{"product_id":"imdsi13-abb-infi-90-digital-slave-input-module-16-ch-24vdc","title":"IMDSI13 ABB INFI 90 Digital Slave Input Module | 16-Ch 24VDC","description":"\u003ch3\u003e\u003cstrong\u003eControl Architecture \u0026amp; Functional Role\u003c\/strong\u003e\u003c\/h3\u003e\n\u003cp\u003eThe \u003cstrong style=\"color: #0056b3;\"\u003eABB IMDSI13\u003c\/strong\u003e is a 16-channel digital slave input module built for distributed control racks within the \u003cstrong style=\"color: #0056b3;\"\u003eBailey Net 90\u003c\/strong\u003e, \u003cstrong style=\"color: #0056b3;\"\u003eINFI 90\u003c\/strong\u003e, and \u003cstrong style=\"color: #0056b3;\"\u003eHarmony\u003c\/strong\u003e automation architectures. Interfacing directly via the I\/O expander bus, the \u003cstrong style=\"color: #0056b3;\"\u003eIMDSI13\u003c\/strong\u003e acquires passive field contact states and transfers discrete process telemetry to host Multi-Function Processors (MFP) or Logic Master Modules (LMM). Engineered with fixed hardware input conditioning and zero onboard jumper configuration, it streamlines panel commissioning while providing a direct 24 VDC functional replacement path for legacy \u003cstrong style=\"color: #0056b3;\"\u003eIMDSI02\u003c\/strong\u003e assemblies.\u003c\/p\u003e\n\u003ch3\u003e\u003cstrong\u003eElectrical \u0026amp; Environmental Specification Matrix\u003c\/strong\u003e\u003c\/h3\u003e\n\u003ctable\u003e\n\u003cthead\u003e\n\u003ctr\u003e\n\u003cth\u003e\u003cstrong\u003eEngineering Parameter\u003c\/strong\u003e\u003c\/th\u003e\n\u003cth\u003e\u003cstrong\u003eTechnical Specification\u003c\/strong\u003e\u003c\/th\u003e\n\u003c\/tr\u003e\n\u003c\/thead\u003e\n\u003ctbody\u003e\n\u003ctr\u003e\n\u003ctd\u003e\u003cstrong\u003eManufacturer \u0026amp; Series\u003c\/strong\u003e\u003c\/td\u003e\n\u003ctd\u003e\n\u003cstrong style=\"color: #0056b3;\"\u003eABB\u003c\/strong\u003e — \u003cstrong style=\"color: #0056b3;\"\u003eBailey Net 90 \/ INFI 90 \/ Harmony Rack\u003c\/strong\u003e\n\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003e\u003cstrong\u003eModule Designation\u003c\/strong\u003e\u003c\/td\u003e\n\u003ctd\u003e\n\u003cstrong style=\"color: #0056b3;\"\u003eIMDSI13\u003c\/strong\u003e (Digital Slave Input Module)\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003e\u003cstrong\u003eChannel Density \u0026amp; Bus Interface\u003c\/strong\u003e\u003c\/td\u003e\n\u003ctd\u003e16 independent discrete input channels; polled via I\/O Expander Bus (MFP \/ LMM)\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003e\u003cstrong\u003eNominal Input Rating\u003c\/strong\u003e\u003c\/td\u003e\n\u003ctd\u003e24 VDC (+10% tolerance) at 5.5 mA nominal loop current\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003e\u003cstrong\u003eSwitching Thresholds\u003c\/strong\u003e\u003c\/td\u003e\n\u003ctd\u003eTurn-on (min): 16.8 VDC | Turn-off (max): 13.0 VDC\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003e\u003cstrong\u003eThreshold \u0026amp; Leakage Limits\u003c\/strong\u003e\u003c\/td\u003e\n\u003ctd\u003eMin turn-on current: 4 mA at 14.7 VDC | Max off-leakage: 7 μA (Vin ≤ 12 VDC)\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003e\u003cstrong\u003eInput Conditioning \u0026amp; Overvoltage\u003c\/strong\u003e\u003c\/td\u003e\n\u003ctd\u003eFixed factory debounce (no user jumpers); Overvoltage Category II (IEC 1010-1)\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003e\u003cstrong\u003eBackplane Power Draw\u003c\/strong\u003e\u003c\/td\u003e\n\u003ctd\u003e95 mA typical at 5 VDC; 115 mA maximum\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003e\u003cstrong\u003eRack Form Factor\u003c\/strong\u003e\u003c\/td\u003e\n\u003ctd\u003eOccupies 1 standard slot in an INFI 90 OPEN Module Mounting Unit (IEMMU)\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003e\u003cstrong\u003eOperating Temperature Window\u003c\/strong\u003e\u003c\/td\u003e\n\u003ctd\u003e0°C to 70°C (32°F to 158°F) internal cabinet rating (IEC 68-2-1, 2, 14)\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003e\u003cstrong\u003eRelative Humidity \u0026amp; Altitude\u003c\/strong\u003e\u003c\/td\u003e\n\u003ctd\u003e5%–95% up to 55°C; 5%–45% at 70°C (noncondensing); Sea level to 3 km\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003e\u003cstrong\u003eAir Quality \u0026amp; Pollution Rating\u003c\/strong\u003e\u003c\/td\u003e\n\u003ctd\u003eISA S71.04 Class LA, LB, LC Level 1 (noncorrosive); Pollution Degree 1\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003c\/tbody\u003e\n\u003c\/table\u003e\n\u003ch3\u003e\u003cstrong\u003eRack Installation \u0026amp; Field Commissioning\u003c\/strong\u003e\u003c\/h3\u003e\n\u003col\u003e\n\u003cli\u003e\n\u003cstrong\u003eVerify Backplane Power Capacity:\u003c\/strong\u003e Confirm the \u003cstrong style=\"color: #0056b3;\"\u003eIEMMU\u003c\/strong\u003e 5 VDC power supply accommodates the 115 mA maximum draw per \u003cstrong style=\"color: #0056b3;\"\u003eIMDSI13\u003c\/strong\u003e card.\u003c\/li\u003e\n\u003cli\u003e\n\u003cstrong\u003eInspect Slot Dipswitches:\u003c\/strong\u003e Set slave module address dipswitches prior to insertion, noting that the board contains no physical debounce jumpers.\u003c\/li\u003e\n\u003cli\u003e\n\u003cstrong\u003eSeat Module into IEMMU:\u003c\/strong\u003e Align the PCB edges with the designated \u003cstrong style=\"color: #0056b3;\"\u003eINFI 90 OPEN\u003c\/strong\u003e card guides and lock the front faceplate latches firmly.\u003c\/li\u003e\n\u003cli\u003e\n\u003cstrong\u003eVerify Field Termination:\u003c\/strong\u003e Confirm 24 VDC field wetting voltage across the associated termination unit (TU) and validate logic states inside the host MFP\/LMM database.\u003c\/li\u003e\n\u003c\/ol\u003e\n\u003ch3\u003e\u003cstrong\u003eField Diagnostics \u0026amp; Maintenance Insights\u003c\/strong\u003e\u003c\/h3\u003e\n\u003cul\u003e\n\u003cli\u003e\n\u003cstrong\u003eLeakage Current Immunity:\u003c\/strong\u003e The 7 μA maximum off-state leakage tolerance prevents false logic-high triggers from two-wire proximity switches or long parallel cable runs.\u003c\/li\u003e\n\u003cli\u003e\n\u003cstrong\u003eZero-Jumper Reliability:\u003c\/strong\u003e Eliminating mechanical debounce jumpers removes oxidation failure points in high-humidity or elevated-temperature cabinets.\u003c\/li\u003e\n\u003cli\u003e\n\u003cstrong\u003eThermal Derating Awareness:\u003c\/strong\u003e Maintain cabinet humidity below 45% noncondensing whenever internal enclosure temperatures approach the 70°C upper threshold.\u003c\/li\u003e\n\u003c\/ul\u003e\n\u003ch3\u003e\u003cstrong\u003eCompatibility \u0026amp; Migration Guidelines\u003c\/strong\u003e\u003c\/h3\u003e\n\u003cul\u003e\n\u003cli\u003e\n\u003cstrong\u003eLegacy Replacement Path:\u003c\/strong\u003e Serves as a direct functional upgrade for older \u003cstrong style=\"color: #0056b3;\"\u003eIMDSI02\u003c\/strong\u003e modules in existing 24 VDC field circuits, provided system logic does not require custom jumper-selectable debounce intervals.\u003c\/li\u003e\n\u003cli\u003e\n\u003cstrong\u003eController Interoperability:\u003c\/strong\u003e Fully supported across \u003cstrong style=\"color: #0056b3;\"\u003eBailey Net 90\u003c\/strong\u003e, \u003cstrong style=\"color: #0056b3;\"\u003eINFI 90\u003c\/strong\u003e, and \u003cstrong style=\"color: #0056b3;\"\u003eHarmony\u003c\/strong\u003e racks managed by MFP or LMM processors.\u003c\/li\u003e\n\u003c\/ul\u003e\n\u003ch3\u003e\u003cstrong\u003ePackage Contents\u003c\/strong\u003e\u003c\/h3\u003e\n\u003cul\u003e\n\u003cli\u003e1 × \u003cstrong style=\"color: #0056b3;\"\u003eABB IMDSI13\u003c\/strong\u003e 16-Channel Digital Slave Input Module\u003c\/li\u003e\n\u003cli\u003eAnti-static protective packaging\u003c\/li\u003e\n\u003c\/ul\u003e\n\u003ch3\u003e\u003cstrong\u003eFrequently Asked Questions (FAQ)\u003c\/strong\u003e\u003c\/h3\u003e\n\u003cp\u003e\u003cstrong\u003eQ1: What critical hardware difference must engineers check before replacing an IMDSI02 with the IMDSI13?\u003c\/strong\u003e\u003c\/p\u003e\n\u003cp\u003eA1: Verify that your field circuits operate exclusively at 24 VDC and that your process logic does not depend on hardware-adjustable debounce jumpers, as the \u003cstrong style=\"color: #0056b3;\"\u003eIMDSI13\u003c\/strong\u003e has no user-configurable jumpers.\u003c\/p\u003e\n\u003cp\u003e\u003cstrong\u003eQ2: Why might a 24 VDC field contact fail to register a clean logic transition on this module?\u003c\/strong\u003e\u003c\/p\u003e\n\u003cp\u003eA2: Voltage drop across long field wiring can pull the signal below the 16.8 VDC minimum turn-on threshold; measure terminal voltage under load to ensure at least 4 mA flows at 14.7 VDC or higher.\u003c\/p\u003e\n\u003cp\u003e\u003cstrong\u003eQ3: How does the 13 VDC maximum turn-off specification protect against induced AC noise on field cables?\u003c\/strong\u003e\u003c\/p\u003e\n\u003cp\u003eA3: The 3.8 VDC hysteresis band between the 16.8 VDC turn-on and 13 VDC turn-off thresholds prevents rapid contact chatter caused by electromagnetic induction in crowded cable trays.\u003c\/p\u003e\n\u003cp\u003e\u003cstrong\u003eQ4: Can this module be installed in cabinets located in corrosive chemical processing areas?\u003c\/strong\u003e\u003c\/p\u003e\n\u003cp\u003eA4: The \u003cstrong style=\"color: #0056b3;\"\u003eIMDSI13\u003c\/strong\u003e is rated for ISA S71.04 Class LA, LB, LC Level 1 noncorrosive environments, so cabinets in harsh chemical zones require positive-pressure air purging or chemical filtration.\u003c\/p\u003e\n\u003cp\u003e\u003cstrong\u003eQ5: Does the IMDSI13 require external termination units to connect field wiring?\u003c\/strong\u003e\u003c\/p\u003e\n\u003cp\u003eA5: Yes, like all \u003cstrong style=\"color: #0056b3;\"\u003eINFI 90 OPEN\u003c\/strong\u003e rack I\/O cards, field wires terminate onto a compatible rear or remote Termination Unit (TU) linked via standard ribbon cables.\u003c\/p\u003e\n\u003cp\u003e\u003cimg src=\"https:\/\/cdn.shopify.com\/s\/files\/1\/0722\/7863\/8774\/files\/IMDSI13.png?v=1794813179\" alt=\"\"\u003e\u003c\/p\u003e","brand":"ABB","offers":[{"title":"Default Title","offer_id":68078355579062,"sku":"IMDSI13","price":109.0,"currency_code":"USD","in_stock":true}],"thumbnail_url":"\/\/cdn.shopify.com\/s\/files\/1\/0722\/7863\/8774\/files\/IMDSI13-1.jpg?v=1794813166","url":"https:\/\/www.plcsparehub.com\/products\/imdsi13-abb-infi-90-digital-slave-input-module-16-ch-24vdc","provider":"Global PLC Spare Hub","version":"1.0","type":"link"}