
  • Internal diagnostics flag loss of field power or line frequency instability to the CPU.

Package Contents, Logistics & Warranty

Logistics Parameter Service Specification Details
Package Dimensions 12.28 in x 1.77 in x 6.42 in (31.2 cm x 4.5 cm x 16.3 cm)
Package Mass 16.8 oz (475.0 g) packaged shipping weight
Warranty Coverage 12 Months comprehensive replacement warranty term
Dispatch Handling Express order processing within 24 to 48 hours
Global Courier Express Worldwide door-to-door delivery via FedEx, UPS, and DHL

Global PLC Spare HUB's Insight

Our field team recently troubleshot an AC input flickering issue at a municipal wastewater facility.

Long cable runs caused capacitive coupling, holding 24 V AC lines near 8 V AC during off states.

Because the Modicon Quantum 140DAI35300 guarantees a state 0 off threshold between 0 and 5 V AC, phantom voltage triggered false inputs.

Engineers installed loading resistors across the field terminals to drain the stray capacitive charge.

The 140DAI35300 module immediately resumed stable, highly accurate signal detection across all 32 channels.

Frequently Asked Questions

Question: How does line frequency affect the voltage thresholds of the 140DAI35300 card?

Answer: At 60 Hz, guaranteed state 1 requires 12 to 30 V AC. At 50 Hz, it requires 14 to 30 V AC.

Question: What happens if induced cable voltage exceeds 5 V AC on an open input point?

Answer: The channel may read a false active state. Install external loading resistors to bleed off capacitive stray voltage.

Question: How many words does the PLC processor allocate for this 32-point AC card?

Answer: The controller reserves two 16-bit input data words to read all 32 discrete AC points.

Question: What key factors should buyers verify before purchasing a 140DAI35300 replacement module?

Answer: Confirm your field power supply matches 24 V AC rather than 24 V DC or 115 V AC levels.

Question: Why does the 140DAI35300 dissipate up to 10.9 Watts of power during operation?

Answer: Internal capacitive input circuitry generates heat while filtering alternating current line fluctuations across 32 active points.

Tags

Q: Are these parts 100% original and new?

A: Yes. Every component is guaranteed to be 100% original, brand-new, and factory-sealed. We also provide a 12-month comprehensive warranty for your peace of mind.

Q: How fast is the shipping to my country?

A: For in-stock items, we offer same-day dispatch. International express shipping (DHL/FedEx/UPS) typically delivers within 3–5 business days worldwide.

Q: Can I get a formal quotation with shipping costs?

A: Absolutely. Our sales team is ready to provide a detailed Proforma Invoice (PI) including the most competitive shipping rates for your location.

Q: Do you offer discounts for bulk orders?

A: We provide volume-based pricing for large projects or multiple-item orders. Please contact us to get our Best Price Guarantee.




12-Month Comprehensive Warranty

Every part supplied by Global PLC Spare Hub is covered by a 12-month warranty from the date of invoice.

  • Coverage: Functional defects and hardware failures under normal operating conditions.
  • Commitment: We provide immediate repair, replacement, or a full refund for any verified defective components to minimize your operational downtime.

Returns & Exchange Policy

We offer a 30-day return policy to ensure you receive the exact part your system requires.

  • Eligibility: Returns are accepted for uninstalled items in their original, factory-sealed packaging.
  • RMA Process: Please contact our support team to obtain a Return Merchandise Authorization (RMA) number before shipping.
  • Fast Processing: Refunds or exchanges are processed within 3–5 business days after the returned item passes our technical inspection.

Need Technical Assistance?Not sure if this part is compatible with your system? [Consult our Engineers] before purchasing to ensure 100% compatibility.