{"product_id":"ge-fanuc-ic694mdl753-pacsystems-rx3i-dc-voltage-output-module","title":"IC694MDL753 PACSystems RX3i Positive Logic Output Module | 12\/24VDC","description":"\u003ch3\u003e\u003cstrong\u003eIC694MDL753 | GE Fanuc PACSystems RX3i High-Density Positive Logic Output Module\u003c\/strong\u003e\u003c\/h3\u003e\n\u003cp\u003eThe \u003cstrong\u003eGE Fanuc IC694MDL753\u003c\/strong\u003e is a 32-point high-density discrete output module for the PACSystems RX3i platform. It provides 12\/24 VDC positive logic outputs for industrial control applications.\u003c\/p\u003e\n\u003cp\u003eThe module organizes its 32 output channels into four independent groups. Each group contains eight output points, supporting distributed load connections within one I\/O module.\u003c\/p\u003e\n\u003cp\u003eEach channel supports up to \u003cstrong\u003e0.5 A output current\u003c\/strong\u003e. The module provides a maximum output response time of \u003cstrong\u003e0.5 ms\u003c\/strong\u003e for both ON and OFF transitions.\u003c\/p\u003e\n\u003cp\u003eOriginally developed under GE Intelligent Platforms, this product belongs to the GE Fanuc RX3i hardware family. Emerson Automation is the current platform brand.\u003c\/p\u003e\n\u003ch3\u003e\u003cstrong\u003e01 | Hardware Identity and System Architecture\u003c\/strong\u003e\u003c\/h3\u003e\n\u003ctable\u003e\n\u003ctbody\u003e\n\u003ctr\u003e\n\u003ctd\u003e\u003cstrong\u003eBrand\u003c\/strong\u003e\u003c\/td\u003e\n\u003ctd\u003eGE Fanuc \/ Emerson\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003e\u003cstrong\u003eManufacturer\u003c\/strong\u003e\u003c\/td\u003e\n\u003ctd\u003eGE Intelligent Platforms (historical); Emerson Automation (current)\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003e\u003cstrong\u003eModel\u003c\/strong\u003e\u003c\/td\u003e\n\u003ctd\u003e\u003cstrong\u003eIC694MDL753\u003c\/strong\u003e\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003e\u003cstrong\u003eProduct Series\u003c\/strong\u003e\u003c\/td\u003e\n\u003ctd\u003ePACSystems RX3i\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003e\u003cstrong\u003eProduct Type\u003c\/strong\u003e\u003c\/td\u003e\n\u003ctd\u003eHigh-Density Discrete Output Module\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003e\u003cstrong\u003eOutput Configuration\u003c\/strong\u003e\u003c\/td\u003e\n\u003ctd\u003ePositive Logic \/ Sourcing\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003e\u003cstrong\u003eNumber of Output Points\u003c\/strong\u003e\u003c\/td\u003e\n\u003ctd\u003e32\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003e\u003cstrong\u003eNumber of Output Groups\u003c\/strong\u003e\u003c\/td\u003e\n\u003ctd\u003e4\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003e\u003cstrong\u003ePoints per Group\u003c\/strong\u003e\u003c\/td\u003e\n\u003ctd\u003e8\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003e\u003cstrong\u003eNominal Operating Voltage\u003c\/strong\u003e\u003c\/td\u003e\n\u003ctd\u003e12\/24 VDC\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003e\u003cstrong\u003eInstallation Location\u003c\/strong\u003e\u003c\/td\u003e\n\u003ctd\u003eRX3i PACSystems I\/O Slot\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003e\u003cstrong\u003eModule Occupancy\u003c\/strong\u003e\u003c\/td\u003e\n\u003ctd\u003e1 I\/O slot\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003c\/tbody\u003e\n\u003c\/table\u003e\n\u003ch3\u003e\u003cstrong\u003e02 | Output Characteristics and Electrical Performance\u003c\/strong\u003e\u003c\/h3\u003e\n\u003cp\u003eThe module uses positive logic switching to supply DC voltage to connected field loads. Its four-group architecture supports organized distribution of output circuits.\u003c\/p\u003e\n\u003ctable\u003e\n\u003ctbody\u003e\n\u003ctr\u003e\n\u003ctd\u003e\u003cstrong\u003eOutput Voltage Range\u003c\/strong\u003e\u003c\/td\u003e\n\u003ctd\u003e10.2–28.8 VDC\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003e\u003cstrong\u003eNominal Output Voltage\u003c\/strong\u003e\u003c\/td\u003e\n\u003ctd\u003e12\/24 VDC\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003e\u003cstrong\u003eOutput Current per Point\u003c\/strong\u003e\u003c\/td\u003e\n\u003ctd\u003e0.5 A maximum\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003e\u003cstrong\u003eMaximum Output Current per Group\u003c\/strong\u003e\u003c\/td\u003e\n\u003ctd\u003e4 A\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003e\u003cstrong\u003eGroup Common Pin Rating\u003c\/strong\u003e\u003c\/td\u003e\n\u003ctd\u003e3 A maximum\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003e\u003cstrong\u003eSwitching Current per Group\u003c\/strong\u003e\u003c\/td\u003e\n\u003ctd\u003e3 A maximum\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003e\u003cstrong\u003eInrush Current\u003c\/strong\u003e\u003c\/td\u003e\n\u003ctd\u003e5.4 A for 10 ms\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003e\u003cstrong\u003eON-State Voltage Drop\u003c\/strong\u003e\u003c\/td\u003e\n\u003ctd\u003e0.3 VDC maximum\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003e\u003cstrong\u003eOFF-State Leakage Current\u003c\/strong\u003e\u003c\/td\u003e\n\u003ctd\u003e0.1 mA maximum\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003e\u003cstrong\u003eMaximum ON Response Time\u003c\/strong\u003e\u003c\/td\u003e\n\u003ctd\u003e0.5 ms\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003e\u003cstrong\u003eMaximum OFF Response Time\u003c\/strong\u003e\u003c\/td\u003e\n\u003ctd\u003e0.5 ms\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003e\u003cstrong\u003eBackplane Current Consumption\u003c\/strong\u003e\u003c\/td\u003e\n\u003ctd\u003e260 mA maximum at 5 VDC\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003c\/tbody\u003e\n\u003c\/table\u003e\n\u003cp\u003e\u003cstrong\u003eLoad design consideration:\u003c\/strong\u003e The per-point, group, and common-pin current ratings impose separate limitations. Engineers must observe the applicable limits simultaneously when calculating the output load.\u003c\/p\u003e\n\u003ch3\u003e\u003cstrong\u003e03 | Four-Group Output Distribution\u003c\/strong\u003e\u003c\/h3\u003e\n\u003cp\u003eThe 32 output points follow a four-group arrangement. Each group contains eight independently controlled channels.\u003c\/p\u003e\n\u003cul\u003e\n\u003cli\u003e\n\u003cstrong\u003eGroup 1:\u003c\/strong\u003e Eight positive logic output channels.\u003c\/li\u003e\n\u003cli\u003e\n\u003cstrong\u003eGroup 2:\u003c\/strong\u003e Eight positive logic output channels.\u003c\/li\u003e\n\u003cli\u003e\n\u003cstrong\u003eGroup 3:\u003c\/strong\u003e Eight positive logic output channels.\u003c\/li\u003e\n\u003cli\u003e\n\u003cstrong\u003eGroup 4:\u003c\/strong\u003e Eight positive logic output channels.\u003c\/li\u003e\n\u003c\/ul\u003e\n\u003cp\u003eThis arrangement supports separate load circuits within one module. Engineers can plan different DC load circuits across groups, subject to the specified voltage and current limitations.\u003c\/p\u003e\n\u003cp\u003eFor example, a control cabinet may allocate separate groups to valve solenoids, relay interfaces, indicator circuits, and auxiliary actuators. Each circuit requires an independent load calculation.\u003c\/p\u003e\n\u003ch3\u003e\u003cstrong\u003e04 | Isolation and Electrical Protection\u003c\/strong\u003e\u003c\/h3\u003e\n\u003cp\u003eElectrical isolation helps separate the field wiring from the PLC backplane. Group isolation also supports the electrical separation requirements of the output architecture.\u003c\/p\u003e\n\u003ctable\u003e\n\u003ctbody\u003e\n\u003ctr\u003e\n\u003ctd\u003e\u003cstrong\u003eField-to-Backplane Isolation\u003c\/strong\u003e\u003c\/td\u003e\n\u003ctd\u003e250 VAC continuous; 1500 VAC for 1 minute\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003e\u003cstrong\u003eField-to-Frame Ground Isolation\u003c\/strong\u003e\u003c\/td\u003e\n\u003ctd\u003eOptical isolation; 250 VAC continuous, 1500 VAC for 1 minute\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003e\u003cstrong\u003eGroup-to-Group Isolation\u003c\/strong\u003e\u003c\/td\u003e\n\u003ctd\u003e50 VAC continuous; 500 VAC for 1 minute\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003e\u003cstrong\u003eOutput Logic\u003c\/strong\u003e\u003c\/td\u003e\n\u003ctd\u003ePositive Logic\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003e\u003cstrong\u003eOFF-State Leakage\u003c\/strong\u003e\u003c\/td\u003e\n\u003ctd\u003e0.1 mA maximum\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003c\/tbody\u003e\n\u003c\/table\u003e\n\u003cp\u003eObserve the specified isolation limits when designing field wiring. Do not treat group isolation as permission to exceed the rated voltage between circuits.\u003c\/p\u003e\n\u003ch3\u003e\u003cstrong\u003e05 | Backplane Consumption and Status Monitoring\u003c\/strong\u003e\u003c\/h3\u003e\n\u003cp\u003eThe module draws its internal operating power from the RX3i backplane. Field-side power supplies provide the voltage required by the connected output loads.\u003c\/p\u003e\n\u003cul\u003e\n\u003cli\u003e\n\u003cstrong\u003eBackplane voltage:\u003c\/strong\u003e 5 VDC.\u003c\/li\u003e\n\u003cli\u003e\n\u003cstrong\u003eMaximum backplane current:\u003c\/strong\u003e 260 mA.\u003c\/li\u003e\n\u003cli\u003e\n\u003cstrong\u003eGroup consumption at 24 VDC:\u003c\/strong\u003e 16.5 mA maximum per group with all eight outputs ON.\u003c\/li\u003e\n\u003cli\u003e\n\u003cstrong\u003eGroup consumption at 12 VDC:\u003c\/strong\u003e 9.6 mA maximum per group with all eight outputs ON.\u003c\/li\u003e\n\u003cli\u003e\n\u003cstrong\u003eChannel indication:\u003c\/strong\u003e 32 individual LED indicators.\u003c\/li\u003e\n\u003c\/ul\u003e\n\u003cp\u003eThe 32 LEDs provide individual output status indication. Technicians can compare commanded output states with visible channel indications during commissioning and troubleshooting.\u003c\/p\u003e\n\u003cp\u003eLED status alone does not confirm that a field load receives the correct voltage. Use electrical measurements when investigating output circuit problems.\u003c\/p\u003e\n\u003ch3\u003e\u003cstrong\u003e06 | Wiring Interface and Cable Compatibility\u003c\/strong\u003e\u003c\/h3\u003e\n\u003cp\u003eThe \u003cstrong\u003eIC694MDL753\u003c\/strong\u003e uses two 24-pin connector interfaces. These interfaces support compatible pre-wired cables or suitable user-built wiring assemblies.\u003c\/p\u003e\n\u003ctable\u003e\n\u003ctbody\u003e\n\u003ctr\u003e\n\u003ctd\u003e\u003cstrong\u003eConnector Arrangement\u003c\/strong\u003e\u003c\/td\u003e\n\u003ctd\u003eTwo male 24-pin connector interfaces\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003e\u003cstrong\u003eConnector Type\u003c\/strong\u003e\u003c\/td\u003e\n\u003ctd\u003eFujitsu FCN-365P024-AU compatible\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003e\u003cstrong\u003eCompatible Cable 1\u003c\/strong\u003e\u003c\/td\u003e\n\u003ctd\u003eIC694CBL327\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003e\u003cstrong\u003eCompatible Cable 2\u003c\/strong\u003e\u003c\/td\u003e\n\u003ctd\u003eIC694CBL328\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003e\u003cstrong\u003eWiring Configuration\u003c\/strong\u003e\u003c\/td\u003e\n\u003ctd\u003ePositive Logic\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003c\/tbody\u003e\n\u003c\/table\u003e\n\u003cp\u003ePositive logic outputs source the positive DC supply to the connected load. The load return connects to the appropriate DC common.\u003c\/p\u003e\n\u003cp\u003eBefore wiring, verify connector pin assignments and group common connections. Follow the RX3i installation documentation for terminal mapping and field power distribution.\u003c\/p\u003e\n\u003ch3\u003e\u003cstrong\u003e07 | Installation and Commissioning Procedure\u003c\/strong\u003e\u003c\/h3\u003e\n\u003cp\u003eThe module occupies one RX3i I\/O slot. It supports installation in compatible local or remote I\/O racks.\u003c\/p\u003e\n\u003col\u003e\n\u003cli\u003e\n\u003cstrong\u003eCheck rack compatibility:\u003c\/strong\u003e Verify the chassis supports the selected RX3i I\/O configuration.\u003c\/li\u003e\n\u003cli\u003e\n\u003cstrong\u003eInspect the module:\u003c\/strong\u003e Check the connector interfaces and module housing.\u003c\/li\u003e\n\u003cli\u003e\n\u003cstrong\u003eConfirm slot assignment:\u003c\/strong\u003e Verify the intended I\/O slot in the hardware configuration.\u003c\/li\u003e\n\u003cli\u003e\n\u003cstrong\u003eInstall the module:\u003c\/strong\u003e Follow the chassis installation procedure.\u003c\/li\u003e\n\u003cli\u003e\n\u003cstrong\u003eConnect field wiring:\u003c\/strong\u003e Use the specified pre-wired cable or approved wiring assembly.\u003c\/li\u003e\n\u003cli\u003e\n\u003cstrong\u003eVerify field power:\u003c\/strong\u003e Confirm the DC supply voltage and polarity.\u003c\/li\u003e\n\u003cli\u003e\n\u003cstrong\u003eCheck output allocation:\u003c\/strong\u003e Match PLC logic addresses with the physical output channels.\u003c\/li\u003e\n\u003cli\u003e\n\u003cstrong\u003eTest individual points:\u003c\/strong\u003e Verify LED indication and field load response.\u003c\/li\u003e\n\u003cli\u003e\n\u003cstrong\u003eCheck group loading:\u003c\/strong\u003e Confirm current limits for every output group.\u003c\/li\u003e\n\u003c\/ol\u003e\n\u003cp\u003e\u003cstrong\u003eCPU STOP mode consideration:\u003c\/strong\u003e The supplied technical references contain conflicting descriptions of output behavior during CPU STOP transitions. Do not assume an automatic ON or OFF state. Verify the configured fault response and applicable hardware manual before commissioning safety-related or interlocked circuits.\u003c\/p\u003e\n\u003ch3\u003e\u003cstrong\u003e08 | Field Diagnostics and Maintenance Recommendations\u003c\/strong\u003e\u003c\/h3\u003e\n\u003cp\u003eOutput faults can originate from the module, field power supply, wiring, or connected load. A systematic diagnostic sequence helps isolate the actual cause.\u003c\/p\u003e\n\u003ctable\u003e\n\u003ctbody\u003e\n\u003ctr\u003e\n\u003ctd\u003e\u003cstrong\u003eObserved Condition\u003c\/strong\u003e\u003c\/td\u003e\n\u003ctd\u003e\u003cstrong\u003eRecommended Engineering Check\u003c\/strong\u003e\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003eOutput LED remains OFF\u003c\/td\u003e\n\u003ctd\u003eCheck PLC logic, channel addressing, and module status.\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003eLED is ON but load does not operate\u003c\/td\u003e\n\u003ctd\u003eMeasure field voltage and inspect the load return path.\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003eUnexpected output voltage drop\u003c\/td\u003e\n\u003ctd\u003eCheck load current and the 0.3 V maximum ON-state drop.\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003eIntermittent load operation\u003c\/td\u003e\n\u003ctd\u003eInspect field wiring, connector seating, and supply stability.\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003eMultiple channels fail together\u003c\/td\u003e\n\u003ctd\u003eInvestigate group common connections and field supply distribution.\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003eExcessive field circuit current\u003c\/td\u003e\n\u003ctd\u003eCheck for short circuits and overloaded output groups.\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003c\/tbody\u003e\n\u003c\/table\u003e\n\u003cp\u003eDuring preventive maintenance, inspect connector contacts and cable insulation. Compare measured output behavior with the PLC program and the expected load characteristics.\u003c\/p\u003e\n\u003ch3\u003e\u003cstrong\u003e09 | System Compatibility and Selection Guidance\u003c\/strong\u003e\u003c\/h3\u003e\n\u003cp\u003eThe \u003cstrong\u003eIC694MDL753\u003c\/strong\u003e belongs to the GE Fanuc PACSystems RX3i discrete output family. Correct selection requires both hardware and electrical compatibility checks.\u003c\/p\u003e\n\u003cul\u003e\n\u003cli\u003e\n\u003cstrong\u003ePlatform:\u003c\/strong\u003e PACSystems RX3i.\u003c\/li\u003e\n\u003cli\u003e\n\u003cstrong\u003eRack position:\u003c\/strong\u003e Compatible local or remote I\/O slot.\u003c\/li\u003e\n\u003cli\u003e\n\u003cstrong\u003eOutput type:\u003c\/strong\u003e 12\/24 VDC positive logic sourcing output.\u003c\/li\u003e\n\u003cli\u003e\n\u003cstrong\u003eChannel count:\u003c\/strong\u003e 32 discrete output points.\u003c\/li\u003e\n\u003cli\u003e\n\u003cstrong\u003eGroup arrangement:\u003c\/strong\u003e Four groups with eight points each.\u003c\/li\u003e\n\u003cli\u003e\n\u003cstrong\u003eWiring:\u003c\/strong\u003e IC694CBL327 or IC694CBL328 compatible cables.\u003c\/li\u003e\n\u003cli\u003e\n\u003cstrong\u003ePower budget:\u003c\/strong\u003e Allow at least the specified maximum 260 mA backplane current.\u003c\/li\u003e\n\u003c\/ul\u003e\n\u003cp\u003eDo not confuse this model with RX3i input modules or negative logic output modules. Their electrical interfaces and field wiring requirements differ.\u003c\/p\u003e\n\u003ch3\u003e\u003cstrong\u003e10 | Five Professional Engineering FAQs\u003c\/strong\u003e\u003c\/h3\u003e\n\u003cp\u003e\u003cstrong\u003eQ1: How should engineers allocate inductive loads across the four output groups?\u003c\/strong\u003e\u003c\/p\u003e\n\u003cp\u003eDistribute loads according to their steady-state current and startup characteristics. Pay particular attention to solenoids, contactors, and other inductive devices. Check suppression requirements and verify that every group remains within its current limits.\u003c\/p\u003e\n\u003cp\u003e\u003cstrong\u003eQ2: Can a PLC output LED confirm that a connected solenoid has received sufficient operating current?\u003c\/strong\u003e\u003c\/p\u003e\n\u003cp\u003eNo. The LED indicates the channel's output status, not the actual current through the load. Measure the field voltage and current when diagnosing solenoid operation. Also inspect the return connection and the condition of the coil.\u003c\/p\u003e\n\u003cp\u003e\u003cstrong\u003eQ3: What is the practical impact of the 0.1 mA maximum OFF-state leakage current?\u003c\/strong\u003e\u003c\/p\u003e\n\u003cp\u003eHigh-impedance electronic loads may respond to small leakage currents. This can produce unexpected voltage readings or faint indicator illumination. Evaluate the load input characteristics when investigating apparent OFF-state activation.\u003c\/p\u003e\n\u003cp\u003e\u003cstrong\u003eQ4: How should engineers handle loads with high startup current?\u003c\/strong\u003e\u003c\/p\u003e\n\u003cp\u003eCompare the load's inrush profile with the specified 5.4 A rating for 10 ms. Also check the continuous channel and group current limits. Consider suitable interposing relays when the load exceeds the module's electrical ratings.\u003c\/p\u003e\n\u003cp\u003e\u003cstrong\u003eQ5: What should technicians investigate when all eight channels in one group stop operating?\u003c\/strong\u003e\u003c\/p\u003e\n\u003cp\u003eStart with the group's common connection and external DC supply. Check the connector contacts and field wiring for loose connections. Then test individual loads and verify the PLC output commands. A shared group fault can affect several channels simultaneously.\u003c\/p\u003e\n\u003ch3\u003e\u003cstrong\u003e11 | Package Contents and Technical Support\u003c\/strong\u003e\u003c\/h3\u003e\n\u003cul\u003e\n\u003cli\u003e1 × \u003cstrong\u003eGE Fanuc IC694MDL753\u003c\/strong\u003e high-density positive logic output module.\u003c\/li\u003e\n\u003cli\u003ePre-wired cables and additional accessories are not included unless specified in the order.\u003c\/li\u003e\n\u003cli\u003e\n\u003cstrong\u003eWarranty:\u003c\/strong\u003e 12 months.\u003c\/li\u003e\n\u003cli\u003e\n\u003cstrong\u003eShipping options:\u003c\/strong\u003e DHL, FedEx, and UPS.\u003c\/li\u003e\n\u003cli\u003e\n\u003cstrong\u003eDispatch arrangement:\u003c\/strong\u003e Typically 24–48 hours, subject to stock confirmation.\u003c\/li\u003e\n\u003cli\u003e\n\u003cstrong\u003eTechnical assistance:\u003c\/strong\u003e Model identification, RX3i compatibility, and wiring verification.\u003c\/li\u003e\n\u003c\/ul\u003e\n\u003ch3\u003e\u003cstrong\u003eRequest a Quotation for IC694MDL753\u003c\/strong\u003e\u003c\/h3\u003e\n\u003cp\u003eLooking for the \u003cstrong\u003eGE Fanuc IC694MDL753\u003c\/strong\u003e 32-point digital output module for your RX3i control system?\u003c\/p\u003e\n\u003cp\u003eSend us your required quantity and application details. Our team can assist with hardware identification, cable compatibility checks, availability confirmation, and quotation arrangements.\u003c\/p\u003e\n\u003cp\u003e\u003cimg src=\"https:\/\/cdn.shopify.com\/s\/files\/1\/0722\/7863\/8774\/files\/IC694MDL753.png?v=1794382674\" alt=\"\"\u003e\u003c\/p\u003e","brand":"GE Fanuc","offers":[{"title":"Default Title","offer_id":45013994012854,"sku":"IC694MDL753","price":163.0,"currency_code":"USD","in_stock":true}],"thumbnail_url":"\/\/cdn.shopify.com\/s\/files\/1\/0722\/7863\/8774\/files\/IC694MDL753-1_59273b45-abe2-4a86-b2cd-1421642e0580.jpg?v=1794382719","url":"https:\/\/www.plcsparehub.com\/products\/ge-fanuc-ic694mdl753-pacsystems-rx3i-dc-voltage-output-module","provider":"Global PLC Spare Hub","version":"1.0","type":"link"}