{"product_id":"sm811k01-3bse018173r1-abb-safety-cpu-module-sil-safety-control","title":"SM811K01 3BSE018173R1 ABB Safety CPU Module – SIL Safety Control","description":"\u003ch3\u003e\u003cstrong\u003eABB 3BSE018173R1 – SM811K01 Safety CPU Module\u003c\/strong\u003e\u003c\/h3\u003e\n\u003cp\u003eThe \u003cstrong\u003e\u003cspan style=\"color: #0084cc;\"\u003eABB 3BSE018173R1\u003c\/span\u003e\u003c\/strong\u003e is an \u003cstrong\u003e\u003cspan style=\"color: #0084cc;\"\u003eSM811K01 Safety CPU Module\u003c\/span\u003e\u003c\/strong\u003e designed to collaborate with the PM865 controller in ABB safety systems. It supervises PM865 operation during SIL 1 and SIL 2 applications. Together, the SM811 and PM865 form a 1oo2 diverse architecture for SIL 3 applications.\u003c\/p\u003e\n\u003cp\u003eThe module connects to the CEX bus through a BC810 CEX bus interconnection box. Its MPC862P processor operates at 96 MHz and uses 32 MB of SDRAM. The hardware also supports redundant configurations, hot swapping, internal voltage monitoring, and overvoltage protection.\u003c\/p\u003e\n\u003cp\u003eFor redundant operation, the SM811 uses an SM Link synchronization connection. The supplied TK852V10 synchronization cable connects the corresponding SM Link interfaces. Status indicators help engineers verify module operation, fault conditions, primary assignment, and synchronization progress.\u003c\/p\u003e\n\u003ch3\u003e\u003cstrong\u003e01 | System Architecture \u0026amp; Processing\u003c\/strong\u003e\u003c\/h3\u003e\n\u003cul\u003e\n\u003cli\u003e\n\u003cstrong\u003eManufacturer:\u003c\/strong\u003e ABB\u003c\/li\u003e\n\u003cli\u003e\n\u003cstrong\u003eModel:\u003c\/strong\u003e \u003cstrong\u003e\u003cspan style=\"color: #0084cc;\"\u003e3BSE018173R1\u003c\/span\u003e\u003c\/strong\u003e\n\u003c\/li\u003e\n\u003cli\u003e\n\u003cstrong\u003eModule designation:\u003c\/strong\u003e SM811K01 Safety CPU Module\u003c\/li\u003e\n\u003cli\u003e\n\u003cstrong\u003eProduct function:\u003c\/strong\u003e Collaborating safety CPU\u003c\/li\u003e\n\u003cli\u003e\n\u003cstrong\u003eController collaboration:\u003c\/strong\u003e PM865\u003c\/li\u003e\n\u003cli\u003e\n\u003cstrong\u003eProcessor:\u003c\/strong\u003e MPC862P, 96 MHz\u003c\/li\u003e\n\u003cli\u003e\n\u003cstrong\u003eSDRAM:\u003c\/strong\u003e 32 MB\u003c\/li\u003e\n\u003cli\u003e\n\u003cstrong\u003eFlash PROM:\u003c\/strong\u003e 4 MB for firmware storage\u003c\/li\u003e\n\u003cli\u003e\n\u003cstrong\u003eSafety architecture:\u003c\/strong\u003e Supports PM865 supervision for SIL 1–2 and a 1oo2 diverse architecture for SIL 3\u003c\/li\u003e\n\u003cli\u003e\n\u003cstrong\u003eBus connection:\u003c\/strong\u003e CEX bus through BC810\u003c\/li\u003e\n\u003cli\u003e\n\u003cstrong\u003eRedundancy interface:\u003c\/strong\u003e SM Link\u003c\/li\u003e\n\u003cli\u003e\n\u003cstrong\u003eHardware functions:\u003c\/strong\u003e Hot swap, redundancy support, internal voltage monitoring, and overvoltage protection\u003c\/li\u003e\n\u003c\/ul\u003e\n\u003ch3\u003e\u003cstrong\u003e02 | Electrical \u0026amp; Interface Characteristics\u003c\/strong\u003e\u003c\/h3\u003e\n\u003cp\u003e\u003cstrong\u003eCEX-Bus Power Consumption\u003c\/strong\u003e\u003c\/p\u003e\n\u003cul\u003e\n\u003cli\u003eNominal voltage: 24 V DC\u003c\/li\u003e\n\u003cli\u003eTypical current consumption: 160 mA\u003c\/li\u003e\n\u003cli\u003eMaximum current consumption: 250 mA\u003c\/li\u003e\n\u003cli\u003eTypical power dissipation: 3.8 W\u003c\/li\u003e\n\u003c\/ul\u003e\n\u003cp\u003e\u003cstrong\u003eConnector Configuration\u003c\/strong\u003e\u003c\/p\u003e\n\u003cul\u003e\n\u003cli\u003eOne 7-pin screw connector\u003c\/li\u003e\n\u003cli\u003eOne RJ45 connector for SM Link\u003c\/li\u003e\n\u003c\/ul\u003e\n\u003cp\u003e\u003cstrong\u003eElectrical Input Characteristics\u003c\/strong\u003e\u003c\/p\u003e\n\u003cul\u003e\n\u003cli\u003eNominal voltage: 24 V\u003c\/li\u003e\n\u003cli\u003eLogic 0 voltage: -30 V \u0026lt; UL \u0026lt; 5 V\u003c\/li\u003e\n\u003cli\u003eLogic 1 voltage: 15 V \u0026lt; UH \u0026lt; 30 V\u003c\/li\u003e\n\u003cli\u003eNominal current: 12 mA\u003c\/li\u003e\n\u003cli\u003eInput impedance: 1.8 kΩ\u003c\/li\u003e\n\u003cli\u003eGalvanic isolation: Yes\u003c\/li\u003e\n\u003c\/ul\u003e\n\u003cp\u003e\u003cstrong\u003eElectrical Output Characteristics\u003c\/strong\u003e\u003c\/p\u003e\n\u003cul\u003e\n\u003cli\u003eNominal voltage: 24 V\u003c\/li\u003e\n\u003cli\u003eProcess voltage range: 12–32 V\u003c\/li\u003e\n\u003cli\u003eOn-state output voltage: UP - 0.5 V \u0026lt; UA \u0026lt; UP\u003c\/li\u003e\n\u003cli\u003eMaximum continuous load current: 0.5 A\u003c\/li\u003e\n\u003cli\u003eOff-state output leakage current: \u0026lt; 10 mA\u003c\/li\u003e\n\u003cli\u003eMaximum short-circuit current: \u0026lt; 2.4 mA\u003c\/li\u003e\n\u003cli\u003eOutput impedance: \u0026lt; 0.4 Ω\u003c\/li\u003e\n\u003cli\u003eGalvanic isolation: Yes\u003c\/li\u003e\n\u003c\/ul\u003e\n\u003cp\u003e\u003cstrong\u003eInsulation \u0026amp; Electrical Ratings\u003c\/strong\u003e\u003c\/p\u003e\n\u003cul\u003e\n\u003cli\u003eOvervoltage category: II\u003c\/li\u003e\n\u003cli\u003eRated insulation voltage: 50 V\u003c\/li\u003e\n\u003cli\u003eInsulation test voltage: 500 V AC for 1 minute\u003c\/li\u003e\n\u003c\/ul\u003e\n\u003ch3\u003e\u003cstrong\u003e03 | Status Indicators \u0026amp; Diagnostic Interpretation\u003c\/strong\u003e\u003c\/h3\u003e\n\u003cp\u003eThe front-panel LEDs provide operating information during commissioning and maintenance. Engineers can use these indications to distinguish controller operation, hardware faults, and synchronization states.\u003c\/p\u003e\n\u003cul\u003e\n\u003cli\u003e\n\u003cstrong\u003eF (Fault) \/ Red:\u003c\/strong\u003e Indicates a detected unit error. Control software manages the indication, while hardware sets and clears the state during controller reset.\u003c\/li\u003e\n\u003cli\u003e\n\u003cstrong\u003eR (Run) \/ Green:\u003c\/strong\u003e Indicates operational status. Control software controls the indication, and hardware clears it during controller reset.\u003c\/li\u003e\n\u003cli\u003e\n\u003cstrong\u003eAccess EN (Enabled) \/ Yellow:\u003c\/strong\u003e Indicates that the Access Enable switch is active.\u003c\/li\u003e\n\u003cli\u003e\n\u003cstrong\u003eDEGR (Degraded Mode) \/ Yellow:\u003c\/strong\u003e Reserved for future use.\u003c\/li\u003e\n\u003cli\u003e\n\u003cstrong\u003ePRIM \/ Yellow:\u003c\/strong\u003e Identifies the SM811 assigned as the primary unit.\u003c\/li\u003e\n\u003cli\u003e\n\u003cstrong\u003eSYNC (Synchronized) \/ Yellow:\u003c\/strong\u003e Indicates synchronization status. The LED flashes during the synchronization process and remains yellow when synchronization completes.\u003c\/li\u003e\n\u003c\/ul\u003e\n\u003ch3\u003e\u003cstrong\u003e04 | Redundant Pair Synchronization\u003c\/strong\u003e\u003c\/h3\u003e\n\u003cp\u003eSM811 synchronization requires the correct SM Link connection and a defined activation sequence. Follow the equipment-specific engineering procedure and verify the controller state before starting.\u003c\/p\u003e\n\u003col\u003e\n\u003cli\u003e\n\u003cstrong\u003eCheck the synchronization cable:\u003c\/strong\u003e Confirm that the TK852V10 cable connects the SM Link ports of both SM811 modules.\u003c\/li\u003e\n\u003cli\u003e\n\u003cstrong\u003eInsert the module:\u003c\/strong\u003e Install the SM811 in its designated position in accordance with the system procedure.\u003c\/li\u003e\n\u003cli\u003e\n\u003cstrong\u003eObserve the SYNC LED:\u003c\/strong\u003e The LED flashes during startup and then follows a repeating three-flash-and-pause pattern.\u003c\/li\u003e\n\u003cli\u003e\n\u003cstrong\u003eTrigger synchronization:\u003c\/strong\u003e Press the designated button to create an edge on digital input 3 of the running Safety Module.\u003c\/li\u003e\n\u003cli\u003e\n\u003cstrong\u003eMonitor synchronization:\u003c\/strong\u003e The SYNC LED flashes faster while the synchronization process proceeds.\u003c\/li\u003e\n\u003cli\u003e\n\u003cstrong\u003eVerify completion:\u003c\/strong\u003e The SYNC LED turns steady yellow when synchronization is complete.\u003c\/li\u003e\n\u003c\/ol\u003e\n\u003cp\u003e\u003cstrong\u003eEngineering note:\u003c\/strong\u003e Do not treat the initial flashing sequence as proof of completed synchronization. Confirm the final LED state and verify the redundant pair through the applicable system diagnostics before returning the system to service.\u003c\/p\u003e\n\u003ch3\u003e\u003cstrong\u003e05 | Installation \u0026amp; Maintenance Considerations\u003c\/strong\u003e\u003c\/h3\u003e\n\u003cul\u003e\n\u003cli\u003e\n\u003cstrong\u003eCEX bus topology:\u003c\/strong\u003e Check the BC810 interconnection arrangement and confirm that the module occupies the intended bus position.\u003c\/li\u003e\n\u003cli\u003e\n\u003cstrong\u003ePower verification:\u003c\/strong\u003e Measure the 24 V DC supply and check that the CEX-Bus current capacity supports the installed configuration.\u003c\/li\u003e\n\u003cli\u003e\n\u003cstrong\u003eRedundancy checks:\u003c\/strong\u003e Inspect the SM Link cable and connector seating before initiating synchronization.\u003c\/li\u003e\n\u003cli\u003e\n\u003cstrong\u003eModule replacement:\u003c\/strong\u003e Although the hardware supports hot swap, follow the approved system procedure and application-specific safety requirements before removing or inserting a module.\u003c\/li\u003e\n\u003cli\u003e\n\u003cstrong\u003eLED diagnostics:\u003c\/strong\u003e Record Fault, Run, Primary, and Sync indications when investigating controller or redundancy issues.\u003c\/li\u003e\n\u003cli\u003e\n\u003cstrong\u003ePost-maintenance validation:\u003c\/strong\u003e Confirm controller supervision, redundant-pair status, and the expected safety-system operating state before handover.\u003c\/li\u003e\n\u003c\/ul\u003e\n\u003ch3\u003e\u003cstrong\u003e06 | Mechanical Data\u003c\/strong\u003e\u003c\/h3\u003e\n\u003cul\u003e\n\u003cli\u003eProduct net depth: 127.5 mm\u003c\/li\u003e\n\u003cli\u003eProduct net height: 185 mm\u003c\/li\u003e\n\u003cli\u003eProduct net width: 59 mm\u003c\/li\u003e\n\u003cli\u003eProduct net weight: 0.6 kg\u003c\/li\u003e\n\u003c\/ul\u003e\n\u003cp\u003e\u003cimg src=\"https:\/\/cdn.shopify.com\/s\/files\/1\/0722\/7863\/8774\/files\/SM811K01.png?v=1795161735\" alt=\"\"\u003e\u003c\/p\u003e","brand":"ABB","offers":[{"title":"Default Title","offer_id":68112686416054,"sku":"SM811K01","price":236.0,"currency_code":"USD","in_stock":true}],"thumbnail_url":"\/\/cdn.shopify.com\/s\/files\/1\/0722\/7863\/8774\/files\/SM811K01-1.jpg?v=1795161735","url":"https:\/\/www.plcsparehub.com\/products\/sm811k01-3bse018173r1-abb-safety-cpu-module-sil-safety-control","provider":"Global PLC Spare Hub","version":"1.0","type":"link"}